background image

10/10

504,763M

*2P1010*

*P504763M*

E

2010 Lennox Industries Inc.

Dallas, Texas, USA

MISCELLANEOUS
KITS AND ACCESSORIES

Litho U.S.A.

504,763M 
10/10
Supersedes 04/03

BC OUTDOOR

TEMPERATURE SENSOR

INSTALLATION INSTRUCTIONS FOR THE BC OUTDOOR TEMPERATURE SENSOR (59M05)

USED WITH BUILDING CONTROLLERS ON THE L CONNECTION NETWORK

Shipping and Packing List

Package 1 of 1 contains:

1 − Sensor (A2) assembly
1 − Weathertight fitting
4 − Screws

WARNING

Personal injury, loss of life, or damage to property!

Installation and service must be performed by a
qualified installer or service agency.

Improper installation, adjustment, alteration, ser-
vice or maintenance can cause personal injury, loss
of life, or damage to property.

Application

This sensor provides outdoor temperature data to the
Building Controller, which, based on over− or under−tem-
perature conditions, may use the data to override NCP
scheduled outputs and to set alarms.
The BC Building Controller, when used with the L Connec-
tion Network, controls lights, vent hoods, exhaust fans,
sprinklers, security and fire systems, and other building
equipment.

Location

Install sensor on unit side panel near low voltage entry or
other outdoor location.

Installation

1. Route one twisted pair shielded cable from rooftop unit

to Building Controller.

CABLE TYPE

: Lennox P/N 94L63, Belden type

88761 or equivalent (22AWG stranded or twisted pair,
100% aluminum shield with drain wire, Teflon jacket).

2. Remove knock−out in back of sensor housing. Drill a

hole in unit panel the same size as the knock−out on
the back of the sensor housing.

3. Align knock−outs and install sensor using weathertight

fitting as shown in figure 1 or screws provided in kit.

NOTE − Make sure screws clear any components on
the inside of the unit.

4. Connect sensor to any available input (T1, T2, T3, T4)

on P187 Building Controller terminal block. Connect
the shield drain wire to the input common as shown in
figure 2. Note which inputs are used and refer to Unit
Controller (UC) Software manual to configure override
outputs and alarms.

The temperature will be displayed on the NCP. Refer
to the NCP Software manual to enter a description of
the temperature input.

KNOCK−OUT
IN HOUSING

OPTIONAL

WEATHER-

TIGHT FIT-

TING

SENSOR COVER

(ORIENT DOWN-

WARD)

KNOCK−OUT

IN UNIT

Figure 1. Install Sensor Assembly

T1

T2

T3

T4 

P187

1
2
3
4
5
6
7
8

1

Building

Controller

BC Temperature
Sensors

Figure 2. Wire Outdoor Sensor to P187 on BC1

Sensor Check

Check the temperature displayed on the NCP. If the tem-
perature is incorrect, disconnect the sensor from the BC
and measure the resistance. The resistance should corre-
spond to the temperature as follows:

IMPORTANT: The sensor must be disconnected from the
BC before measuring resistance.

°F

 Resistance

°F

 

Resistance

°F

 

Resistance

−40

335,671

40

26,106

90

7,332

−20

164,959

50

19,904

100

5,826

0

85,323

60

15,313

120

3,756

20

46,218

70

11,884

130

3,047

30

34,566

80

9,298

All values are +/− 2%.

The operating range of each input is −40°F to 130°F (−40°C to 54°C).

Отзывы: