Wattstopper

 

®

DLM Enhanced Digital Single Relay Plug Load Controller
Relais numérique simple amélioré – Contrôleur de prises DLM
Controlador DLM de un solo relé para receptáculo de CA

Quick Start Guide • Guide de démarrage rapide • Guía de inicio rápido

No: 28156 – 7/19  rev. 3

Catalog Number • Numéro de Catalogue • Número de Catálogo: LMPL-111-20M

Country of Origin: Made in China • Pays d’origine: Fabriqué en Chine • País de origen: Hecho en China

LMPL-111-20M -U is BAA and TAA compliant (Product produced in the U.S.)

SPECIFICATIONS

Input Voltage ...................................................120VAC, 50/60Hz
Maximum Duplex Receptacle Rating ..................... 120VAC, 20A
Connection to the DLM Local Network ...................2 RJ-45 ports
Output to DLM Local Network ................up to 150mA @ 24VDC
DLM Local Network Characteristics when using LMPL-111-20M:
 

Provides low voltage power over Cat 5e cable (LMRJ);  

 

max current 800mA. Supports up to 64 load addresses, 48  

 

communicating devices, and free topology up to 1,000’  

 

max.Can be only combined with up to 4 LMRC/LMPL-100  

 

series load controllers. All other LMRC/LMPL series can  

 

support more than 4 per room

Metering capability in LMPL-111-20M provides power monitoring 

/-2% of the true value.
Power monitoring capability when used with Wattstopper 

compatible Network Management Software (DLM Dashboard, 

Niagara N4 or BACnet compliant BMS).
Environment: 

 

Operating Temperature ................32° to 131°F (0° to 55°C) 

 

Storage Temperature ................. 23° to 176°F (-5° to 80°C) 

 

Relative Humidity ..................... 5 to 95% (non condensing)

UL 2043 Plenum Rated, ROHS Compliant

This unit is pre-set for Plug n’ Go™ operation, adjustment is 

optional.

Installation shall be in accordance with all applicable regulations, local and 

NEC codes. 

Wire connections shall be rated suitable for the wire size (lead and 

building wiring) employed. 

For Class 2 DLM devices and device wiring: To be connected to a Class 2 power 

source only. Do not reclassify and install as Class 1, or Power and Lighting Wiring.

WARNING:

 TURN THE 

POWER OFF AT THE CIRCUIT 

BREAKER BEFORE WIRING.

CAUTION:

 TO CONNECT A COMPUTER TO THE DLM LOCAL 

NETWORK USE THE LMCI-100.  

NEVER CONNECT THE DLM 

LOCAL NETWORK TO AN ETHERNET PORT

 – IT MAY 

DAMAGE COMPUTERS AND OTHER CONNECTED EQUIPMENT.

MOUNTING, WIRING, AND CONNECTING TO A DLM NETWORK

The LMPL-111-20M plug load controller can be 

mounted external to any junction box with 1/2” 

knockouts, placing it in the plenum space.
The relay is rated for a load of up to 20A. The 

Line (Black) and both Load (Red, and Black with 

White Stripe) wires are #12 AWG. The Neutral 

(White) wiring is #18 AWG.
The LMPL-111-20M communicates to all other 

DLM devices connected to the DLM Local 

Network. Connections shown are for example 

only. The low voltage LMRJ cables can 

connect to any DLM device with an open RJ45 

receptacle. 

LMPL-111-20M

Room Controller

Dimmer

Switch

Corner Mount

Sensor

Ceiling Mount

Sensor

DLM Local Network

Low Voltage

LMRJ Cables

LMRC series

Line

Voltage

Deep J-Box

Loads

Red wire to Switched Receptacle

Line/Hot

Black wire

Neutral

White wire

Switched

Receptacle

Black wire w/white stripe to Unswitched Receptacle

Unswitched

Receptacle

Ground

Ground

This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) this device may not cause harmful 

interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.

NOTE: 

This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits 

are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment 

generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful 

interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be 

required to correct the interference at his own expense.

Warning:

 Any changes or modifications not expressly approved by The Watt Stopper Inc. could void the user’s authority to operate the equipment.