The LNL-300XA 13.8 VDC 4 A Battery Monitoring 
Switched Mode PSU

The LNL-300XA is a high-efficiency and cost-effective power supply 
designed for use within a Lenel access control system.

Featuring a regulated 13.8 VDC output, the LNL-300XA supplies 
continuous full rated current to load, and a universal mains voltage input. 
Maximum battery life is assured using deep discharge protection to prevent 
premature battery failure when operating in standby mode for extended 
periods. Two sets of volt-free contacts are provided to signal (i) loss of 
mains and (ii) battery and loss of output faults.

Other features of the LNL-300XA include:

Continuous full-rated current-to-load

Universal mains input voltage 90 to 264 VAC

High-efficiency electronics for reduced running costs and lower 
operating temperatures

Mains transient protection circuit

Lid and removal from wall tamper detection

Green mains present LED

Red fault diagnostic LED

Volt-free contact signaling mains failure (EPS)

Volt-free contact signaling output and batter faults (GEN)

Full electronic short circuit and overload protection on load output 
under mains operation

Individual battery and output fuse protection

Installation Instructions

This unit is only suitable for installation as permanently connected 
equipment. The PSU is NOT SUITABLE for external installation.

This unit must be fed from a mains power source that has a separate 
(approved) disconnect device and is fitted with a fuse or other over-current 
protection device rated at 3 A maximum. Ensure that the disconnect device 
used has appropriate earth fault protection to the applicable standard.

Before connecting the PSU to the mains power source, verify that the 
external disconnect device is OFF.

Install the PSU according to all relevant safety regulations applicable to the 
application. EQUIPMENT MUST BE EARTHED.

Mounting

1.

Mount the PSU securely in correct orientation allowing minimum 
clearance.

Mounting the Power Supply

2.

Route mains and low voltage output cables via different knockouts 
and/or cable entry holes.

Note:

Use bushes and cable glands rated to UL94 HB minimum.

Mains Power-up

1.

Attach the appropriately-rated mains cable (minimum 0.5mm

2

 [3A], 

300/500 VAC) and fasten using cable ties.

2.

Apply mains power. Check for 13.8 VDC on load outputs. Ensure that 
the green Mains LED is on.

3.

Disconnect mains power.

Load Output

1.

Attach the appropriately-rated load cable and fasten using cable ties. 
Note polarity.

2.

Apply mains power. Check green Mains LED is on.

Note:

The red LED on the PSU may flash to indicate that no battery 
has been connected. This is normal.

3.

Verify load is operating correctly.

4.

Disconnect mains power.

Signaling

1.

Connect EPS and GEN fault outputs to appropriate inputs of control 
and indicating equipment (CIE).

Standby Battery

1.

Attach supplied battery cables to terminal block and batteries.

Note:

Ensure correct polarity of battery connections: 

+BAT

 use 

red

 

lead, 

-BAT 

use 

black

 lead.

LNL-300XA 13.8 VDC 4 A Battery Monitoring

Switched Mode PSU Quick Reference