LEGRAND 0 026 72 Скачать руководство пользователя страница 7

7/29

Technical data sheet: S000114123EN-1 

Updated: 

Created: 18/01/2021

Cat. No(s): 0 026 72/73/74/76/78/79

KNX controller multi-application DIN

  7 . COMMUNICATION OBJECTS

7 .1 List of objects

The device has 254 communication objects. Overview of all 

communication objects of the device can be seen on the following 

table. Object names will be changed according to channel function as 

follows.

Fan coil:

 Fan A/B1, Fan C/D1, Fan E/F1, Fan G/H1, Fan I/J1 etc.

Valve control:

 Valve A/B, Valve C/D, Valve E/F, Valve G/H, Valve I/J.

Shutter/Blind DC:

 Output A/B, Output C/D, Output E/F, Output G/H, 

Output I/J.

Shutter/Blind AC:

 Output A, Output B, Output C, Output D, Output E.

Switch:

 Output A1, Output A2, Output B1, Output B2, Output C1, 

Output C2 etc.

No

Name

Function

DTP Type Length Flags

0

General

In operation

1.002

1 bit

CWT

1

General 

Scene 8-bit

18.001

1 byte

CW

2

Blind

Wind alarm 

1.005

1 bit

CWTU

3

Blind

Rain alarm

1.005

1 bit

CWTU

4

Blind

Frost alarm

1.005

1 bit

CWTU

5

Input a

Disable

1.003

1 bit

CW

6

Input a

Switch

1.001

1 bit

CWT

Switch – short

1.001

1 bit

CWT

Shutter Up/Down

1.008

1 bit

CT

Value (0,1)

1.001

1 bit

CWT

Value (forced)

2.001

2 bit

CWT

Value [0...255]

5.001

8 bit

CWT

Value [0...65535]

8.001

16 bit

CWT

Value [-32768...32767]

7.001

16 bit

CWT

Value [0...4294967295]

12.001

32 bit

CWT

7

Input a

Switch – long

1.001

1 bit

CWT

Dimming brighter / darker

3.007

4 bit

CT

Shutter stop / lamella

1.007

1 bit

CT

Value (0,1) - long

1.001

1 bit

CT

Value (forced) - long

2.001

1 bit

CT

Value [0...255] - long

5.001

8 bit

CT

Value [0...65535] - long

8.001

16 bit

CT

Value [-32768...32767]

7.001

16 bit

CT

Value [0...4294967295]

12.001

32 bit

CT

8

Input a

Shutter upper limit position

1.002

1 bit

CW

Value (temperature)

14.068

32 bit

CT

9

Input a

Shutter lower limit position

1.002

1 bit

CW

Value (temperature) - long

14.068

32 bit

CT

10…94

Input b … s

Same as “Input a”

95

Output A1

Switch

1.001

1 bit

CW

Output A

Output A/B

Move blind/shutters up-down

1.008

1 bit

CW

Fan A/B1

Fan speed switch

5.010

1 byte 

CW

Control input

Control value HEATING

5.001

1 byte

CW

96

Output A1

Status Switch

1.001

1 bit

CW

Output A

Output A/B

Slat adjustment/stop up-down

1.007

1 bit

CW

Fan A/B1

Switch speed 1

1.001

1 bit

CW

Control input

Control value COOLING

5.001

1 byte

CW

97

Output A1

Enable staircase function

1.003

1 bit

CRW

Output A

Blind/shutters up-down limited

1.008

1 bit

CW

Output A/B

Enable limitation

1.003

1 bit

CW

Fan A/B1

Switch speed 2

1.001

1 bit

CW

Control input

Toggle Heating/Cooling

1.100

1 bit

CW

98

Output A1

Staircase lighting duration

7.007

2 byte

CRW

Output A

Output A/B

Move to position height 0…255

5.001

1 byte

CW

Fan A/B1

Switch speed 3

1.001

1 bit

CW

Control input

Fault control value

1.005

1 bit

CRT

99

Output A1

Permanent ON

1.001

1 bit

CW

Output A/B

Move slats 0…255

5.001

1 byte

CW

Fan A/B1

Fan speed UP/DOWN

1.007

1 bit

CW

Valve HEATING Block

1.003

1 bit

CW

   7 .  COMMUNICATION OBJECTS (continued)

7 .1 List of objects (continued)

No

Name

Function

DTP Type Length Flags

100

Output A1

External logic input

1.001

1 bit

CW

Output A

Output A/B

Move to position 1, 2

1.022

1 bit 

CW

Fan A/B1

Status fan ON/OFF

1.001

1 bit

CT

Valve HEATING Forced operation

1.003

1 bit

CW

101

Output A1

Forced positioning

2.001

2 bit

CW

Output A

Output A/B

Move to position 3, 4

1.022

1 bit 

CW

Fan A/B1

Status fan speed

5.010

1 byte

CRT

Valve HEATING Trigger valve purge

1.017

1 bit

CW

102

Output A1

Sweep

1.017

1 bit

CW

Output A

Output A/B

Set position 1, 2

1.022

1 bit

CW

Fan A/B1

Status fan speed 1

1.001

1 bit

CRT

Valve HEATING Status valve purge

1.003

1 bit

CRT

103

Output A2

Switch

1.001

1 bit

CW

Output A

Output A/B

Set position 3, 4

1.022

1 bit

CW

Fan A/B1

Status fan speed 2

1.001

1 bit

CRT

Valve HEATING

Status valve position

1.001

1 bit

CRT

Status valve position

5.001

1 byte

CRT

104

Output A2

Status Switch

1.001

1 bit

CW

Output A

Output A/B

Trigger reference movement

1.008

1 bit

CW

Fan A/B1

Status fan speed 3

1.001

1 bit

CRT

Valve COOLING Block

1.003

1 bit

CW

105

Output A2

Enable staircase function

1.003

1 bit

CRW

Output A

Output A/B

Block

1.003

1 bit

CWTU

Fan A/B1

Forced operation

1.003

1 bit

CW

Valve COOLING Forced operation

1.003

1 bit

CW

106

Output A2

Staircase lighting duration

7.007

2 byte

CRW

Output A

Forced operation 1 bit

1.003

1 bit

CWTU

Output A/B

Forced operation 2 bit

2.002

2 bit

CW

Fan A/B1

Automatic ON/OFF

1.003

1 bit

CW

Valve COOLING Trigger valve purge

1.017

1 bit

CW

107

Output A2

Permanent ON

1.001

1 bit

CW

Output A

Output A/B

Status height 0…255

5.001

1 byte

CRT

Fan A/B1

Status automatic

1.003

1 bit

CW

Valve COOLING Status valve purge

1.003

1 bit

CRT

108

Output A2

External logic input

1.001

1 bit

CW

Output A

Status slat 0…255

5.001

1 byte

CRT

Valve COOLING

Status valve position

1.001

1 bit

CRT

Status valve position

5.001

1 byte

CRT

109

Output A2

Forced positioning

2.001

2 bit

CW

Output A

Output A/B

Status upper end position

1.011

1 bit 

CRT

110

Output A2

Sweep

1.017

1 bit

CW

Output A

Output A/B

Status lower end position

1.011

1 bit

CRT

111…254

Output B1…U2

Output C/D…

Output T/U

Same as “Output A1” for switch

Same as “Output A/B” for blind

CONTENTS

Содержание 0 026 72

Страница 1: ...ch Sensor parameter 10 7 5 2 a Switch Dim Sensor parameter 11 7 5 2 a Switch Dim Sensor parameter continued 11 7 5 3 a Blind Sensor parameter 11 7 5 4 a Value Forced Operation parameter 12 7 6 Enable...

Страница 2: ...n parameter 23 7 10 2 A B1 Status Message parameter 24 7 10 3 A B1 Automatic Operation parameter 25 7 10 4 A B1 Direct Mode parameter 25 7 11 Function Chart 26 7 12 Object Description 26 7 12 1 Genera...

Страница 3: ...ut x4 AC Blind x2 DC Blind x1 2 Point valve x2 3 point valve x2 Suitable for switching resistive capacitive and inductive loads as well as fluorescent lamp loads according to EN 60 669 A single switch...

Страница 4: ...4123EN 1 Updated Created 18 01 2021 Cat No s 0 026 72 73 74 76 78 79 KNX controller multi application DIN 4 CONNECTION 0 026 72 73 AC Motor D2 NA Fan1 Fan2 Fan3 4 CONNECTION continued 0 026 74 AC Moto...

Страница 5: ...ted 18 01 2021 Cat No s 0 026 72 73 74 76 78 79 KNX controller multi application DIN 4 CONNECTION continued 0 026 76 AC Motor AC Motor DC Motor F G DC Motor F G 4 CONNECTION continued 0 026 78 79 AC M...

Страница 6: ...S4 or higher Important A detailed information about parameter configuration can be found in Product Manual of device Installation and commissioning of device may only be implemented by trained electri...

Страница 7: ...100 1 bit CW 98 Output A1 Staircase lighting duration 7 007 2 byte CRW Output A Output A B Move to position height 0 255 5 001 1 byte CW Fan A B1 Switch speed 3 1 001 1 bit CW Control input Fault con...

Страница 8: ...e sent freely within a period Note If the value of the object cannot be sent in the time of a period The object is buffered for the next period time The buffered object will be updated if the object v...

Страница 9: ...valuate the transmitted scene address and switches the output to the stored scene value A scene is activated when it receives its scene number at the scene object The storing of the current channel va...

Страница 10: ...is distinction between short and long operation The contact type of the push button attached to the channel is adjusted here Cyclic transmission of object no switch OFF switch ON always This paramete...

Страница 11: ...operation STOP telegram sends at the end of operation Brightness change on every sent telegram 100 6 25 1 56 This parameter is only visible with the Dimming steps options This parameter is cyclically...

Страница 12: ...op command is sent such as STOP Lamella adj UP or STOP Lamella adj DOWN 1 Shutter MOVE UP STOP Lamella UP 2 Shutter MOVE DOWN STOP Lamella DOWN 2 button stepping On operation Stop lamella adjustment T...

Страница 13: ...n shutter blind DC fan coil valve control individually Both output group can be combined into one DC blind In DC blind operation the four relay contacts of the device can be used to control electrical...

Страница 14: ...bus voltage return Behavior bus voltage failure keep position open contact close contact When the bus voltage fails the device set the wanted switching state of the output The relay can be open close...

Страница 15: ...mber of pre warning and time for pre warning interval The warning function is for warning that the staircase lighting time run out and the lights are switched off soon In the warning lights short turn...

Страница 16: ...B General parameter continued Behavior after ETS programming or after ETS reset Behavior bus voltage failure no reaction up down stop position 1 2 3 4 approach position This parameter can be used to c...

Страница 17: ...e Trigger reference movement communication object is visible The reference movement is triggered via this communication object In long time slight inaccuracies can occur so the upper and lower end pos...

Страница 18: ...This function allows you set a height position or slat position directly using with communication object Enable communication objects Move to pos Height Move slat 0 255 no yes The communication Move t...

Страница 19: ...havior in case of rain alarm Behavior in case of frost alarm no reaction up down stop position 1 position 2 position 3 position 4 individual position When the alarm is activated the blind moves this p...

Страница 20: ...tion communication object is updated After the bus voltage return forced position function set to the parametrized position Set the parameter to no forced position active The forced operation is deact...

Страница 21: ...ING is deactivated Set the parameter to 1 When the telegram is received 1 HEATING operation is activated COOLING is deactivated Monitoring control valves yes no This parameter activate the thermostat...

Страница 22: ...vel time This time is maximum one minute Valve limitation yes no The limitation of the control value limits the height of the control value The limitation is activated when a value is chosen which is...

Страница 23: ...ons Thus initially the number of fan levels required for the connected devices can be defined The number of fan levels can be specified separately for each fan coil channel Controlling the fan levels...

Страница 24: ...ime has elapsed 7 COMMUNICATION OBJECTS continued 7 10 Fan Coil parameter continued 7 10 2 A B1 Status Message parameter Enable communication object Status fan speed x 1 bit yes no The data format for...

Страница 25: ...peed In s 0 65535 0 65535 This parameter defines the dwell time for a fan speed of the fan until it switches to the next higher or lower fan speed 0 no delay time for switching 7 COMMUNICATION OBJECTS...

Страница 26: ...x Des 1 0x00 0 0x80 128 2 0x01 1 0x81 129 3 0x02 2 0x82 130 4 0x03 3 0x83 131 5 0x04 4 0x84 132 6 0x05 5 0x85 133 7 0x06 6 0x86 134 8 0x07 7 0x87 135 9 0x08 8 0x88 136 10 0x09 9 0x89 137 11 0x0A 10 0x...

Страница 27: ...d operation 1 byte 0 255 DPT 5 001 brightness value 2 byte 32768 32767 DPT 7 001 signed value 2 byte 0 65535 DPT 8 001 unsigned value 4 byte float value DPT14 068 temperature 4 byte 0 4294967295 DPT12...

Страница 28: ...or 4 104 Trigger reference movement Output A DTP 1 008 1 bit CW This object is triggered the reference movement If the telegram is received the blind is moved up or down end position Then the blind c...

Страница 29: ...OMMUNICATION OBJECTS continued 7 17 Fan Object Description No Object name Name DTP Type Length Flags 95 Fan speed switch Fan DPT 5 010 1 byte CW This object is used to switch on fan speed via 1 byte o...