background image

1/8

Technical data sheet: S000077897EN-1 

Updated:  

Created: 10/03/2014

Cat. No(s): 0 489 14

Lighting management sensor - PIR

230 V~

500 VA

2.1 A 

max.

I max. ≤ 2.1 A

110 V~

250 VA

U ≤ 30 V

=

2.1 A max.

  1. Use

This device allows a light source to be controlled automatically by 

detecting movement in a monitored area.

It can be installed in work areas (offices, classrooms, meeting rooms, 

open-plan offices).

Motion sensor with 180° detection angle.

Detection type: infrared (PIR)

Mounting type: wall

  2. TeChNICaL ChaRaCTeRIsTICs

Voltage: 240 V~

Frequency: 50/60 Hz

No-load power consumption: 0.6 W

Output via normally open contact connected to the phase

Wiring: 2 x 2.5 mm

2

Number of terminals: 4

Terminal type: screw

Stripping length: 8 mm

Drilling diameter:  67 mm with flush-mounting box

Weight: 114

 

g

Impact resistance: IK04

Penetration by solid and liquid matter:  IP42

Usage temperature: - 5°C to + 45°C

Storage temperature: - 20°C to + 70°C

   2.  TeChNICaL ChaRaCTeRIsTICs (continued)

Products approved for 40,000 operations

Mains zero breaking: in order to limit the effect of induced currents on 

cut-off relays by fluorescent loads in particular, this sensor breaks the 

voltage at mains zero. Switching occurs when the voltage is at point 0 

which ensures a longer life for sources and for the sensor.

Cover removed

CoNTeNTs 

Page

1. Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

2. Technical characteristics. . . . . . . . . . . . . . . . .1

3. Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

4. Connection . . . . . . . . . . . . . . . . . .   . . . . . . . . .2

5. Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

6. Installation  . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

7. Operation  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5

8. Settings  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6

9. Performance. . . . . . . . . . . . . . . . . . . . . . . . . . . .7

10. Care . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8

11. Standards and certifications. . . . . . . . . . . . .8

12. Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . .8

Light level cell

Sensor/PIR sensor

Learn button

Detection LED

Learn LED

230 V~ 2000 W

8.5 A

1000 VA

4.3 A

1000 VA

4.3 A

10x(2x36 W)

4.3 A

250 W

1 A

250 W

1 A

250 W

1 A

500 VA

2.1 A

110 V~ 1000 W

500 VA

500 VA

5x(2x36 W)

125 W

125 W

125 W

250 VA

1 - Halogen bulbs
2 -  ELV halogen, compact fluorescent and fluorescent bulbs with 

separate electronic ballast

3 -   ELV halogen, compact fluorescent and fluorescent bulbs with 

separate ferromagnetic ballast

4 - Fluorescent tubes
5 -  Compact fluorescent bulbs with built-in electronic ballast
6 -  Compact fluorescent bulbs with built-in ferromagnetic ballast
7 - LED bulbs

1

2

3

4

5

6

7

8

8 - Contactor
9 - Motor

Содержание 0 489 14

Страница 1: ...00 operations Mains zero breaking in order to limit the effect of induced currents on cut off relays by fluorescent loads in particular this sensor breaks the voltage at mains zero Switching occurs wh...

Страница 2: ...gement sensor PIR 3 Dimensions With protective cover 84 46 31 118 2 1 A max SN S2 S1 100 m max 8 5 A max PB L 8 5 A max 2 1 A max PB 100 m max 8 5 A max 2 1 A max V U 30 V 4 Connection 4 1 Wiring with...

Страница 3: ...0 489 14 Lighting management sensor PIR PIR 2 5 m 3 5 m 1 2 2 1 A max SN S2 S1 100 m max 8 5 A max 8 5 A max 8 5 A max PB LN L2 L1 4 Connection continued 4 4 Wiring for several loads connected in par...

Страница 4: ...Updated Created 10 03 2014 Cat No s 0 489 14 Lighting management sensor PIR 6 INSTALLATION continued 6 3 Fitting 6 INSTALLATION continued 6 3 Fitting continued 3 50 67 4 0 489 71 6 4 Choice of detect...

Страница 5: ...he sensors S switch to the ON state one short press all the sensors S inversion of OFF to ON or ON to OFF L1 OFF L2 OFF Ln OFF S1 OFF S2 OFF Sn OFF 1 s L1 ON L2 ON Ln ON S1 ON S2 ON Sn ON L1 ON L2 ON...

Страница 6: ...5 10 15 20 min 0 59 min 59 s Sensitivity PIR very high Low medium high very high Modes Auto on Auto off Inactive Activate Deactivate Walk through mode Active Activate Deactivate Manual on Auto off In...

Страница 7: ...0 4 m Height 2 5 m Sensitivity Low 25 Sensitivity Medium 50 Sensitivity High 75 Sensitivity Very high 100 a m b m a m b m a m b m a m b m 2 6 3 6 4 6 4 6 b a CK 12 m PIR 2 5 m 0 4 Height 2 5 m Sensit...

Страница 8: ...ents vibrations and radiators can cause unintended operation 1 Reduce the sensitivity level 2 If the interference continues using the configuration tool go into the Detection system parameters select...

Отзывы: