Emergency Lighting Test Switch
   682083 (Trade)

Cat No 682083 

Emergency Lighting 

Test Switch - Trade

OPERATION

Six Month Test - 90 min

Operate the Key Switch and remove the key. 

The Red pilot LED will flash at once a second. 

During this test the contactor will engage for a period of 90 

m 45 minutes. The extra 45 minutes is designed to al-

low walk through to check the fittings. The total duration of this 

test is 135 minutes (90min+45min)
Push the STOP button to terminate the test.

Commissioning Test - 120min

Hold down the STOP button whilst operating the Key Switch. 

The Red pilot LED will flash once every 2 seconds. 

During this test the contactor will engage for a period of 120 

m 45 minutes. The extra 45 minutes is designed to al-

low walk through to check the fittings. The total duration of this 

test is 165 minutes (45min)
Push the STOP button to terminate the test.

Cat No 682083 

Emergency Lighting 

Test Switch - Trade

WIRING DIAGRAM

When the optional 8 Channel Sensing 

Module Cat No 682085 is required, the link 

between ‘+’ and ‘OP’ must be removed. 

(See wiring Diagram of Sensing Module)

204565 (27.07.2009)

- Power

Up Time

Delay

= 0min

(Red

LED solid

On*)

- Power

Up Time

Delay

= 10 min

(LED

3sec

flash*)

- Test

135min

= Turn

key-switch

only (LED

1sec

flash)

- Test

165min

= Press

Red button

+ turn

key-switch

(LED

0.5sec

flash)

- Abort

Test =

Press

Red button

- Power

Failure

(LED

Off)

* To change

Time

Delay

, turn

key to

stand-by

position

and

press

down

Red button

for 5sec

204623

25483A

Cat No 682083 

Emergency Lighting Test Switch - Trade

Six Month Test - 90 min

Turn the Key-switch to Start Test position to start discharge test.

The Red button LED will flash once a second. 

During this test the contactor will operate for a period of 90 m 45 

minutes. The extra 45 minutes is designed to allow walk through to check the 

fittings. The total duration of this test is 135 minutes (90min+45min)

Push the Red button (STOP) to terminate the test 

(Key on Stand-by position).

Commissioning Test - 120min

Hold down the Red button (STOP) and turn Key-switch to Start Test position 

to start discharge test.

The Red button LED will flash once every 0.5 seconds. 

During this test the contactor will operate for a period of 120 m 45 

minutes. The extra 45 minutes is designed to allow walk through to check the 

fittings. The total duration of this test is 165 minutes (45min)

Push the Red button (STOP) to terminate the test 

(Key on Stand-by position).

Power up Time Delay

Power-up time delay provides additional 10 minutes of emergency lighting 

once the Mains power is restored. This is typically used to allow discharge 

lamps to warm up and regain sufficient light before the emergency lights 

are turned off avoiding a black out period.

Power-up time delay = 0 min 

Red button LED solid On  (Default) 

Power-up time delay = 10 min 

Red button LED flashes every 3 seconds

To change Power-up time delay, turn Key-switch to Stand-by position and 

press down Red button for 5 seconds.

Emergency Lighting Test Switch
   682083 (Trade)

Cat No 682083 

Emergency Lighting 

Test Switch - Trade

OPERATION

Six Month Test - 90 min

Operate the Key Switch and remove the key. 

The Red pilot LED will flash at once a second. 

During this test the contactor will engage for a period of 90 

m 45 minutes. The extra 45 minutes is designed to al-

low walk through to check the fittings. The total duration of this 

test is 135 minutes (90min+45min)
Push the STOP button to terminate the test.

Commissioning Test - 120min

Hold down the STOP button whilst operating the Key Switch. 

The Red pilot LED will flash once every 2 seconds. 

During this test the contactor will engage for a period of 120 

m 45 minutes. The extra 45 minutes is designed to al-

low walk through to check the fittings. The total duration of this 

test is 165 minutes (45min)
Push the STOP button to terminate the test.

Cat No 682083 

Emergency Lighting 

Test Switch - Trade

WIRING DIAGRAM

When the optional 8 Channel Sensing 

Module Cat No 682085 is required, the link 

between ‘+’ and ‘OP’ must be removed. 

(See wiring Diagram of Sensing Module)