background image

13

Four Field-provided Anchor Bolts

Figure 21. Securing Outdoor Unit to Slab

Four Field-Provided 

Anchor Bolts

Figure 22. Securing Outdoor Unit to Rails

Securing Outdoor Unit to Hanging Brackets

If  the  outdoor  unit  is  installed  on  field-provided  wall 

mounting brackets, use lag bolts or equivalent to secure 

the outdoor unit to the bracket. Minimum rear clearance 

can be reduced to 6 inches (152 mm) when mounted 

on brackets and with no obstructions on the other three 

sides. Allow for condensate disposal when placing units 

above one another.

Air Outlet

Air Inlet

6 in

152 mm

Figure 23. Securing Outdoor Unit to Brackets

Refrigerant Piping Connections

Field piping consists of two copper lines connecting the 

outdoor unit to the indoor unit. “Table 3. Refrigerant Piping 

and  Indoor  Unit  Connection  Sizes”  on  page  14  lists 

the  connection  sizes.  The  connections  are  made  using 

the provided brass flare nuts at the end of the refrigerant 

piping connections. 

1. 

Choose  the  correct  pipe  sizes  for  your  application 

using 

“Table  3.  Refrigerant  Piping  and  Indoor  Unit 

Connection Sizes” on page 14

.

2. 

Confirm that you are using the correct diameter piping.

3.  Determine the necessary piping length required for the 

application.

4. 

Cut  the  selected  pipes  with  a  pipe  cutter.  Make  the 

cuts  flat  and  smooth  as  illustrated  in  “Figure  24. 

Cutting Piping”.

90

Lean

Crude

Burr

o

 

 

Figure 24. Cutting Piping

5.  Insulate the copper piping.
6. 

Insert a flare nut onto each pipe before flaring. 

7. 

Use “Table 2. Flaring Pipe” to properly flare the pipe.

Table 2.   Flaring Pipe 

Pipe Diameter

Flare Dimension 

A (mm)

Flare Shape

Min

Max

1/4” (6.35)

8.3

8.7

R0.4~0.8

A

45°

90

°

4

-+

3/8” (9.62)

12.0

12.4

1/2” (9.52”

15.4

15.8

5/8” (15.9)

18.6

19.1

3/4” (22.9)

22.9

23.3

8. 

After flaring the pipe, temporarily sealed pipe ends with 

adhesive tape to avoid contaminants from entering the 

pipes.

9.  The seal on the unit refrigerant piping connections 

should remain in place until the last possible moment. 

This will prevent dust or water from getting into the 

refrigerant piping before it is connected.

10. 

CAREFULLY

 adjust refrigerant piping connections to 

suit the application.

11. 

Slowly  loosen  one  of  the  flare  nuts  to  release  the 

factory nitrogen charge from the indoor units only.

Содержание 3PC036

Страница 1: ...7784 01 Table of Contents General 1 Included Parts 2 Model Number Identification 3 Indoor Outdoor Unit Match Ups 4 Typical System Components 4 System Dimensions 5 Outdoor Units 5 Indoor Units 6 System...

Страница 2: ...er guide 1 ea Wireless control holder with 2 mounting screws 1 Mounting plate with mounting screws and anchors FROM EDGE TO HOLE CENTER 50mm FROM EDGE TO HOLE CENTER 100mm 150 100 100 100 50 50 50 2 2...

Страница 3: ...ominal Cooling Capacity 036 3 tons Refrigerant Type 4 HFC 410A Minor Design Sequence 1 1st Revision 3 P C 036 S 4 S 1 P Series Type 3 3 ton outdoor unit for 3PC 3WMC Wall Mount system OUTDOOR SINGLE Z...

Страница 4: ...Panel Outdoor Unit Power Cable 1 2 3 4 5 6 7 8 9 10 1 2 3 4 6 7 8 9 10 5 Humidity Boost IMPORTANT The refrigerant metering device for this system is located in the outdoor unit This makes it necessary...

Страница 5: ...SIDE VIEW 37 1 4 946 26 1 2 673 40 1 2 1029 GAS VALVE LIQUID VALVE 2 3 8 60 4 1 4 108 3 5 8 92 18 1 8 460 18 457 15 7 8 403 DRAIN HOLE Bottom of Unit 31 7 8 810 15 1 4 387 16 1 8 410 2 7 8 73 1 25 Fi...

Страница 6: ...O HOLE CENTER 70mm BUBBLE LEVEL 150 100 50 2 4 6 RECOMMAND mm inch 100 100 50 50 2 2 4 4 LIQUID GAS mm inch Indoor unit outline Right rear side refrigerant pipe inlet 2 1 2 64 diameter Left rear side...

Страница 7: ...th no obstructions on the other three sides Figure 5 Outdoor Unit Clearances Inches mm Indoor Unit FRONT VIEW Wall Vertical Clearance Clearance to Floor 72 inches 1829 mm Minimum 96 inches 2438 mm Rec...

Страница 8: ...local codes Allow sufficient space around unit for proper operation and maintenance Install unit a minimum of 3 feet 1m away from any antenna power cord line radio telephone security system or interc...

Страница 9: ...sed to these construction materials Installation of Indoor Unit on Wall Mounting Plate 1 A length of field provided flexible condensate piping should be connected to the drain prior to securing the un...

Страница 10: ...tall the unit as far as possible from the prop erty line When possible do not install the unit directly outside a window Glass has a very high level of sound trans mission Install unit level Ground Le...

Страница 11: ...et Figure 14 Outdoor Unit on Brackets above Snow Line Air Outlet Air Inlet 12 in 305 mm 79 in 2007 mm Figure 15 Outdoor Unit Air Flow Obstructed by Snow Figure 16 Avoid Defrost Water Ice Hazard Prevai...

Страница 12: ...low drainage to occur If the heat pump unit is installed on wall mounting bracket insert the provided drain connector into one of the 1 inch 25 mm drain holes and attached a field provided insulated d...

Страница 13: ...using Table 3 Refrigerant Piping and Indoor Unit Connection Sizes on page 14 2 Confirm that you are using the correct diameter piping 3 Determine the necessary piping length required for the applicat...

Страница 14: ...Refrigerant Piping and Indoor Unit Connection Sizes Size Btuh Liquid Line in Suction Line in 36000 3 8 5 8 A B CANT ON THE OUTSIDE OF THE FLARE MALE FLARE CONNECTION Figure 25 Making Connections Male...

Страница 15: ...tested and evacuated to remove any non condensables and moisture from the system Leak Test Use the following procedure to test for system leaks 1 Connect the manifold gauge set and dry nitrogen gas c...

Страница 16: ...e to reattach all electrical box covers after con nections are complete Indoor Unit Indoor unit is powered by the outdoor unit Communication Wiring Use one stranded 3 conduc tor wire to provide power...

Страница 17: ...17 T5 T5 NOTE Recommend to use two core shielded wire Figure 27 3PC036 Outdoor Unit Wiring Diagram...

Страница 18: ...ed 24 hours before unit start up to prevent compressor damage as a result of slugging 1 Inspect all factory and field installed wiring for loose connections 2 Verify that the manifold gauge set is con...

Страница 19: ...e detection PC 00 Error Inverter module IPM error PC 01 Error High or Low voltage protection PC 02 Error High temperature sensed at compressor top PC 03 Error Low or High pressure protection PC 04 Err...

Страница 20: ...he mode button to scroll through the following functions one at a time COOL Select lowest possible temperature HEAT Select highest possible temperature 4 Let each function run for 5 minutes and perfor...

Страница 21: ...e or other various factors Also the Follow Me mode does not operate in this mode NOTE In addition the indoor units do not have a humidistat installed therefore they are unable to determine humidity le...

Страница 22: ...ture Figure 30 Self Clean User Information Indoor Unit Display Remote Control Remote Control Holder Louver Front Panel Air Filter pull up Display window ECO intelligent eye Humidity Boost Figure 31 In...

Страница 23: ...ow out After cleaning the internal blower then keeps operating with hot air to blow dry the evaporator thus preventing the growth of mold and keeping the inside clean When this function is turned on t...

Страница 24: ...r operation use the remote control to activate the unit Unit must be turned off before manual operation To operate your unit manually 1 Locate the MANUAL CONTROL button on the right hand side panel of...

Отзывы: