background image

www.lennoxemea.com

COMPACTAIR2

8 - 85 kW

VERTICAL PACKAGED AIR CONDITIONER

INSTALLATION, OPERATING 

AND MAINTENANCE

COMPACTAIR ADV2 IOM-

MIL162E-0920-09/2020

Содержание ADVANCED COMPACTAIR2

Страница 1: ...www lennoxemea com COMPACTAIR2 8 85kW VERTICAL PACKAGED AIR CONDITIONER INSTALLATION OPERATING AND MAINTENANCE COMPACTAIR ADV2 IOM MIL162E 0920 09 2020...

Страница 2: ...RIBUTION 33 4 72 23 20 20 www lennoxemea com Due to LENNOX EMEA ongoing commitment to quality the specifications ratings and dimensions are subject to change without notice and without incurring liabi...

Страница 3: ...ehold name Flexible design solutions to meet your needs and uncompromising attention to detail Engineered to last simple to maintain and Quality that comes as standard For information on local contact...

Страница 4: ...VEL INDICATOR YES NO DATA INPUT COOLING CYCLE Air intake temperature to the outdoor coil Air output temperature to the outdoor coil High pressure Low pressure circuit 1 circuit 2 circuit 1 circuit 2 A...

Страница 5: ...ice We reserve the right to modify our products without notice without obligation to modify previously supplied goods These operating instructions contain useful and important information for the smoo...

Страница 6: ...e admissible operating limits Before switching on the installation always ensure all electrical connections are correct on these elements which are used to isolate the electrical power supply to the c...

Страница 7: ...a shut off valvemust be carried out by a qualified and authorised engineer These proce dures must be carried out with the unit shut down Never work on any of the electrical components until the gener...

Страница 8: ...azier The brazing shall comply with standard NF EN1044 AG107 minimum 30 silver Replacing components Replacement of components shall be carried out using spare parts or using parts approved by LENNOX O...

Страница 9: ...2 36 CAMH060DM2M 400 V 3 Ph 4 27 2 92 2 67 3 31 3 39 3 50 CAMH075DM2M 400 V 3 Ph 3 67 2 83 2 66 2 77 3 02 2 47 CAMH085DM2M 400 V 3 Ph 3 98 2 88 2 57 3 15 3 05 2 54 CASH020SM2M CAIH020SM2M 400 V 3 Ph...

Страница 10: ...indoor section The unit incorporates a high pressure minipresostat and high pressure and low pressure transducers It incorporates dehydrator filter ex pansion system with electronic valves one in the...

Страница 11: ...relay for unit electrical protection Coils Treatment Anticorrosion protection condensor evaporator coils Refrigerant circuit Sevice valves Refrigerant precharged OPTIONS 1 GENERAL CHARACTERISTICS 1 2...

Страница 12: ...62E 0920 09 2020 1 GENERAL CHARACTERISTICS 1 3 PHYSICAL DATA SET Cooling capacity Heating capacity Nominal absorbed power Cold Nominal absorbed power Heating DIMENSIONS Height Width Depth NET WEIGHT O...

Страница 13: ...0 80 80 170 202 202 Installation Manual COMPACTAIR ADV2 IOM MIL162E 0920 09 2020 SET Cooling capacity Heating capacity Nominal absorbed power Cold Nominal absorbed power Heating DIMENSIONS Height Widt...

Страница 14: ...2M CAMH035SM2M CAMH045SM2M kW 10 10 10 15 15 15 20 20 20 A 14 43 14 43 14 43 21 65 21 65 21 65 28 87 28 87 28 87 Installation Manual COMPACTAIR ADV2 IOM MIL162E 0920 09 2020 1 4 ELECTRICAL DATA ELECTR...

Страница 15: ...2M CAMH075DM2M CAMH085DM2M kW 15 15 15 20 20 20 40 40 40 A 21 65 21 65 21 65 28 87 28 87 28 87 57 74 57 74 57 74 Installation Manual COMPACTAIR ADV2 IOM MIL162E 0920 09 2020 1 GENERAL CHARACTERISTICS...

Страница 16: ...res Minimum temperatures Cooling Cycle Operation Indoor temperature Outdoor temperature Heating Cycle Operation Indoor temperature Outdoor Temperature COLD MODE HEAT MODE 25 C 15 C 24 C 12 C Entrance...

Страница 17: ...N PERFORMANCES INDOOR FANS Nominal speed Pressure Pa Airflow m3 h Airflow m3 h Pressure Pa Pressure Pa Pressure Pa Pressure Pa Pressure Pa Min Airflow Max Airflow Nominal 100 80 60 Min Airflow Max Air...

Страница 18: ...OR FANS 1 GENERAL CHARACTERISTICS Pressure Pa Min Airflow Max Airflow Nominal 100 80 60 Airflow m3 h Pressure Pa Pressure Pa Pressure Pa Pressure Pa Pressure Pa Airflow m3 h Airflow m3 h Airflow m3 h...

Страница 19: ...4 BS4 BS2 BS2 Ventilador PLUG FAN Ventilador PLUG FAN Ventilador PLUG FAN Ventilador PLUG FAN CH B11 B12 B13 B13_1 BS1 BS14 BS4 BS2 BS13 BS13_1 Installation Manual COMPACTAIR ADV2 IOM MIL162E 0920 09...

Страница 20: ...1 BS12_1 B22 B21 Acumulador Aspiraci n V lvula expansi n electr nica Filtro secador V lvula 4 v as V lvula retenci n BS1 BS24 B23 BS23 BS2 BS4 Ventilador PLUG FAN Ventilador PLUG FAN Bater a Ventilado...

Страница 21: ..._1 BS12_1 V lvula expansi n electr nica Filtro secador V lvula retenci n BS1 Ventilador PLUG FAN Ventilador PLUG FAN BS4 BS2 BS2 Ventilador PLUG FAN Ventilador PLUG FAN Bater a BS4 CH CH CH B11 B21 B1...

Страница 22: ...73 4 74 8 74 9 82 4 73 7 85 64 1 74 4 70 6 73 4 74 1 72 2 82 4 68 6 85 73 8 84 2 80 4 83 2 83 9 82 2 92 2 78 9 94 63 9 74 3 70 4 73 2 74 2 72 9 82 2 70 4 85 085 Hz 63 125 250 500 1000 2000 4000 8000...

Страница 23: ...CAIH 020 035 045 SM2M STD 1000 1000 1000 1000 All dimensions in millimeters 82 468 340 88 25 26 340 52 928 1445 62 1092 292 1093 29 319 1092 32 316 45 866 35 1410 1527 Z CASH_B_SM2M_STD Folio 1 1 Form...

Страница 24: ...000 1000 1000 All dimensions in millimeters 929 52 340 26 25 88 340 468 82 2813 292 1092 116 1092 222 319 1093 52 1095 249 316 1092 58 1092 251 1380 116 13 921 113 695 113 34 2935 867 1200 867 1496 13...

Страница 25: ...00 1000 1000 CAMH 060 075 085 All dimensions in millimeters 301 1043 126 1043 301 26 735 319 52 1093 1095 249 870 385 462 23 319 1089 58 1092 252 18 699 85 18 26 340 52 929 2813 1380 116 13 113 695 11...

Страница 26: ...he control acts on the servomotor which opens the outside damper and closes the return damper allowing cool outside air to enter the room The damper is proportionally regulated If there is not a great...

Страница 27: ...loose and must be placed in the fan exit FILTRATION OPTIONS INDOOR UNIT 2 CIRCUITS 060 075 085 1 12 OPTIONS Return fan Fan return cabinet is supplied loose FRESH AIR OPTIONS HIGH EFFICIENCY FILTER M5...

Страница 28: ...ttings It is possible to configure until 7 time zones each day with 4 operating modes per zone It can be configured with the DM or during installation by a Lennox technician 1 GENERAL CHARACTERISTICS...

Страница 29: ...amount of CO2 in the air between 0 and 2000 ppm This value varies depending on the occu pancy levels of the space The sensor sends a signal 0 20 mA to the controller to modulate the outside air Envir...

Страница 30: ...ade to the LENNOX Distribution Department for this type of damage cannot be considered under the Guarantee The modifications that the customer makes in the units will be under his responsibility and i...

Страница 31: ...unit always use a forklift and or crane For handling operations of the units of the B BOX range the manual pallet truck can also be used This element can never be used to move the units of the C BOX...

Страница 32: ...red necessary units of the C BOX range 1 Remove the fixing screws and disassemble the cross bedplates as shown in below picture 2 Remove the fixing screws of the unit to the metallic structure 3 Inser...

Страница 33: ...er conditions please consult If the outside temperature in the area where the heat pump unit is to be installed is low or the cycle functioning are too long it may necessary to install an electrical h...

Страница 34: ...gh a siphon with a height difference of 80 mm to avoid drainage problems from the depression formed by the fans The pipes should have an inclination of 2 to ease drainage of condensation Also slightly...

Страница 35: ...ure of 750mm Hg Once a level of 750mm Hg is reached keep the vacuum pump running for at least one hour 7 Refrigerant charge Check TABLE for the amount of refrigerant charge depending on the length and...

Страница 36: ...WAYS INSULATED THE HORIZONTAL LINES MUST BE TIPPED AT LEAST 2 TOWARD THE OUTDOOR UNIT THE MAXIMUM SPEED INSIDE LINES SHOULD NOT BE MORE THAN 15 m seg OUTDOOR UNIT INDOOR UNIT A B C Unit positions L To...

Страница 37: ...s the service valves TABLE 2 EXTRA REFRIGERANT CHARGE R410A BY METER OF COPPER PIPE Liquid Gas gr m The unit is precharged from factory with nytrogene The installer should remove this gas and charge t...

Страница 38: ...supplied with the unit Take into account the current standard for the installation of the unit whether local regional or national standards USE SUPERINMUNIZED DIFFERENTIAL SWITCHES 2 8 1 ELECTRICAL C...

Страница 39: ...ndard for the installation of the unit whether local regional or national standards USE SUPERINMUNIZED DIFFERENTIAL SWITCHES 2 8 ELECTRICAL CONNECTIONS Connection 1 Connection 31 Connection 32 Unit Ba...

Страница 40: ...unit Connection between the DC and the unit must be made using shielded twisted pair cables and shielded where the screens is connected to ground by the side of the electrical panel and with a hose of...

Страница 41: ...anual supplied with the unit Connection between the DC and the unit must be made using shielded twisted pair cables and shielded where the screens is connected to ground by the side of the electrical...

Страница 42: ...ities according the local normative in each country 1 Check that drain pipe connections their fixtures and that the level of the unit is tipped toward the drain 2 Inspect the state of the ducts and gr...

Страница 43: ...th the unit operating check that the fans are turning freely and in the correct direction CHECK THAT THE COMPRESSOR IS ROTATING IN THE CORRECT DIRECTION If you have the option phase rotation indicator...

Страница 44: ...the compressors Monitoring of the pressures draining and filling of the sys tem under pressure shall be carried out using connections provided for this purpose and suitable equipment To pre vent the...

Страница 45: ...nes Modes Night Day Day I DayII b Setpoints per mode 3 Regulation temperature probe selection a Select the regulation probe DC Return Customer etc in the Room Temp Config screen 4 Outside temperature...

Страница 46: ...rical consumptions b Heating mode i Test C Heat if variable speed compressor set speed value 1 Check circuit pressures and temperatures 2 Check electrical consumptions 4 Unit option tests a Electrical...

Страница 47: ...he entrance of the air circulation AIR FILTER The air filter can be removed through the side by sliding it over the rail or downwards See figure For downwards removal remove the two profiles that supp...

Страница 48: ...es indicated on the commissioning sheet Check the position of the crankcase heaters around the compressor if fitted and the proper functioning of it Check the well fixation of the crankcase heaters if...

Страница 49: ...any possible dirt dust filings burrs etc When there is a leak collect what remains of the charge create a vacuum in the unit and completely recharge with new R 410A Refrigerant Brazing should always...

Страница 50: ...nd solutions as the cold cycle but with reference to the coils and indoor fan Unit stops due to low pressure Low pressure switch defective Check the cut off pressure with a pressure gauge and replace...

Страница 51: ...49 Installation Manual COMPACTAIR ADV2 IOM MIL162E 0920 09 2020 NOTES...

Страница 52: ...50 Installation Manual COMPACTAIR ADV2 IOM MIL162E 0920 09 2020 NOTES...

Страница 53: ...www lennoxemea com COMPACTAIR2 8 85kW VERTICAL PACKAGED AIR CONDITIONER INSTALLATION OPERATING AND MAINTENANCE COMPACTAIR ADV2 IOM MIL162E 0920 09 2020...

Страница 54: ...RIBUTION 33 4 72 23 20 20 www lennoxemea com Due to LENNOX EMEA ongoing commitment to quality the specifications ratings and dimensions are subject to change without notice and without incurring liabi...

Отзывы: