background image

Page 9

Blower Control Board (A54)

Electric shock hazard. Can cause injury or
death. Before attempting to perform any
service or maintenance, turn the electrical
power to unit OFF at disconnect
switch(es). Unit may have multiple power
supplies.

WARNING

!

15CHAX units are equipped with a variable speed motor
that is capable of maintaining a specified CFM throughout
the external static range. A particular CFM can be obtained
by positioning jumpers (

COOL

HEAT

, and 

ADJUST

) on

the blower control board. The HEAT and COOL  jumpers
are labeled A, B, C and D. Each of the numbers corre-
sponds with an air volume (CFM) setting. The 

ADJUST

jumper is labeled Test, −, +, and Norm. The + and − pin set-
tings are used to add or subtract a percentage of the CFM
selected. The Test jumper is used to operate the motor in
the test mode. See figure 8.

Factory settings for the blower speed jumpers are given in
the wiring diagram in figure 7. Figure 8  shows the blower
control board. Use tables 2, 3 and 4 to determine the cor-
rect air volume for operation in heat and cool mode.

The CFM

 LED located on the blower control board flashes

one time per 100 cfm to indicate selected blower speed.
For example, if the unit is operating at 1000 CFM, 

CFM

LED will flash 10 times. If the CFM is 1150, 

CFM

 LED will

flash 11 full times plus one fast or half flash.

At times the light may appear to flicker or glow. This takes
place when the control is communicating with the motor be-
tween cycles. This is normal operation.

Read through the jumper settings section before adjusting
the jumper to obtain the appropriate blower speed.

To change jumper positions, gently pull the jumper off the
pins and place it on the desired set of pins. The following
section outlines the different jumper selections available
and conditions associated with each one. Refer to figure 8.

After the CFM for each application has been determined,
the jumper settings must be adjusted to reflect those given
in tables 2, 3 and 4. From the tables, determine which row
most closely matches the desired CFM. Once a specific
row has been chosen (+, NORMAL, or −), CFM volumes
from other rows cannot be used. Below are descriptions of
the jumper selections.

The variable speed motor slowly ramps up to and down
from the selected air flow during both cooling and heating
demand. This minimizes noise and eliminates the initial
blast of air when the blower is initially energized.

ADJUST

The 

ADJUST

 pins allow the motor to run at normal speed,

approximately 15 percent higher, or approximately 15 per-
cent lower than normal speed. Tables 2, 3 and 4 give three
rows (+, NORMAL, and −) with their respective CFM vol-
umes. Notice that the normal adjustment setting for cool
speed position D in table 2 is  900 CFM. The + adjustment
setting for that position is 1035 CFM and for the − adjust-
ment setting is 765 CFM. After the adjustment setting has
been determined, choose the remaining speed settings
from those offered in the table in that row.

The TEST pin is available to bypass the blower control and
run the motor at approximately 70 percent to make sure
that the motor is operational. This is used mainly in trouble-
shooting. The G terminal must be energized for the motor
to run.

BLOWER CONTROL BOARD (A54)

16−PIN PLUG

(BOARD TO MOTOR)

ADJUST

SELECTOR PINS

(Setting affects both

heating and cooling

modes)

DIAGNOSTIC

LED

HEATING SPEED

SELECTOR PINS

COOLING SPEED

SELECTOR PINS

Figure 8

Содержание 15CHAX?24

Страница 1: ...it If you find any damage im mediately contact the last carrier WARNING Improper installation adjustment alteration service or maintenance can cause property damage person al injury or loss of life In...

Страница 2: ...HAX 24 75 94 117 94 16 29 15CHAX 30 75 94 117 94 16 29 15CHAX 36 83 97 121 104 16 30 15XHAX 42 110 138 163 129 21 33 15CHAX 48 114 139 164 134 21 33 5 15CHAX 60 119 145 171 140 21 33 5 Model No A B C...

Страница 3: ...s under construction the following conditions must be met or the warranty will be void A room thermostat must control the unit The use of fixed jumpers that will provide continuous heating or cooling...

Страница 4: ...of the unit Rigging Setting Unit Exercise care when moving the unit Do not remove any packaging until the unit is near the place of installation An optional lifting lug kit 92M51 may be purchased sep...

Страница 5: ...hat each appliance connected to the common venting system is venting properly step 3 return all doors windows exhaust fans fireplace dampers and any other gas burning appliances to their previous mode...

Страница 6: ...e job They should NOT be sized by simply matching the dimensions of the duct connections on the unit Ducting installed outdoors MUST be insulated and waterproofed CAUTION When fastening duct system to...

Страница 7: ...ower supplies Failure to disconnect all power supplies could result in personal injury or death CAUTION When connecting electrical power and control wir ing to the unit waterproof type connectors MUST...

Страница 8: ...Page 8 Figure 7 15CHAX Series Packaged Electric Units Typical Wiring Diagram...

Страница 9: ...jumper positions gently pull the jumper off the pins and place it on the desired set of pins The following section outlines the different jumper selections available and conditions associated with ea...

Страница 10: ...rformance 0 through 0 80 in w g 0 through 200 Pa External Static Pressure Range AD Jumper Speed Positions AD JUST COOL Speed HEAT Speed CONTINOUS FAN Speed JUST Jumper A B C D A B C D A B C D Jumper S...

Страница 11: ...devices LSOM LED Functions Power LED green Voltage within the range of 19 28VAC is present at the system monitor power connec tion Alert LED yellow Communicates an abnormal system condition through a...

Страница 12: ...ondenser fan is not running 4 Return air duct has substantial leakage 5 If low pressure switch is present see Flash Code 1 info Yellow Alert Flash Code 3 Short Cycling Compres sor is running only brie...

Страница 13: ...l stop System Performance For maximum performance of this cooling system the operating temperatures and pressure should be checked and subcooling determined at Standard ARI test conditions of 82 F out...

Страница 14: ...y lubricated and require no further lubrication Motors should be cleaned yearly to prevent the accumulation of dust and dirt on the windings or motor exterior Coil Dirt and debris should not be allowe...

Отзывы: