11/38
Cat. No(s).: 5 735 04/05
5 735 12/13
KNX
Arteor 4 and 6 touches glass controls
Technical data sheet: S000090563EN-2
Updated: 07/06/2016
Created : 27/07/2015
11. COMMUNICATION OBJECTS DESCRIPTION (continued)
11.1.8 Led behavior on Disable status (continued)
Parameters
Setting
Disable : led behaviour
Off
On
Slow blink
Fast blink
Soft blink
Flash 1
Flash 2
Flash 3
Pulse
The parameter determines the state of Led when a Disable telegram on Channel x is disabled.
Disable : led color
Green
Blue
White
Orange
Gold
Yellow
Turquoise
Cyan
Light blue
Violet
Pink
Purple
The parameter determines the color of Led when a Disable telegram on Channel x is disabled.
Invert enable/disable logic
No
Yes
This parameter determines the type of logic to active/deactive a Disable status.
11.1.9 Use Alarm
A message can activate in red blinking the 4 leds.
No
Alarm is not usable, no accessible communication object.
Yes (makes available the alarm communication object)
When alarm object is active all the LED blinks and the instensity is set to 100%
No.
Object name
Function
Size
Flags
86
Alarm
Alarm
1.010 DP_Start (1 bit )
CW
Alarm activation telegrams are sent via the group address linked with this object
Parameters
Setting
Invert alarm logic
No
Yes
This parameter determines the type of logic to active/deactive an alarm
Disable on Alarm
Yes for all
No for all
Configure Independatly
The parameter determines if the channels are disabled on alarm. If is it chosen “Configure
independently” it is possible to choose one by one the channel behaviour.