E-Flex
1
2
3
Room Controller
Installation and User Manual
Rev. 1.02 F643
7 January 2020
Страница 1: ...E Flex 1 2 3 Room Controller Installation and User Manual Rev 1 02 F643 7 January 2020 ...
Страница 2: ......
Страница 3: ...ory or 12 months after initial energization of said equipment with the one expiring first given precedence and written notice thereof given to the supplier within 30 days of discovery The sole and exclusive liability of the supplier for Breach of Warranty shall be at its option to replace or repair the product or part concerned F O B its factory or such place as it may designate The warranties sta...
Страница 4: ...Shipment Inspection 4 Mounting 4 Circuit Breaker Protection 4 Terminations and Conduit Access 5 Wiring Requirements 5 High voltage Wiring 5 Low Voltage Wiring 7 CapT2 Station Connections 7 CapT Power Enable Disable 7 Occupancy Input 8 Daylight Input 8 Contact Closure 8 0 10V Outputs 9 DMX Input DMX Model Only 9 FlexNet Input 9 Controller Power Load Capability 9 ...
Страница 5: ...n board Sensor to Zone Configuration SW5 11 Setting the FlexNet ID SW4 ON 1 OFF 0 11 CapT2 Station Configuration 12 Assigning CapT Stations to CapT Signal 12 Assigning Zones to CapT Signal with Jumpers 12 Power Up and Configuration 13 Pre Check 13 Power Up 13 Emergency Test 13 Reset Factory Defaults 13 ...
Страница 6: ...relays with the following ratings o Resistive 50A 277VAC 20A 347VAC o Tungsten 20A 240 VAC 277VAC o Standard Ballast 20A 120VAC 277VAC 347VAC o Electronic Ballast 16A 120VAC 277VAC Up to three 0 10V outputs with current sink of 100mA and will open upon power loss Integrated 24V DC power supply to provide power for sensors and CapT stations Dry contact closure input for timeclock fire alarm or dema...
Страница 7: ...pants of the upcoming change After a delay the LightsOut preset will be activated During this delay any button press at any station will further delay the activation of the LightsOut preset Once the LightsOut preset is in effect light levels may be changed by a user After 15 minutes of no inactivity the LightsOut sequence will start again Occupancy Mode Automatically turn lights ON when the occupa...
Страница 8: ... be subject to tampering by unauthorized personnel Do not use this equipment for anything but intended use Use of accessory equipment not recommended by the manufacturer may cause unsafe conditions Must be serviced by qualified personnel only SAVE THESE INSTRUCTIONS Warnings and Notices Warning This warning indicates situations where there is a risk of electric shock Warning A warning statement in...
Страница 9: ...ck the contents of the shipping container against the packing list and ensure that the order is complete If there are any discrepancies with the contents of the shipment contact Lehigh customer service Mounting Mount the room controller in an accessible location to allow for end use programming or relay bypassing Mount the room controller on a standard 4 X 4 junction box with a depth of 2 1 8 or g...
Страница 10: ...ltage access thru star grommets provided on the top left side If code requires star grommets can be removed to install conduit for low voltage terminations Wiring Requirements High voltage Wiring Line Load AC Wiring Line In HOT Black 12 AWG NEUTRAL White 12 AWG Loads LOAD1 Blue 12 AWG LOAD2 Yellow 12 AWG LOAD3 Red 12 AWG UL924 Models Emergency Load Feed Black 16 AWG Load Yellow 16 AWG Note All lin...
Страница 11: ...E Flex Room Controller Installation and Manual Rev 1 02 6 ...
Страница 12: ... be provided by one source By default the EFRC does not provide power to the stations A jumper JP2 on the room controller enables or disables the 24V power to the EFRC RJ45 connectors See EFRC unit load capability CapT2 stations and the E Flex room controller all have two RJ45 connectors to connect devices together in a system using standard Cat5 cable Maximum cable runs 300 ft CapT Power Enable D...
Страница 13: ... 02 8 Occupancy Input Push in spring connection 24 16 AWG wires and strip length 3 16 in Daylight Input Push in spring connection 24 16 AWG wires and strip length 3 16 in Contact Closure Push in spring connection 24 16 AWG wires and strip length 3 16 in ...
Страница 14: ... analog control wiring from controller to last driver Limiting to a voltage drop of 3V maximum will help ensure meeting IEC 60929 Annex E standard for minimum light level at 1V DMX Input DMX Model Only 24 12 AWG wires strip length in torque 1 7 lbs End of Line termination switch ON only for each end of the cable run FlexNet Input 24 12 AWG wires strip length in torque 3 5 lbs End of Line terminati...
Страница 15: ...r supply load information for the E Flex Controller Load Capability Controller Unit Load Capacity Comments E Flex 1 2 3 3 capacity ULC use an external PS H4019 Input Device Unit Loads Control Device Unit Load Comments Occupancy Sensor 1 Daylight Sensor 25 CapT 25 A unit load is defined as 50mA Note If the total unit loads is greater than the capacity of the EFRC install an LPS 20UL link power supp...
Страница 16: ...FlexNet ID SW4 1234 567 FlexNet ID SW4 1234 567 1 1000 000 26 0101 100 51 1100 110 76 0011 001 2 0100 000 27 1101 100 52 0010 110 77 1011 001 3 1100 000 28 0011 100 53 1010 110 78 0111 001 4 0010 000 29 1011 100 54 0110 110 79 1111 001 5 1010 000 30 0111 100 55 1110 110 80 0000 101 6 0110 000 31 1111 100 56 0001 110 81 1000 101 7 1110 000 32 0000 010 57 1001 110 82 0100 101 8 0001 000 33 1000 010 ...
Страница 17: ...apT signal so they control the same zone s Position 0 CAP1 Position 1 CAP2 Position 2 CAP3 Position 3 CAP4 E Flex relay panels only Assigning Zones to CapT Signal with Jumpers on EFRC The stations are first assigned to one of the CapT signals See above CapT signals are then assigned to control a zone or zones on the room controller Zone assignment can be done without software using hardware jumper...
Страница 18: ...he E Flex room controller includes an integral automatic control relay This relay tracks relay 1 and is capable of up to 3A electronic ballast 120 or 277 VAC On power loss this relay closes to feed the emergency HOT to the emergency load In addition the 0 10V COM signal is also opened so that any 0 10V ballasts go to full brightness All emergency lighting systems should be tested monthly This is a...
Страница 19: ...E Flex Room Controller Installation and Manual Rev 1 02 14 ...