Miniature PIR presence detector - DALI dimming

Technical data sheet: S000104982EN-3 

Updated: 03/02/2021 

Created: 25/10/2018

Cat. No(s): 0 489 53

CONTENTS

 7. SETTINGS

The detector functions are controlled by a number of parameters which can be changed or programmed by an infrared configurator.

In combination with configuration tool 0 882 40, the Legrand Close Up smartphone app can be used to view and modify all the detector parameters with 

online help.

Point the infrared configuration tool at the detector for all read/write operations.

Valid commands will be indicated by a red flashing LED on the product and the lighting switches off automatically for all read/write operations.

Before changing the settings, an initialisation operation must be performed as suggested in the Legrand Close Up configuration app:
1 – Click on "Scan product settings"
2 – Click on "Settings details/copy"
3 – In the menu at the top right (…) select "Initialise"
4 – Click on "Write product settings"
This operation allows predefined setting of certain parameters.

Parameter

Default 

value

Value after 

initialisation

Range/

option

Description

Output channel modes

Switching only

-

-

-

Only the relay part is used

Switch and dim 

together

-

The 2 outputs are synchronised and go ON/OFF at the same time

Switch and dim 

separately

-

-

-

The 2 outputs are not synchronised and the DALI luminaire can be turned off with-

out switching the relay output OFF

General parameters

LED operation 

test

Off

-

On or Off

When this option is activated, a red LED on the sensor flashes when it detects move-

ment. Use this function to check that the sensitivity levels are suitable.

Inhibit  

detection

No

-

Yes/No

Disables presence/absence detection so that the detector does not control switch-

ing, only dimming. Use this mode for light regulation without automatic control 

according to occupancy.

Timeout

20 minutes

-

0 to 99  

minutes

Once the detector is turned on, this value sets how long the lights will stay on once 

movement has ceased. Select 0 for a 10-second period (for commissioning only).

Manual timeout 

period

10 minutes

-

0 to 99  

minutes

When a manual operation occurs, either via the switch input or the infrared, it 

invokes the timeout period.
Example 1: A detector in presence mode has a detector timeout of 15 minutes and 

a manual timeout of 3 minutes. When the user leaves the room, they press the off 

button. The sensor will revert to automatic mode after 3 minutes. Walking back into 

the room will turn the lights on.
Example 2: Using the settings above, the user turns the lights off (say for a 

presentation) but stays in the room. Every time a movement is detected, the manual 

timeout period is re-triggered, but when it doesn’t pick up over a short timeout 

period, the detector will revert to automatic mode. This means that the lights may 

come on inadvertently during the presentation, even if the occupants are still 

present during the manual timeout period, so adjust the timing carefully.

Sensitivity On

8

9

1 (min) 

to 9 (max)

Sensitivity level for detecting movement when the detector is already on.

Содержание 0 489 53

Страница 1: ...mming commands from the infrared configurator Light level sensor Measures the overall Lux level in the detection area LED status The LED flashes red to indicate the following RJ11 connector The sensor head has an RJ11 socket for connection to the power supply Power supply This power supply has a 6 A relay It also has connections for an auxiliary switch that can be used to turn on the lighting manu...

Страница 2: ...ballast 4 Compact fluorescent lamps with separate ferromagnetic ballast 5 ELV halogen lamps with separate electronic ballast 6 Fluorescent tubes with separate electronic ballast 7 Compact fluorescent lamps with built in electronic ballast 8 Compact fluorescent lamps with separate electronic ballast 9 LED lamps with separate electronic ballast 10 LED lamps with built in electronic ballast 2 TECHNIC...

Страница 3: ...be required to insert the flush mounting ring Power up test procedure When power is applied to the unit the load will turn on immediately Set the timeout to 10 seconds vacate the room or remain very still and wait for the load to switch off Check that the load switches on when movement is detected The unit is now ready for programming Surface mounted on luminaire or the ceiling Use the lugs on the...

Страница 4: ...meters LED operation test Off On or Off When this option is activated a red LED on the sensor flashes when it detects move ment Use this function to check that the sensitivity levels are suitable Inhibit detection No Yes No Disables presence absence detection so that the detector does not control switch ing only dimming Use this mode for light regulation without automatic control according to occu...

Страница 5: ... the ambient light drops below the Lux On Level this is the delay before the lights comes on If at any time during the timed delay the Lux level position is reversed the process is cancelled A minimum time of 15 seconds is defined for a value of 0 If you try to turn on the lights using a manual control the lights will come on regardless of the ambient light level However if there is sufficient amb...

Страница 6: ...hting Reduce and adjust the value of the Lux Off level parameter in steps of 10 or 20 Example Lux level for regulation 150 Lux On Level 145 Lux Off Level 215 Lux Off Time 1 Min value 82 6 If the light level is too high Reduce and adjust the value of the Lux level for regulation parameter Adjust the value of the following parameters Lux On level Lux level for regulation 5 Lux Off level Lux level fo...

Отзывы: