Cat. No(s): 0 487 72/82
FL4653/53W/63
Technical data sheet: S000102895EN-1
Updated: 31/05/2018
Created: 24/04/2018
1/3
Bedside panel
BUS-SCS
128, av. du Maréchal-de-Lattre-de-Tassigny - 87045 LIMOGES Cedex
Tel: +33(0)5 55 06 87 87 Fax: +33(0)5 55 06 88 88
www.legrand.com
The bedside panel is dedicated to hotels. It has a thermostat function
which can be used on heating and/or air conditioning installations, 5
scenario control units and a “Do not disturb” housekeeping function. It
is possible to display and set the reference temperature, fan speed, and
switch ON with thermal overload protection.
The screen displays the measured ambient temperature or the reference
temperature.
It indicates and can be used to activate the housekeeping information:
- Do Not Disturb
- Make up room: only available on configured version.
It has a proximity sensor which can be disabled by configuration: when
the device detects an approach, it switches from standby state to active
state. The LED brightness level (on standby or active) and the time delay
before returning to standby state can also be set by configuration.
The control & management software is used to view and control the
thermostat. Configuration is possible with the MyHotel_Suite software
on SCS installations which include the MH201 device, or with the Hotel
Room Controller Software on IP installations which include the 0 484 08
or 0 484 12 device.
1. DESCRIPTION
Front view
Rear view
CONTENTS
Page
1. Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
2. Technical characteristics . . . . . . . . . . . . . . . . . .1
3. Standards, certifications and markings . . .1
4. Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
5. Connection diagrams . . . . . . . . . . . . . . . . . . . .2
6. Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
7. Configured version
Cat. No. 0 487 82/FL4663 . . . . . . . . . . . . . . . . .3
2. TECHNICAL CHARACTERISTICS
BUS/SCS power supply:
18 - 27 VDC
Consumption with screen off:
8 mA
Consumption with ultra-bright screen: 30 mA
Operating temperature:
0°C to +40°C
Storage temperature:
-20°C to +70°C
Unit of measurement:
°C or °F
Loads controllable by an actuator:
On/Off
Open/closed
Fan coil unit with 2 tubes and
On/Off valve
IP gateway (centralised HVAC
package)
Fan coil unit with 2 tubes and
proportional valve
Fan coil unit with 4 tubes and
On/Off valve
Fan coil unit with 4 tubes and
proportional valve
Proportional valve
Fan coil unit with 2 tubes and
proportional speed control
Fan coil unit with 4 tubes and
proportional speed control
Protection index:
IP 20, IK 04
Plate and surround colour (standard): Black Cat. No. 0 487 72/FL4653 or
White Cat. No. FL4653W
Key
1. Scenario buttons
2. Heating enabled indicator
(red) Air conditioning enabled
indicator (blue)
3. MODE button: pressing briefly
changes from normal mode (ON)
to protection mode (frost guard
or thermal overload).
A longer press changes
the function (heating/air
conditioning/automatic)
according to the configuration.
4. Measured temperature (SET off)
or reference temperature (SET on)
indicator
5. + button: increases the reference
value
6. – button: decreases the reference
value
7. FAN button: sets the fan speed
(3 automatic)
8. Fan speed indicator (3 levels) +
automatic
9. DND indicator (red LED on: DO
NOT DISTURB)
10. Local contact
11. Connection to the BUS
DEFAULT VALUES
Heating
Air conditioning
Setting interval
3-40°C
3-40°C
Comfort
21°C
25°C
Economy
18°C
28°C
Frost guard
7°C
Thermal overload
35°C
3. STANDARDS, CERTIFICATIONS AND MARKINGS
EN 60669-2-5
CE marked
2
4
8
9
5
6
1
7
3
10 11
4. DIMENSIONS
129
42.4
11.5
93