Page 4

If unit coil cannot be mounted away from prevailing winter
winds, a wind barrier should be constructed. Size the barri-
er at least the same height and width as outdoor unit. Mount
barrier 24 inches (610 mm) from the sides of the unit in the
direction of prevailing winds.

wind barrier

inlet air

prevailing winter winds

Rooftop Application

Wind Barrier ConstrucTion

inlet air

inlet air

inlet air

Figure 3

Electrical

In the U.S.A., wiring must conform with current local codes
and the current National Electric Code (NEC). In Canada,
wiring must conform with current local codes and the current
Canadian Electrical Code (CEC).

Refer to the furnace or blower coil installation instructions
for additional wiring application diagrams and refer to unit
nameplate for minimum circuit ampacity and maximum
overcurrent protection size.

WARNING

Unit must be grounded in accordance with national
and local codes.
Electric Shock Hazard.
Can cause injury or death.

 1 − Install line voltage power supply to unit from a properly

sized disconnect switch.

 2 − Ground unit at unit disconnect switch or to an earth

ground.

NOTE − To facilitate conduit, a hole is in the bottom of 
the control box. Connect conduit to the control box us
ing a proper conduit fitting.

NOTE − Units are approved for use only with copper 
conductors.

24V, Class II circuit connections are made in the low 
voltage junction box. Refer to figure 4 for field wiring 
diagram.

NOTE − A complete unit wiring diagram is located in
side the unit control box cover.

 3 − Install room thermostat (ordered separately) on an in-

side wall approximately in the center of the conditioned
area and 5 feet (1.5 m) from the floor. It should not be
installed on an outside wall or where it can be effected
by sunlight, drafts or vibrations.

 4 − Install low voltage wiring from outdoor to indoor unit and

from thermostat to indoor unit. See figures 5 and 6.

Содержание 12HPB Series

Страница 1: ...4 532M 06 04 Supersedes 04 04 Table of Contents 12HPB Outdoor Units 1 Shipping Packing List 1 General Information 1 Unit Dimensions 2 Setting the Unit 3 Electrical 4 Refrigerant Piping 6 Refrigerant M...

Страница 2: ...tion 4 3 8 111 4 3 8 111 4 3 8 111 4 3 8 111 4 3 8 111 compressor coil drain outlets around perimeter of base optional unit stand off kit 4 field installed B C A optional unit stand off kit 4 field in...

Страница 3: ...to allow adequate drainage of defrost water and prevent ice buildup 3 In heavy snow areas do not locate the unit where drift ing will occur The unit base should be elevated above the depth of average...

Страница 4: ...G Unit must be grounded in accordance with national and local codes Electric Shock Hazard Can cause injury or death 1 Install line voltage power supply to unit from a properly sized disconnect switch...

Страница 5: ...power power common common 1st stage aux heat 1st stage aux heat indoor blower compressor Figure 5 R C W1 Y1 O G R C W1 W2 W3 G Outdoor Unit and Blower Unit Thermostat Designations with emergency heat...

Страница 6: ...o the compressor Installing Refrigerant Line During the installation of any heat pump or a c system it is important to properly isolate the refrigerant lines to prevent unnecessary vibration Line set...

Страница 7: ...Line IMPORTANT Refrigerant lines must not contact structure Outside Wall Inside Wall Liquid Line Vapor Line IMPORTANT Refrigerant lines must not contact wall Wood Block Between Studs Strap Sleeve Woo...

Страница 8: ...ire Tie Wire Tie around vapor line only Floor Joist or Roof Rafter Tape or Wire Tie Strap the vapor line to the joist or rafter at 8 ft intervals then strap the liquid line to the vapor line To hang l...

Страница 9: ...Line Metal Sleeve Anchored Heavy Nylon Wire Tie Automotive Muffler Type Hanger Wall Stud Wall Stud Liquid Line Vapor Line Wrapped in Armaflex Strap Liquid Line To Vapor Line Metal Sleeve Figure 9 Out...

Страница 10: ...d line at the indoor coil Refrigerant Metering Device 12HPB units are used in check expansion valve systems only See the Lennox Engineering Handbook for approved TXV match ups and application informat...

Страница 11: ...e wrench 2 Connect gauge to the service port 3 When testing is completed replace service port cap Tighten finger tight then an additional 1 6 turn To Open Service Valve 1 Remove stem cap with an adjus...

Страница 12: ...r use oxygen to pressurize a refrigera tion or air conditioning system Oxygen will explode on contact with oil and could cause personal injury WARNING Danger of explosion Can cause equipment damage in...

Страница 13: ...r port hose from vacuum pump Attach the manifold center port hose to a nitrogen cylin der with pressure regulator set to 150 psig 1034 kPa and purge the hose Open the manifold gauge valves to break th...

Страница 14: ...which charg ing method to use Proceed with the appropriate charg ing procedure Weighing in the Charge TXV Systems Outdoor Temp 65 F 18 C If the system is void of refrigerant or if the outdoor ambient...

Страница 15: ...erature to check liquid line tempera ture Verify the unit charge using the approach method 5 The difference between the ambient and liquid temper atures should match values given in table 6 If the val...

Страница 16: ...ts An amber indicating light simultaneously comes on to remind the homeowner that he is operating in the emergency heat mode Emergency heat is usually used during an outdoor shut down but it should al...

Страница 17: ...mode If the jumper is removed before an addi tional 5 second period has elapsed 7 seconds total the unit will remain in defrost mode until the defrost thermostat opens or 14 minutes have passed If th...

Страница 18: ...lubrication is needed 3 Adjust blower speed for cooling Measure the pressure drop over the coil to determine the correct blower CFM Refer to the unit information service manual for pressure drop tabl...

Отзывы: