17

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

Framing Dimensions for Roof

Pitch 

D

0/12

 

10-1/2 in. 

10-1/2 in.

 

(267 mm)  (267 mm)

6/12

 

10-1/2 in. 

12 in.

 

(267 mm)  (305 mm)

12/12

 

10-1/2 in. 

17-3/4 in.

 

(267 mm)  (451 mm)

Figure 25 

Figure 26 

Figure 28 

Figure 27

If the vent system extends more than 5' (1.5 

m) above the roof flashing, stabilizers may be 

necessary. Additional screws may be used at 

section joints for added stability. Guide wires 

may be attached to the joint for additional sup-

port on multiple joint configurations.

G.

 

Continue installation of horizontal/inclined 

sections -

 Continue with the installation of the 

straight vent sections in horizontal/inclined run 

as described in 

Step C.

 Install support straps 

every 5' (1.52 m) along horizontal/inclined vent 

runs using conventional plumber’s tape. 

It is 

very  important  that  the  horizontal/inclined 

run be maintained in a straight (no dips) and 

slightly elevated plane in a direction away 

from the fireplace 

1/4" per foot (20 mm per 

meter)  of  horizontal  vent

.

  Use  a  carpenter’s 

level to measure from a constant surface and 

adjust the support straps as necessary. 

It is important to maintain the required clear-

ances to combustibles: 1" (25 mm) at all sides 

for all vertical runs; and 3" (76 mm) at the top, 

1" (25 mm) at sides, and 1" (25 mm) at the 

bottom for all horizontal/inclined runs.

F. Change vent direction to horizontal/inclined 

run -

 At transition from or to a horizontal/in-

clined run, install the SV4.5E45 and SV4.5E90 

elbows in the same manner as the straight vent 

sections.  The elbows feature a twist section to 

allow them to be routed about the center axis 

of their initial collar section to align with the 

required direction of the next vent run element. 

Twist elbow sections in a clockwise direction 

only so as to avoid the possiblity of unlocking 

any of the previously connected vent sections.

 

See 

Figure 24

.

E.

 

Support the vertical vent run sections -

Note - 

Proper venting support is very important. 

The weight of the vent must not be supported 

by the fireplace in any degree. 

Support  the  vertical  portion  of  the  venting 

system every 8 feet (2.4m) above the fireplace 

vent outlet. One method of support is by utiliz-

ing field provided support straps (conventional 

plumber's tape). Secure the plumber's tape to 

the  framing  members  with  nails  or  screws. 

Loop the tape around the vent, securing the 

ends  of  the  tape  to  the  framing.  If  desired, 

sheet metal screws #6 x 1/2" length may be 

used to secure the support straps to the vent 

pipe.  See 

Figure 23

Figure 24 

SV4.5E90

(90

°

 Elbow)

8-1/8"

(206 mm)

Swivel Joint

(360

°

 swivel)

4-13/16"

(122 mm)

SV4.5E45

(45

°

 Elbow)

Swivel Joint

(360

°

 swivel)

C

D

Storm

Collar

K. Install the vertical termination - 

The final 

step  involves  installation  of  the  SV4.5CGV-1 

Vertical Termination.  Extend the vent sections 

to the height as shown in the "Vertical vent ter-

mination section" on 

page 6

.  The SV4.5CGV-1 

Vertical Termination (

Figure 28

 ) installs in the 

exact same fashion as any other 

Secure Vent

 

section.  Align the termination over the end of 

the previously installed section, adjusting the 

radial alignment until the four locking dimples 

of the termination are aligned with the inlets of 

the four incline channels of the last vent section.  

Push the termination down until it fully engages, 

then twist the termination clockwise running the 

dimples down and along the incline channels 

until they seat at the end of the channels.

I.

 

Install the roof flashing - 

Extend the vent 

sections through the roof structure. Install the 

roof flashing over the vent section and posi-

tion such that the vent column rises vertically 

(use carpenters level) (

Figure 26

 ). Nail along 

perimeter to secure flashing or adjust roofing 

to overlap the flashing edges at top and sides 

only and trim where necessary. Seal the top 

and both sides of the flashing with waterproof 

caulking.

J. Install the storm collar -

 Install the storm 

collar,  supplied  with  the  flashing,  over  the 

vent/flashing joint. See 

Figure 27

Loosen the 

storm collar screw. Slide collar down until it 

meets the top of the flashing. Tighten the adjust-

ing screw. Apply non-combustible caulking or 

mastic around the circumference of the joint 

to provide a water tight seal.

H.

 

Frame roof opening -

 Identify location for 

vent at the roof. Cut and/or frame opening per 

Roof Framing Chart and 

Figure 25

.

Содержание MPD35PF-NE-B

Страница 1: ...imm diatement votre fournisseur de gaz depuis un voisin Suivez les instructions du fournisseur Si vous ne pouvez rejoindre le fournisseur de gaz appelez le service des incindies L installation et l e...

Страница 2: ...of high surface temperature and should stay away to avoid burns or clothing ignition Lesenfantsetlesadultesdevraient treinfor m sdesdangersqueposentlestemp ratures de surface lev es et se tenir dista...

Страница 3: ...an cause serious injury or death from fire burns explosion or carbon monoxide poisoning Onlytrimkit s suppliedbythemanufacturer shall be used in the installation of this ap pliance Seules les trousses...

Страница 4: ...d width will dimenish 4 for every 1 000 feet of altitude REQUIREMENTS FOR THE COMMON WEALTH OF MASSACHUSETTS Thesefireplacesareapprovedforinstallationin the US state of Massachusetts if the following...

Страница 5: ...ED HOME REQUIREMENTS This appliance may be installed in an aftermar ket permanently located manufactured home and must be installed in accordance with the manufacturer s instructions and the Manufac t...

Страница 6: ...ent Termination Clearances Terminatemultipleventterminationsaccordingto the installation codes listed above and Figures 4 and 5 Note See Figure 36 on Page 21 for the exterior wall recess allowances of...

Страница 7: ...s n i h c a e o t e c n a r a e l C H y l b m e s s a r o t a l u g e r r e t e m t e e f 5 1 f o t h g i e h a n i h t i w m c 1 9 t e e f 3 y l b m e s s a r o t a l u g e r r e t e m e h t e v o b...

Страница 8: ...the unit The appliance may be located onornearconventionalconstructionmaterials However if installed on combustible materials such as carpeting vinyl tile etc a metal or woodbarriercoveringtheentireb...

Страница 9: ...and pre wired 1 Remove the shipping carton Remove the shipping pad exposing the front glass door 2 Open the two latches located under the firebox floor securing the glass door Remove the door by tilt...

Страница 10: ...The typical sequence of installation is outlined below However each installation is unique and may result in variations to the steps described See the page numbers references in the follow ing steps f...

Страница 11: ...hed dimension should be 22 558 mm Inches millimeters Minimum Framing Stud Size is 2 x 4 See side views of fireplace below for gas line inlet location options Fireplace Framing Specifications Center of...

Страница 12: ...aming Specifications Center of gas line is 3 1 8 inches 79 mm up from floor Notes This dimension does not include the addition of drywall to the inside of framing or clearance for the Side Vent Seal C...

Страница 13: ...supplyto theapplianceinvolvesnumerousconsiderations of materials protection sizing locations con trols pressure sediment andmore Certainlyno one unfamiliar and unqualified should attempt sizing or ins...

Страница 14: ...openings in the enclosing wall at any of the joints in the vent pipe Installation of Vent Restrictor A vent restrictor may be needed with this appliance The restrictor is installed in the appliance t...

Страница 15: ...9 2 2 5 2 1 9 1 0 0 1 6 0 7 5 2 3 2 5 7 3 9 1 0 0 0 0 5 5 7 3 2 5 7 9 1 1 0 0 0 5 6 5 1 4 2 5 2 1 0 2 0 0 0 7 0 7 6 4 2 5 0 2 1 0 0 7 0 8 2 5 2 1 2 0 1 0 7 0 8 4 6 2 2 2 0 0 1 7 0 8 6 7 2 3 2 0 0 0 8...

Страница 16: ...age 15 for an aidinselectinglengthcombinations Elbowsare available in 90 and 45 configurations Refer to Figure 24 for the SV4 5E45 and SV4 5E90 elbow dimensional specifications Where required a telesc...

Страница 17: ...n of the venting system every 8 feet 2 4m above the fireplace vent outlet One method of support is by utiliz ing field provided support straps conventional plumber s tape Secure the plumber s tape to...

Страница 18: ...WO 90 DEGREE ELBOWS 40 feet 12 2 meters Maximum uCeiling Firestop Spacer SV4 5VF uWhenusingSecureFlex use Firestop Spacer SF4 5VF uCeiling Firestop Spacer SV4 5VF vWall Firestop Spacer SV4 5HF uCeilin...

Страница 19: ...x use Firestop Spacer SF4 5HF uCeiling Firestop Spacer SV4 5VF uCeiling Firestop Spacer SV4 5VF vWall Firestop Spacer SV4 5HF Table D H H1 Maximum V Minimum feet meter feet meter 5 1 524 Elbow Only 5...

Страница 20: ...ocking any of the previously connected vent sections See Figure 24 on page 15 I Continueinstallationofhorizontal inclined sections Continue with the installation of the straightventsectionsinhorizonta...

Страница 21: ...ll thicknesses L Install Firestop Spacer at exterior wall When using the square termination install SV4 5HF Secure Vent SF4 5HF Secure Flex Firestop Spacerovertheopeningattheexterior sideoftheframing...

Страница 22: ...4 5HF Secure Vent SF4 5HF Secure Flex firestop spacer must be used anytime vent pipe passes through a combustible wall Note Secure Vent components rigid vent pipe and terminal are shown in the figures...

Страница 23: ...revery1 foot of V vertical you are allowed 5 feet of H H1 horizontal run up to a maximum horizontal run of 20 feet Table H H H1 Maximum V Minimum feet meter feet meter 3 0 914 Elbow Only 5 1 524 1 0 3...

Страница 24: ...restop Spacer SV4 5VF uCeiling Firestop Spacer SV4 5VF vWall Firestop Spacer SV4 5HF vWall Firestop Spacer SV4 5HF Figure 41 Side Vent THREE 90 DEGREE ELBOWS Square termination SV4 5HT 2 shown Square...

Страница 25: ...adapter overthepreviouslyinstalledsectionorappliance collar adjusting the radial alignment until the four locking dimples of the adapter are aligned with the inlets of the four incline channels of the...

Страница 26: ...ent une fois l entretien termin CAUTION Donotconnectoptinalcontrolswitch to 120VAC power supply 2 Install the junction box and receptacle outlet to the left of the valve in the front for optional blow...

Страница 27: ...ompliance with local codes A sediment trap is recommended in the gas piping within the home to prevent moisture and debris in the line from damaging the valve These appliances are equipped with a gas...

Страница 28: ...ight until it disengages from the left corner post hole Remove the modesty panel To remove the modesty panel slide the panel forward until it contacts the cabinet bottom panel then lift straight up an...

Страница 29: ...ance beforeyouinstallvermiculite embersandlogs DO NOT attempt to install the logs until the ap plianceinstallationhasbeencompleted thegas lineconnectedandtestedforleaksandtheinitial burner operation h...

Страница 30: ...wool Separate into Quarter Size separate Pieces NOTE DIAGRAMS ILLUSTRATIONS ARE NOT TO SCALE F D Bottom View of Logs in packaging C E A B C F A D Top View of Logs E B Top View of Logs Installed F E A...

Страница 31: ...in Figure 58 Do not use more than is necessary Ensure that the main burner ports remain uncovered by the ember material Note This appliance is provided with enough Glowing Embers for several applicati...

Страница 32: ...sarecool Turnoffallelectricitytotheappliance beforeyouinstallgrate volcanicstone vermiculite embers and logs This appliance is not designed to burn wood Any attempt to do so could cause irreparable da...

Страница 33: ...e Panel see Figure 62 Retrieve the glass door Visually inspect the gasket on the backside of the frame Gasket surface must be clean free of irregularities and seated firmly Position the door in front...

Страница 34: ...shown in the table in Figure 64 2 Light appliance follow lighting procedure on lighting label in control compartment or see the Care and Operation Manual 3 Allow the burner to operate for at least 15...

Страница 35: ...Burner Factory Air Shutter Opening Setting All Models Model Natural Gas Propane Gas MPD35ST PF 1 8 3 2mm 1 4 6 4mm Air Shutter Adjusting Rod Increase Shutter Opening In This Direction Decrease Shutter...

Страница 36: ...errupteur ou le thermostat mural pour liminer la poussi re et les traces de graisse ou d huile Collez l tiquette sur la surface de la plaque de l interrupteur mural qui contr le le foyer Figure A ou d...

Страница 37: ...1 SV4 5SC6 Storm Collar 6 per box H6183 SV4 5HF5 Firestop Spacer 5 rigid H6184 SF4 5HF5 Firestop Spacer 5 flex H2246 SV4 5HF 10 Firestop Spacer Horizon tal rigid 3 1 1 spacing 10 Pack H2247 SV4 5VF 10...

Страница 38: ...HGS Termination Guard for Horizontal Square Termi nation Deluxe 1 pack Ref instr 750 055M H5820 SV4 5HTSK Termination Shroud Guard for Horizontal Square Termination 1 pack ref instr 750246M H5816 750...

Страница 39: ...cabinet panel hole Pull the panel away from the fireplace See Figure 52 on Page 29 WARNING Thisconversionkitshallbeinstalledbyaqualifiedserviceagencyinaccor dance with the manufacturer s instructions...

Страница 40: ...t gas line to free the pilot assembly from the gas line Remove the pilot orifice and replace it with the one provided with the conversion kit Reinstall the pilot assembly by reversing the steps detail...

Страница 41: ...on kit to the rating plate on the appliance Step 11 Turn on gas supply and test for gas leaks b Install the burner as shown in Figure 72 Ensure that the arm of the venturi of the burner is hooked onto...

Страница 42: ...42 NOTE DIAGRAMS ILLUSTRATIONS ARE NOT TO SCALE NOTE THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 43: ...43 NOTE DIAGRAMS ILLUSTRATIONS ARE NOT TO SCALE NOTE THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 44: ...4M REV J 01 2011 1508 Elm Hill Pike Suite 108 Nashville TN 37210 Lennox Hearth Products reserves the right to make changes at any time without notice in design materials specifications prices and also...

Отзывы: