14

12. 

Remove  the  flare  nuts  from  the  connections  on  the 

unit and discard the seal from each of the piping 

connections.

13. 

Slide the flare nuts onto the ends of the field-provided 

refrigerant piping before using a suitable flaring tool to 

flare the end of the copper pipe.

14. Apply recommended HFC-410A refrigerant lubricant to 

the outside of the flared refrigerant lines. 

IMPORTANT

The  compressor  in  this  unit  contains  PVE 

oil  (Polyvinylether).  PVE  oil  is  formulated  for 

 

hydrofluorocarbon  (HFC)  refrigerants,  such  as  HFC-

410A, which this system contains. While it may have 

some miscibility properties with mineral-based oil and 

POE oil (Polyolester), it is not recommended to mix PVE 

oil with any other type of refrigerant oil.

15. 

Align the threaded connections with the flared refrigerant 

lines. Tighten the flare nuts lightly at first to obtain a smooth 

match as illustrated in “Figure 25. Making Connections 

 

(Male to Female Connection)”.

Table 3.   Refrigerant Piping and Indoor Unit 

Connection Sizes

Size 

(Btuh)

Liquid Line 

in.

Suction Line 

in.

36000

3/8

5/8

A

B

CANT ON THE OUTSIDE OF

THE FLARE

MALE FLARE

CONNECTION

Figure 25. Making Connections  

(Male to Female Connection)

16. 

Once  snug,  continue  another  half-turn  on  each  nut 

which should create a leak-free joint. A torque wrench 

may be used to tighten flare nuts using “Table 4. Flare 

Nut Torque Recommendations”. 

Do not over-tighten 

a  flared  joint.  Flared  connections  should  always 

be accessible and must be insulated to prevent 

condensation.

17. After refrigerant piping has been installed and checked 

for leaks, apply insulation over all flared connections.

IMPORTANT

Always use two wrenches when tightening flare nuts to 

avoid twisting refrigerant piping. DO NOT over-tighten 

flare nuts.

TORQUE WRENCH

TO INDOOR

UNIT

TO OUTDOOR UNIT

BACKUP

WRENCH

Figure 26. Tighten Flare Nut

Table 4.   Flare Nut Torque Recommendations

Outside 

Diameter

Recommended 

Torque

No torque wrench available 

Finger tighten and use an 

appropriately sized wrench to 

turn an additional:

Inches

3/8

26 ft.-lb. (35 N)

1/2 turn

5/8

48 ft.-lb. (65 N)

1 full turn

Содержание 3PC036

Страница 1: ...7784 01 Table of Contents General 1 Included Parts 2 Model Number Identification 3 Indoor Outdoor Unit Match Ups 4 Typical System Components 4 System Dimensions 5 Outdoor Units 5 Indoor Units 6 System...

Страница 2: ...er guide 1 ea Wireless control holder with 2 mounting screws 1 Mounting plate with mounting screws and anchors FROM EDGE TO HOLE CENTER 50mm FROM EDGE TO HOLE CENTER 100mm 150 100 100 100 50 50 50 2 2...

Страница 3: ...ominal Cooling Capacity 036 3 tons Refrigerant Type 4 HFC 410A Minor Design Sequence 1 1st Revision 3 P C 036 S 4 S 1 P Series Type 3 3 ton outdoor unit for 3PC 3WMC Wall Mount system OUTDOOR SINGLE Z...

Страница 4: ...Panel Outdoor Unit Power Cable 1 2 3 4 5 6 7 8 9 10 1 2 3 4 6 7 8 9 10 5 Humidity Boost IMPORTANT The refrigerant metering device for this system is located in the outdoor unit This makes it necessary...

Страница 5: ...SIDE VIEW 37 1 4 946 26 1 2 673 40 1 2 1029 GAS VALVE LIQUID VALVE 2 3 8 60 4 1 4 108 3 5 8 92 18 1 8 460 18 457 15 7 8 403 DRAIN HOLE Bottom of Unit 31 7 8 810 15 1 4 387 16 1 8 410 2 7 8 73 1 25 Fi...

Страница 6: ...O HOLE CENTER 70mm BUBBLE LEVEL 150 100 50 2 4 6 RECOMMAND mm inch 100 100 50 50 2 2 4 4 LIQUID GAS mm inch Indoor unit outline Right rear side refrigerant pipe inlet 2 1 2 64 diameter Left rear side...

Страница 7: ...th no obstructions on the other three sides Figure 5 Outdoor Unit Clearances Inches mm Indoor Unit FRONT VIEW Wall Vertical Clearance Clearance to Floor 72 inches 1829 mm Minimum 96 inches 2438 mm Rec...

Страница 8: ...local codes Allow sufficient space around unit for proper operation and maintenance Install unit a minimum of 3 feet 1m away from any antenna power cord line radio telephone security system or interc...

Страница 9: ...sed to these construction materials Installation of Indoor Unit on Wall Mounting Plate 1 A length of field provided flexible condensate piping should be connected to the drain prior to securing the un...

Страница 10: ...tall the unit as far as possible from the prop erty line When possible do not install the unit directly outside a window Glass has a very high level of sound trans mission Install unit level Ground Le...

Страница 11: ...et Figure 14 Outdoor Unit on Brackets above Snow Line Air Outlet Air Inlet 12 in 305 mm 79 in 2007 mm Figure 15 Outdoor Unit Air Flow Obstructed by Snow Figure 16 Avoid Defrost Water Ice Hazard Prevai...

Страница 12: ...low drainage to occur If the heat pump unit is installed on wall mounting bracket insert the provided drain connector into one of the 1 inch 25 mm drain holes and attached a field provided insulated d...

Страница 13: ...using Table 3 Refrigerant Piping and Indoor Unit Connection Sizes on page 14 2 Confirm that you are using the correct diameter piping 3 Determine the necessary piping length required for the applicat...

Страница 14: ...Refrigerant Piping and Indoor Unit Connection Sizes Size Btuh Liquid Line in Suction Line in 36000 3 8 5 8 A B CANT ON THE OUTSIDE OF THE FLARE MALE FLARE CONNECTION Figure 25 Making Connections Male...

Страница 15: ...tested and evacuated to remove any non condensables and moisture from the system Leak Test Use the following procedure to test for system leaks 1 Connect the manifold gauge set and dry nitrogen gas c...

Страница 16: ...e to reattach all electrical box covers after con nections are complete Indoor Unit Indoor unit is powered by the outdoor unit Communication Wiring Use one stranded 3 conduc tor wire to provide power...

Страница 17: ...17 T5 T5 NOTE Recommend to use two core shielded wire Figure 27 3PC036 Outdoor Unit Wiring Diagram...

Страница 18: ...ed 24 hours before unit start up to prevent compressor damage as a result of slugging 1 Inspect all factory and field installed wiring for loose connections 2 Verify that the manifold gauge set is con...

Страница 19: ...e detection PC 00 Error Inverter module IPM error PC 01 Error High or Low voltage protection PC 02 Error High temperature sensed at compressor top PC 03 Error Low or High pressure protection PC 04 Err...

Страница 20: ...he mode button to scroll through the following functions one at a time COOL Select lowest possible temperature HEAT Select highest possible temperature 4 Let each function run for 5 minutes and perfor...

Страница 21: ...e or other various factors Also the Follow Me mode does not operate in this mode NOTE In addition the indoor units do not have a humidistat installed therefore they are unable to determine humidity le...

Страница 22: ...ture Figure 30 Self Clean User Information Indoor Unit Display Remote Control Remote Control Holder Louver Front Panel Air Filter pull up Display window ECO intelligent eye Humidity Boost Figure 31 In...

Страница 23: ...ow out After cleaning the internal blower then keeps operating with hot air to blow dry the evaporator thus preventing the growth of mold and keeping the inside clean When this function is turned on t...

Страница 24: ...r operation use the remote control to activate the unit Unit must be turned off before manual operation To operate your unit manually 1 Locate the MANUAL CONTROL button on the right hand side panel of...

Отзывы: