9.9 Calling number sequence depending from position of selection switch I/ II/III
OFF
ON
PROG
*
.
9
.
7
.
1
.
3
7 5
#
.
#
.
*
.
Value
#
.
OFF
ON
PROG
Value
Comment
0
dialling not depend on switch position I/II/III, same calling sequence
(=factory setting)
1
dialling depend on switch position I/II/III, with different calling sequence => the
calling sequence as describe in section 5.2.2
9.10Setting presence verification time out
If there is no activation within this period, an alarm is triggered after a pre programmed time.
OFF
ON
PROG
*
.
9
.
7
.
1
.
3
6 7
#
.
#
.
*
.
Value
#
.
OFF
ON
PROG
Value
Comment
0
Presence verification is switch off
(=factory setting)
6..255
Time –out in steps of 10 min.(min. 60min, max. 42.5h). in case during this time no action detected,
trigger an alarm by sensor monitoring. Value=144 (144x10min = 1440min = 24h)
9.11Wireless sensor
9.11.1 Supervision time-out for (status report monitoring)
Some wireless sensors report their status every 65 minutes (among others low battery, alarm contact, tamper). It
can be happen the detector fails technically, or the radio channel experience interference during reception, or
the detector is on the boarder of reception area. If a detector does not report its status within supervision time
then
will trigger an alarm.
OFF
ON
PROG
*
.
9
.
7
.
1
.
3
2 2
#
.
#
.
*
.
Value
#
.
OFF
ON
PROG
Value
Comment
10..30
Supervision time in steps of 20 min. (max. 10 h).
factory setting=3
0 (30x20 min =600 min =10 h)
Important note:
The supervision time setting not small than 10 (=200min), if doing so radio supervision have
problem
31
Supervision is switch off, that is radio detector will not monitor for failure.
9.11.2 Initial status of contact sensors (NV71)
At power on
initialises the contact status as follow:
OFF
ON
PROG
*
.
9
.
7
.
1
.
3
2 3
#
.
#
.
*
.
Value
#
.
OFF
ON
PROG
Value
Comment
0
Contacts are initialised as closed => Advantage: The sensors are not report as open during start up
=> Disadvantage: if the contact is open, an alarm is triggered after the first status report!
1
Contacts are
i
nitialised as open
(=factory setting)
=> The contact detector are report as open during
start-up. Advantage: If the contact is closed then the contact will be automatically synchronised at
first status report => Disadvantage: if someone enters into the zone prior to the first status report NO
alarm is triggered!
Value
Value
Value
Value