Catalog Number • Numéro de Catalogue • Número de Catálogo: LMRC-102

Country of Origin: Made in China • Pays d’origine: Fabriqué en Chine • País de origen: Hecho en China

LMRC-102-U is BAA and TAA compliant (Product produced in the U.S.)

SPECIFICATIONS

Input Voltage ....  Single Phase 120/230/240/277VAC, 50/60Hz
Load Requirements ......................... Not to exceed 20A total
Each relay rated for up to: 

 Incandescent ........................................20A @ 120VAC 

 Ballast ...........................................20A @ 120/277VAC 

 Motor ............................................ 1Hp @ 120/240VAC
Output ....................................................... 150mA @ 24VDC
DLM Local Network Characteristics: 

Provides low voltage power over Cat 5e cable (LMRJ). 

Supports up to 24 communicating devices, including 4  

LMRC‑10x or LMPL‑101 max per each DLM Local Network. 

Free topology up to 1,000ft of low voltage cable.
Environment: 

 

Operating Temperature .........32° to 104°F (0° to 40°C) 

 

Storage Temperature ...........23° to 176°F (‑5° to 80°C) 

 

Relative Humidity ...............5 to 95% (non condensing)

Patent Pending

PLACEMENT EXAMPLE

This unit is pre-set for Plug n’ Go™ operation, adjustment is optional.

For full operational details, adjustment and more features of the product, see the 

DLM System Installation Guide provided with Wattstopper room controllers, and also 

available at www.legrand.us/wattstopper.

Installation shall be in accordance with all applicable regulations, local and 

NEC codes. 

Wire connections shall be rated suitable for the wire size (lead and 

building wiring) employed. 

For Class 2 DLM devices and device wiring: To be connected to a Class 2 power 

source only. Do not reclassify and install as Class 1, or Power and Lighting Wiring.

WARNING:

 Do not install to cover a junction box having Class 1, 3 or Power and 

Lighting Circuits.

Corner Mount

Occupancy

Sensor

Switch

Daylighting

Sensor

Ceiling Mount

Occupancy

Sensor

Room

Controller

J Box

To

Load

DLM Local Network

(low voltage, Class 2)

LMRJ cables

WARNING:

 TURN THE 

POWER OFF AT THE CIRCUIT 

BREAKER BEFORE WIRING.

CAUTION:

 TO CONNECT A COMPUTER TO THE 

DLM LOCAL NETWORK USE THE LMCI-100.  

NEVER 

CONNECT THE DLM LOCAL NETWORK 

TO AN ETHERNET PORT

 – IT MAY DAMAGE 

COMPUTERS AND OTHER CONNECTED EQUIPMENT.

MOUNTING THE CONTROLLER

The LMRC‑102 room controller can be mounted external to either 

a 4”x 4” or 4‑11/16 x 4‑11/16 junction box, placing it in the plenum 

space or mounted directly inside a 4‑11/16 x 4‑11/16 junction box. 

ATTACHING CABLES

Lin

e

J-Box

Load

J-Boxes

Load

Lin

e

Outside a 4” x 4” or  

4 11/16 x 4‑11/16 box

Inside a 4 11/16 x 4‑11/16 box

Remove rubber jack covers if using all 3 RJ45 receptacles. 

Leave covers in place for all unused receptacles.

Содержание Wattstopper LMRC-102

Страница 1: ...d more features of the product see the DLM System Installation Guide provided with Wattstopper room controllers and also available at www legrand us wattstopper Installation shall be in accordance wit...

Страница 2: ...M device for 3 seconds The red LED on the LMRC 102 begins to blink as does the red LED on ALL other communicating devices connected to the DLM Local Network The red LEDs continue to blink until you ex...

Страница 3: ...JAMAIS CONNECTER LE R SEAU LOCAL DLM UN PORT ETHERNET CELA POURRAIT ENDOMMAGER LES ORDINATEURS AINSI QUE LE MAT RIEL CONNECT AVERTISSEMENT COUPER LE COURANT AU DISJONCTEUR PRINCIPAL AVANT D INSTALLER...

Страница 4: ...terminent automatiquement celui qui devient le contr leur principal et le nombre de charges pour chaque relais du r seau local DLM Le contr leur de pi ce principal est celui qui poss de le plus de rel...

Страница 5: ...ENT mais la charge ne commute pas 1 S assurer que le r seau local DLM n est pas en mode PnL 2 V rifier les connexions avec les contr leurs de pi ce et ou contr leurs de prises INSTRUCCIONES EN ESPA OL...

Страница 6: ...102 FUNCIONAMIENTO DE PLUG N GO PNG Plug n Go apoya la estrategia de control de mayor eficiencia energ tica Por ejemplo si al menos dos cargas un interruptor y un sensor de ocupaci n se conectan a la...

Страница 7: ...El LED azul se muestra atenuado para indicar que el bot n ya no controla la carga que est actualmente ACTIVADA Para desvincular un sensor de ocupaci n presione el bot n de ajuste hacia arriba o abajo...

Страница 8: ...s de d fauts de mat riaux et de fabrication pour une p riode de cinq 5 ans Wattstopper ne peut tre tenu responsable de tout dommage cons cutif caus par ou li l utilisation ou la performance de ce prod...

Отзывы: