background image

   

1/4 

 

 

 

87045 LIMOGES Cedex 

Telephone: 05 55 06 87 87 – Fax: 05 55 06 88 88

 

 

 

Photovoltaic (PV) modular voltage 

Photovoltaic (PV) modular voltage 

Photovoltaic (PV) modular voltage 

Photovoltaic (PV) modular voltage     

surge protectors

surge protectors

surge protectors

surge protectors    

 

Catalogue number(s): 4 141 50/51

Catalogue number(s): 4 141 50/51

Catalogue number(s): 4 141 50/51

Catalogue number(s): 4 141 50/51

    

    

 

 

 

 
 
 
 
 
 
 

4 141  50/51

 

 

CONTENTS                                    

CONTENTS                                    

CONTENTS                                    

CONTENTS                                    PAGES    

1. General features .................................. 1-2 
2. Overall dimensions  ............................. 2 
3. Technical features ............................... 2 
4. Conformity ........................................... 3 
5. Setup ................................................... 3 
6. Accessories ......................................... 3 

7. Maintenance ........................................ 4 
 

 

 

 

 

 

 

 

 

 

 

1. GENERAL FEATURES

1. GENERAL FEATURES

1. GENERAL FEATURES

1. GENERAL FEATURES    

1.1 Brief description

1.1 Brief description

1.1 Brief description

1.1 Brief description    

Type  2  voltage  surge  protectors  for  photovoltaic  (PV)  installations 

with  voltages  which  may  reach  a  maximum  (Uocmax)  of  1200  VDC 

(irrespective  of  the  local  environmental,  temperature,  sunlight,  etc. 

conditions). 

Specifically  designed  to  protect  the  DC  part  of  PV  installations  

(PV panels and inverters)  

-  Based  on  the  use  of  non-polarised  panels  (panels  which  do 

not require their active conductors to be earthed)* 

-  Without energy storage system (e.g. batteries, etc.) 

 Equipped with draw-out replacement cassettes with LED indicators (red 

LED: cassettes need to be replaced). 

* Please contact us for installations with polarised panels 

 

1.2 Use 

1.2 Use 

1.2 Use 

1.2 Use     

1.2.1 Legrand recommendations

 

1.2.1.1 Protection of the DC part of the PV installation

 

To  provide  correct  voltage  surge  protection  of  the  DC  part  of  the  
PV installation, a PV voltage surge protector is recommended: 
 
- On each inverter input 

(1)

 (in the DC enclosures in accordance with 

guide UTE C 15-712-1, voltage surge protector compulsory according 
to  the  type  and  location  of  the  installation  to  be  protected,  see  

UTE C 15-712-1) 
 
- Close to the panels (in the group junction boxes according to guide 
UTE  C  15-712-1)  when  they  are  more  than  10  m  away  from  the 
inverter or the DC enclosure 

(2)

 

(1)

  For  multi-input  inverters  or  multi-MPPT,  it  is  advisable  to  use  a 

voltage surge protector on each input 
 

(2)

 PV generators with a Uocmax voltage of less than 600 V: 

According to guide UTE C 15-712-1, this protection is only necessary 
if  Legrand  600  V  voltage  surge  protectors  are  installed close  to the 

inverters.  However  this  protection  is  recommended  for  widespread  
PV installations with very long lines. 

 
 

 

 

1.2.1.2 Protection of the AC part of the PV installation

 

Likewise,  for  correct  protection  of  the  AC  part  of  the  
PV  installation,  it  is  advisable  to  group  the  inverters  together  in 
the same equipment room as the main panel (main LV distribution 
board)  connecting  the  PV  installation  to  the  LV  distribution 
system. Thus a single AC voltage surge protector 

(1)

 is all that is 

necessary to protect the main LV distribution board (voltage surge 
protector  compulsory  according  to  the  type  and  location  of  the 
installation to be protected, see UTE C 15-712-1). 

If the inverters are not installed in the equipment room in which the 

main LV distribution board is located (or are installed out of doors) an 

AC voltage surge protector is also necessary close to each inverter. 

Recommended types of AC voltage surge protector: 

Power of the 

 

PV installation 

Main LV board prot.

 

Installations with

 

lightning conductors 

(3)

 

Main LV board prot.

 

Installations w/out 

lightning conductors 

Protection 

 

close to

 

inverters 

(2)

 

P < 36 kWc 

Type 1

 

(Iimp 12.5 kA) 

protected

 

v. surge protector 

protected  

v. surge protector 

P < 100 kWc 

Type 1

 

(Iimp 25 kA) 

Type 2 

 

(Imax 70 kA) 

Type 2

 

(Imax 15 kA) 

P > 100 kWc 

Type 1

 

(Iimp 25 kA) 

Type 1

 

(Iimp 25 kA) 

Type 2

 

(Imax 40 kA) 

 
(1)

 An additional AC voltage surge protector is also necessary close 

to each inverter that is more than 10 m away from the main LV 

distribution board. This voltage surge protector must be the same 

type as those used close to the inverters (see above table). 

 

(2)

 AC voltage surge protectors necessary close to each inverter that is 

- More than 10 m away from the main LV distribution board  

-  Installed  out  of  doors  or  outside  the  equipment  room  in  which 

the main LV distribution board is installed 

 

(3)

 When a PV installation is protected by lightning conductors, it is 

advisable to create an isolated lightning protection system (isolated 

LPS) as described in standard NF EN 62305, maintaining adequate 

separation distances between the metal structures of the panels and 

the LPS (lightning conductors and downcomers). 

 
1.2.1.3  Protection  of  the  AC  part  of  the  existing  installation 
(consumption part)

 

To ensure correct voltage surge protection of the whole installation 
(PV installation and installation on the consumption side), it is 
advisable to protect the AC installation on the consumption side so 
as to avoid any possible risk resulting from overvoltage on the  

PV installation or overvoltage from the distribution system. 

 

 

Technical data sheet: F01271EN/00  

Updated on:  

 

Created on: 13/01/2012   

Отзывы: