Page 7

Unit must be electrically grounded in accordance with local
codes or in the absence of local codes with the National
Electric Code, ANSI/NFPA No. 70 (latest edition) or CSA
C22.2 Part 1 (latest edition).
Power supply to the unit must  comply with all applicable
codes and NEC or CEC. A fused disconnect switch should
be field provided for the unit. The switch must be separate
from all other circuits. If any of the wire supplied with the
unit must be replaced, replacement wire must be of the
type shown on the wiring diagram.
Electrical wiring must be sized to carry minimum circuit
ampacity marked on the unit. 

USE COPPER

CONDUCTORS ONLY

. Each unit must be wired with a

separate branch circuit and be properly fused.

WARNING

Unit is equipped with a single−pole contactor. Line
voltage is present at all components when unit is not
in operation. Disconnect all remote electric power
supplies before opening access panel. Unit may
have multiple power  supplies. Failure to disconnect
all power supplies could result in personal injury or
death.

CAUTION

When connecting electrical power and control wir-
ing to the unit, waterproof type connectors MUST be
used so that water or moisture cannot be drawn into
the unit during normal operation.

WARNING

Unit must be grounded in accordance with national
and local codes. Failure to ground unit properly can
result in personal injury or death.

See figure 6 for typical field wiring connections and figure  7
for typical unit wiring diagram.

Optional Electric Heat

Optional electric heat is available and must be purchased
separately. Install the electric heat section as outlined in

the installation instructions packaged with the electric heat
section.

Thermostat

The room thermostat should be located on an inside wall
where it will not be subject to drafts, sun exposure or heat
from electrical fixtures or appliances. Follow
manufacturer’s instructions enclosed with thermostat for
general installation procedure. Color coded insulated wires
(# 18 AWG) should be used to connect thermostat to unit.

Typical Single−Phase Unit Wiring Connections

Figure 6

Содержание 15CHAX?24

Страница 1: ...it If you find any damage im mediately contact the last carrier WARNING Improper installation adjustment alteration service or maintenance can cause property damage person al injury or loss of life In...

Страница 2: ...HAX 24 75 94 117 94 16 29 15CHAX 30 75 94 117 94 16 29 15CHAX 36 83 97 121 104 16 30 15XHAX 42 110 138 163 129 21 33 15CHAX 48 114 139 164 134 21 33 5 15CHAX 60 119 145 171 140 21 33 5 Model No A B C...

Страница 3: ...s under construction the following conditions must be met or the warranty will be void A room thermostat must control the unit The use of fixed jumpers that will provide continuous heating or cooling...

Страница 4: ...of the unit Rigging Setting Unit Exercise care when moving the unit Do not remove any packaging until the unit is near the place of installation An optional lifting lug kit 92M51 may be purchased sep...

Страница 5: ...hat each appliance connected to the common venting system is venting properly step 3 return all doors windows exhaust fans fireplace dampers and any other gas burning appliances to their previous mode...

Страница 6: ...e job They should NOT be sized by simply matching the dimensions of the duct connections on the unit Ducting installed outdoors MUST be insulated and waterproofed CAUTION When fastening duct system to...

Страница 7: ...ower supplies Failure to disconnect all power supplies could result in personal injury or death CAUTION When connecting electrical power and control wir ing to the unit waterproof type connectors MUST...

Страница 8: ...Page 8 Figure 7 15CHAX Series Packaged Electric Units Typical Wiring Diagram...

Страница 9: ...jumper positions gently pull the jumper off the pins and place it on the desired set of pins The following section outlines the different jumper selections available and conditions associated with ea...

Страница 10: ...rformance 0 through 0 80 in w g 0 through 200 Pa External Static Pressure Range AD Jumper Speed Positions AD JUST COOL Speed HEAT Speed CONTINOUS FAN Speed JUST Jumper A B C D A B C D A B C D Jumper S...

Страница 11: ...devices LSOM LED Functions Power LED green Voltage within the range of 19 28VAC is present at the system monitor power connec tion Alert LED yellow Communicates an abnormal system condition through a...

Страница 12: ...ondenser fan is not running 4 Return air duct has substantial leakage 5 If low pressure switch is present see Flash Code 1 info Yellow Alert Flash Code 3 Short Cycling Compres sor is running only brie...

Страница 13: ...l stop System Performance For maximum performance of this cooling system the operating temperatures and pressure should be checked and subcooling determined at Standard ARI test conditions of 82 F out...

Страница 14: ...y lubricated and require no further lubrication Motors should be cleaned yearly to prevent the accumulation of dust and dirt on the windings or motor exterior Coil Dirt and debris should not be allowe...

Отзывы: