Specifications

Vo l tages: 

DW-100 & DW - 2 0 0  . . . . . . . . . . . . .1 2 0 / 2 3 0 / 2 7 7 VAC, 50/60Hz
DW - 1 0 0 - 3 4 7 . . . . . . . . . . . . . . . . . . . . . . . . . . .3 4 7 VAC, 50/60Hz

Load Limits for each re l a y :

@ 1 2 0 VAC  . . . . . . . . . . . .0-800W tungsten or ballast, 1/6 HP
@230 or 277VAC  . . . . . . . . . . . . . . . . . . . . . . .0-1200W ballast
@ 3 4 7 VAC  . . . . . . . . . . . . . . . . . . . . . . . . . . . . .0-1500W ballast

Load Type Compatibility:

I n ca n d e s cent, fluore s cent, magnetic or ele c t ronic ballast
H o rs e p ower Rating (each re l a y )  . . . . . . . . .1/6 HP @120VAC

Time Delay Adjust m e n t  . . . . . . . . . . . . . . . . . . . .5 to 30 minute s

Wa l k - T h rough Mode  . .3 minutes if no activity after 30 sec.
Te st Mode  . . . 5 sec. at initial power up or DIP switch re s e t

PIR Adjust m e n t . . . . . . . . . . . . . . . . . . .High or Low (DIP switc h )
U l t rasonic Adjust m e n t . . .Minimum to Maximum (trimpot), Off

Fre q u e n c y  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 0 k H z

Light Level Adjust m e n t . . . . . . . . . . . . . . . . . . . . . . .8 fc to 180+fc
A le r t s

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .S e le c ta b le Audible

US Pa tents: 5189393, 5640113,

6617560B2, A4787722

DW - 1 0 0 / DW - 1 0 0 - 3 4 7 / DW - 2 0 0

Dual Te c h n o logy Wall Switc h

O ccupancy Sensor 

D W-100 & DW- 1 0 0 - 3 4 7

D W- 2 0 0

Содержание WattStopper DW-100

Страница 1: ...ballast HorsepowerRating each relay 1 6 HP 120VAC Time Delay Adjustment 5 to 30 minutes Walk Through Mode 3 minutes if no activity after 30 sec Test Mode 5 sec at initial power up or DIP switch reset...

Страница 2: ...oad ON The relays are programmed independently for either Auto ON or Manual ON In either mode the load can be turned ON or OFF using the ON OFF button Load turns ON and OFFautomatically based on occup...

Страница 3: ...to 30 minutes if the space gets heavy usage SmartSet behavior starts immediately and is refined continually as history is collected A Test Mode with a short time delay of 5 seconds is set when DIP sw...

Страница 4: ...Trigger Mode The DW sensor has 4 occupancy trigger options set with DIP switches 5 and 6 Determine the appropriate option using the Trigger matrix In the Trigger Mode DIP switch setting table in order...

Страница 5: ...metalbracket M a tchthem up with the holes in the wall box and tighten 4 Turn the circuit breaker ON Wait one minute then push the ON OFF button for each load and the lights will turn ON 5 Test and ad...

Страница 6: ...sonic PIR Lens DIP SWITCH SETTINGS Call 800 879 8585 for Technical Support Ultrasonic Cones Ultrasonic Sensitivity Adjustment Trimpot Button Hinges Tabs DW 200 shown DW 100 has a single button and the...

Страница 7: ...together the top sides of the buttonassembly Gently pull it away from the unit When the adjustments arecompleted replace the button cap by inserting its hinges into the tabs on the main unit and then...

Страница 8: ...ASP 422 Blank cover plate for 2 gang box ASP 432 Switch option cover plate for 2 gang box Lights do not turn OFF 1 There can be up to a 30 minute time delay after the last motion is detected To verify...

Отзывы: