Lennox Hearth Products MPD35PF-NE-B Скачать руководство пользователя страница 16

16

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

First Vent

Component
Align the dimple (four places)

with the opening of the locking

incline channel on appliance

collar.  Twist vent component

clockwise to engage and seal.

Locking

Incline Channel

Dimple

Appliance collar

Vent / Appliance Collar

Connection

Align the dimple (four places) of the

upper vent section with the opening of

the locking incline channel on  the

lower vent section.  Twist vent

component clockwise to engage and

seal until arrow and dimple align.

Locking

Incline Channel

Dimple

Arrow

Connected

Vent Sections

Vent / Vent Section

Connection

Arrow

Arrow

Figure 20 

Figure 21 

Figure 23 

Figure 22 

C.  Attach  vent  components  to  each  other 

-

  Other  vent  sections  may  be  added  to  the 

previously installed section in accordance with 

the  requirements  of  the  vertical  vent  figures 

and tables.  To add another vent component 

to a length of vent run, align the dimpled end 

over the inclined channel end of the previously 

installed section, adjusting the radial alignment 

until the four locking dimples are aligned with 

the  inlets  of  the  four  incline  channels  of  the 

previous section. 

Push the vent component against the previous 

section  until  it  fully  engages,  then  twist  the 

component clockwise running the dimples down 

and along the incline channels until they seat at 

the end of the channels.

This seating position 

is indicated by the alignment of the arrow and 

dimple as shown in

 

Figure 22.

D.

 

Install  firestop/spacer  at  ceiling  -

  When 

using Secure Vent, use SV4.5VF firestop/spacer 

at ceiling joists; when using Secure Flex, use 

SF4.5VF firestop/spacer. If there is living space 

above  the  ceiling  level,  the  firestop/spacer 

must  be  installed  on  the  bottom  side  of  the 

ceiling. If attic space is above the ceiling, the 

firestop/spacer must be installed on the top side 

of the joist. Route the vent sections through the 

framed opening and secure the firestop/spacer 

with 8d nails or other appropriate fasteners at 

each  corner. 

Remember  to  maintain  1"  (25 

mm)  clearance  to  combustibles,  framing 

members,  and  attic  or  ceiling  insulation 

when  running  vertical  chimney  sections. 

Attic insulation shield (96K94) may be used 

to obtain the required clearances indicated 

here. See installation accessories tables on 

pages 37 and 38.

Vertical (Offset) Installation

Analyze  the  vent  routing  and  determine  the 

quantities of vent sections and number of el-

bows required. Refer to 

Vertical Vent Figures 

and Tables on page 15

 to select the type of 

vertical installation desired. Vent sections are 

available  in  net  lengths  of  4-1/2"  (114  mm), 

10-1/2" (267 mm), 22-1/2" (572 mm), 34-1/2" 

(876 mm) and 46-1/2" (1181 mm). Refer to the 

Effective Vent Length Chart on page 15

 for an 

aid in selecting length combinations. Elbows are 

available in 90° and 45° configurations. Refer 

to 

Figure 24

 

for the SV4.5E45 and SV4.5E90 

elbow dimensional specifications.   

Where  required,  a 

telescopic  vent  section  

(SV4.5LA)

  may be used to provide the installer 

with an option in installing in tight and  confined 

spaces or where the vent run made up of fixed 

length pieces develops a joint in a undesirable 

location, or will not build up to the required 

length. The SV4.5LA Telescopic Vent Section 

has an effective length of from 1-1/2" (38 mm) 

to 7-1/2" (191 mm). The SV4.5LA  is fitted with 

a locking inclined channel end (identical to a 

normal vent section component) and a plain end 

with 3 pilot holes. Slip the plain end over the 

locking channel end of  a standard  SV4.5 vent 

component the required distance and secure 

with three screws.

Maintain a minimum 1" (25 mm) clearance to 

combustible materials for all vertical elements. 

Clearances for all horizontal elements are 3"  

(76 mm) on top, 1" (25 mm) on sides and 1"  

(25 mm) on the bottom.

A.

 

Frame ceiling opening -

 Use a plumb line 

from the ceiling above the appliance to locate 

center of the vertical run. Cut and/or frame an 

opening, 10-1/2" x 10-1/2"  (267mm x 267mm) 

inside  dimensions,  about  this  center  mark 

(Figure  20

 

).

To attach a vent component to the appliance 

collar,  align  the  dimpled  end  over  the  collar, 

adjusting  the  radial  alignment  until  the  four 

locking  dimples  are  aligned  with  the  inlet  of 

the four inclined channels on the collar (refer to 

Figure 21

).  Push the vent component against 

the collar until it fully engages, then twist the 

component  clockwise,  running  the  dimples 

down and along the incline channels until they 

seat at the end of the channels.  The unitized 

design  of  the 

Secure  Vent

  components  will 

engage and seal both the inner and outer pipe  

without the need for sealant or screws.  If desired 

a #6 x 1/2" screw may be used at the joint, but 

it is not required as the pipe will securely lock 

when twisted.

Note:

 An elbow may also be attached to the 

appliance collar.  Attach in the same manner 

as you would a vent section. 

B.

 

Attach  vent  components  to  appliance 

-

 

Secure Vent

 SV4.5 direct vent system compo-

nents are unitized concentric pipe components 

featuring positive twist lock connections (see 

Figures 21 and 22

 ).  

All of the appliances covered in this document 

are fitted with collars having locking inclined 

channels. The dimpled end  of the vent com-

ponents fit over the appliance collar to create 

the positive twist lock connection.

1” (25.4 mm) 

Minimum 

Clearance to

Combustibles

8 ft. (2.4 M)

Maximum

v

 SV4.5VF

Firestop / spacer

u

SV4.5SP

Support Plate

u

SV4.5SU

Support Strap

Shown With 

Optional 

Radiant 

Panels

u

Secured 

to Vent with 

Appropriate 

Fasteners

Ceiling

Framing

v

When 

using 

secure 

Flex, use 

Firestop/

Spacer 

SF4.5VF

SV4.5FA or

SV4.5FB Flashing

and SV4.5SC 

Storm Collar

SV4.5CGV-1

Termination

10-1/2" Min. 

(267 mm)

10-1/2" Min. 

(267 mm)

Содержание MPD35PF-NE-B

Страница 1: ...imm diatement votre fournisseur de gaz depuis un voisin Suivez les instructions du fournisseur Si vous ne pouvez rejoindre le fournisseur de gaz appelez le service des incindies L installation et l e...

Страница 2: ...of high surface temperature and should stay away to avoid burns or clothing ignition Lesenfantsetlesadultesdevraient treinfor m sdesdangersqueposentlestemp ratures de surface lev es et se tenir dista...

Страница 3: ...an cause serious injury or death from fire burns explosion or carbon monoxide poisoning Onlytrimkit s suppliedbythemanufacturer shall be used in the installation of this ap pliance Seules les trousses...

Страница 4: ...d width will dimenish 4 for every 1 000 feet of altitude REQUIREMENTS FOR THE COMMON WEALTH OF MASSACHUSETTS Thesefireplacesareapprovedforinstallationin the US state of Massachusetts if the following...

Страница 5: ...ED HOME REQUIREMENTS This appliance may be installed in an aftermar ket permanently located manufactured home and must be installed in accordance with the manufacturer s instructions and the Manufac t...

Страница 6: ...ent Termination Clearances Terminatemultipleventterminationsaccordingto the installation codes listed above and Figures 4 and 5 Note See Figure 36 on Page 21 for the exterior wall recess allowances of...

Страница 7: ...s n i h c a e o t e c n a r a e l C H y l b m e s s a r o t a l u g e r r e t e m t e e f 5 1 f o t h g i e h a n i h t i w m c 1 9 t e e f 3 y l b m e s s a r o t a l u g e r r e t e m e h t e v o b...

Страница 8: ...the unit The appliance may be located onornearconventionalconstructionmaterials However if installed on combustible materials such as carpeting vinyl tile etc a metal or woodbarriercoveringtheentireb...

Страница 9: ...and pre wired 1 Remove the shipping carton Remove the shipping pad exposing the front glass door 2 Open the two latches located under the firebox floor securing the glass door Remove the door by tilt...

Страница 10: ...The typical sequence of installation is outlined below However each installation is unique and may result in variations to the steps described See the page numbers references in the follow ing steps f...

Страница 11: ...hed dimension should be 22 558 mm Inches millimeters Minimum Framing Stud Size is 2 x 4 See side views of fireplace below for gas line inlet location options Fireplace Framing Specifications Center of...

Страница 12: ...aming Specifications Center of gas line is 3 1 8 inches 79 mm up from floor Notes This dimension does not include the addition of drywall to the inside of framing or clearance for the Side Vent Seal C...

Страница 13: ...supplyto theapplianceinvolvesnumerousconsiderations of materials protection sizing locations con trols pressure sediment andmore Certainlyno one unfamiliar and unqualified should attempt sizing or ins...

Страница 14: ...openings in the enclosing wall at any of the joints in the vent pipe Installation of Vent Restrictor A vent restrictor may be needed with this appliance The restrictor is installed in the appliance t...

Страница 15: ...9 2 2 5 2 1 9 1 0 0 1 6 0 7 5 2 3 2 5 7 3 9 1 0 0 0 0 5 5 7 3 2 5 7 9 1 1 0 0 0 5 6 5 1 4 2 5 2 1 0 2 0 0 0 7 0 7 6 4 2 5 0 2 1 0 0 7 0 8 2 5 2 1 2 0 1 0 7 0 8 4 6 2 2 2 0 0 1 7 0 8 6 7 2 3 2 0 0 0 8...

Страница 16: ...age 15 for an aidinselectinglengthcombinations Elbowsare available in 90 and 45 configurations Refer to Figure 24 for the SV4 5E45 and SV4 5E90 elbow dimensional specifications Where required a telesc...

Страница 17: ...n of the venting system every 8 feet 2 4m above the fireplace vent outlet One method of support is by utiliz ing field provided support straps conventional plumber s tape Secure the plumber s tape to...

Страница 18: ...WO 90 DEGREE ELBOWS 40 feet 12 2 meters Maximum uCeiling Firestop Spacer SV4 5VF uWhenusingSecureFlex use Firestop Spacer SF4 5VF uCeiling Firestop Spacer SV4 5VF vWall Firestop Spacer SV4 5HF uCeilin...

Страница 19: ...x use Firestop Spacer SF4 5HF uCeiling Firestop Spacer SV4 5VF uCeiling Firestop Spacer SV4 5VF vWall Firestop Spacer SV4 5HF Table D H H1 Maximum V Minimum feet meter feet meter 5 1 524 Elbow Only 5...

Страница 20: ...ocking any of the previously connected vent sections See Figure 24 on page 15 I Continueinstallationofhorizontal inclined sections Continue with the installation of the straightventsectionsinhorizonta...

Страница 21: ...ll thicknesses L Install Firestop Spacer at exterior wall When using the square termination install SV4 5HF Secure Vent SF4 5HF Secure Flex Firestop Spacerovertheopeningattheexterior sideoftheframing...

Страница 22: ...4 5HF Secure Vent SF4 5HF Secure Flex firestop spacer must be used anytime vent pipe passes through a combustible wall Note Secure Vent components rigid vent pipe and terminal are shown in the figures...

Страница 23: ...revery1 foot of V vertical you are allowed 5 feet of H H1 horizontal run up to a maximum horizontal run of 20 feet Table H H H1 Maximum V Minimum feet meter feet meter 3 0 914 Elbow Only 5 1 524 1 0 3...

Страница 24: ...restop Spacer SV4 5VF uCeiling Firestop Spacer SV4 5VF vWall Firestop Spacer SV4 5HF vWall Firestop Spacer SV4 5HF Figure 41 Side Vent THREE 90 DEGREE ELBOWS Square termination SV4 5HT 2 shown Square...

Страница 25: ...adapter overthepreviouslyinstalledsectionorappliance collar adjusting the radial alignment until the four locking dimples of the adapter are aligned with the inlets of the four incline channels of the...

Страница 26: ...ent une fois l entretien termin CAUTION Donotconnectoptinalcontrolswitch to 120VAC power supply 2 Install the junction box and receptacle outlet to the left of the valve in the front for optional blow...

Страница 27: ...ompliance with local codes A sediment trap is recommended in the gas piping within the home to prevent moisture and debris in the line from damaging the valve These appliances are equipped with a gas...

Страница 28: ...ight until it disengages from the left corner post hole Remove the modesty panel To remove the modesty panel slide the panel forward until it contacts the cabinet bottom panel then lift straight up an...

Страница 29: ...ance beforeyouinstallvermiculite embersandlogs DO NOT attempt to install the logs until the ap plianceinstallationhasbeencompleted thegas lineconnectedandtestedforleaksandtheinitial burner operation h...

Страница 30: ...wool Separate into Quarter Size separate Pieces NOTE DIAGRAMS ILLUSTRATIONS ARE NOT TO SCALE F D Bottom View of Logs in packaging C E A B C F A D Top View of Logs E B Top View of Logs Installed F E A...

Страница 31: ...in Figure 58 Do not use more than is necessary Ensure that the main burner ports remain uncovered by the ember material Note This appliance is provided with enough Glowing Embers for several applicati...

Страница 32: ...sarecool Turnoffallelectricitytotheappliance beforeyouinstallgrate volcanicstone vermiculite embers and logs This appliance is not designed to burn wood Any attempt to do so could cause irreparable da...

Страница 33: ...e Panel see Figure 62 Retrieve the glass door Visually inspect the gasket on the backside of the frame Gasket surface must be clean free of irregularities and seated firmly Position the door in front...

Страница 34: ...shown in the table in Figure 64 2 Light appliance follow lighting procedure on lighting label in control compartment or see the Care and Operation Manual 3 Allow the burner to operate for at least 15...

Страница 35: ...Burner Factory Air Shutter Opening Setting All Models Model Natural Gas Propane Gas MPD35ST PF 1 8 3 2mm 1 4 6 4mm Air Shutter Adjusting Rod Increase Shutter Opening In This Direction Decrease Shutter...

Страница 36: ...errupteur ou le thermostat mural pour liminer la poussi re et les traces de graisse ou d huile Collez l tiquette sur la surface de la plaque de l interrupteur mural qui contr le le foyer Figure A ou d...

Страница 37: ...1 SV4 5SC6 Storm Collar 6 per box H6183 SV4 5HF5 Firestop Spacer 5 rigid H6184 SF4 5HF5 Firestop Spacer 5 flex H2246 SV4 5HF 10 Firestop Spacer Horizon tal rigid 3 1 1 spacing 10 Pack H2247 SV4 5VF 10...

Страница 38: ...HGS Termination Guard for Horizontal Square Termi nation Deluxe 1 pack Ref instr 750 055M H5820 SV4 5HTSK Termination Shroud Guard for Horizontal Square Termination 1 pack ref instr 750246M H5816 750...

Страница 39: ...cabinet panel hole Pull the panel away from the fireplace See Figure 52 on Page 29 WARNING Thisconversionkitshallbeinstalledbyaqualifiedserviceagencyinaccor dance with the manufacturer s instructions...

Страница 40: ...t gas line to free the pilot assembly from the gas line Remove the pilot orifice and replace it with the one provided with the conversion kit Reinstall the pilot assembly by reversing the steps detail...

Страница 41: ...on kit to the rating plate on the appliance Step 11 Turn on gas supply and test for gas leaks b Install the burner as shown in Figure 72 Ensure that the arm of the venturi of the burner is hooked onto...

Страница 42: ...42 NOTE DIAGRAMS ILLUSTRATIONS ARE NOT TO SCALE NOTE THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 43: ...43 NOTE DIAGRAMS ILLUSTRATIONS ARE NOT TO SCALE NOTE THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 44: ...4M REV J 01 2011 1508 Elm Hill Pike Suite 108 Nashville TN 37210 Lennox Hearth Products reserves the right to make changes at any time without notice in design materials specifications prices and also...

Отзывы: