LEGRAND 0 026 72 Скачать руководство пользователя страница 27

27/29

Technical data sheet: S000114123EN-1 

Updated: 

Created: 18/01/2021

Cat. No(s): 0 026 72/73/74/76/78/79

KNX controller multi-application DIN

   7 .  COMMUNICATION OBJECTS (continued)

7 .13 Input Object Description

No

Object name

Name

DTP Type

Length Flags

5

Disable

Input a

DPT 1.003

1 bit

CW

0: enable input

1: disable input

This object is only visible if it is used as an input. Via the group address linked to this object 

blocking of the respective input channel is turned on or off. 

When a disabled input is enabled, no telegrams are sent on the bus, even if the state of the 

input has changed during blocking. If the input is just being operated as it is being enabled, 

the input behaves as if the operation has just commenced. 

6

Switch

Switch - short

Input a

DPT 1.001

1 bit

CWT

0: OFF

1: ON

Switching telegrams are sent via the group address linked with this object. Object can be 

switched by actuation of the ON, OFF or TOGGLE input.

6

Shutter up/down

Input a

DPT 1.008

1 bit

CT

The driving object is for moving the shutters “move UP” and “move DOWN”.

0: Move upwards (UP)

1: Move downwards (DOWN)

6

Value

Input a

CWT

An adjustment can be made as to whether a value telegram is to be sent as a reaction to a 

short and / or long button press action when a push button is pressed or released. Additionally, 

it is possible to configure whether the value associated with the long button press action is 

sent via a second object.
1 bit [0 / 1]

DPT 1.001

switch command

2 bit [0…3]

DPT 2.001

forced operation

1 byte [0…255]

DPT 5.001

brightness value

2 byte [-32768…32767]

DPT 7.001

signed value

2 byte [0…65535]

DPT 8.001

unsigned value

4 byte [float value]

DPT14.068

temperature

4 byte [0…4294967295]

DPT12.001

value unsigned

7

Switch - long

Input a

DPT 1.008

1 bit

CT

0: OFF

1: ON

Switching telegrams for long push button press are sent via the group address linked with this 

object if the parameter “Number of objects for short/long operation” is set to “2 object”.

7

Dimming brighter / darker

Input a

DPT 3.007

4 bit

CT

4 bit: B

1

U

3

 

1

c StepCode

B U U U

c = {0,1}

StepCode = [000b . . .111b]

c

Increase or decrease the brightness

0 – recall scene
1 – store scene

StepCode The amount of intervals into 

which the range of 0 % … 100 % is 

subdivided or the break indication.

- 001b … 111b: Step

   Number of interval = (2)

(StepCode-1)

- 000b                : Break

The dimming telegrams are sent to the dimming actuator via the group address linked with 

this object. In the process, a long push button action produces a “100 % dimming” telegram. A 

stop command is sent when the push button is released.

7

Shutter stop / lamella

Input a

DPT 1.007

1 bit

CT

The stop‐/lamella adjustment object is for the adjustment of the lamellas and additional it 

stops a running movement of the shutter.

0: Stop / lamella UP

1: Stop / lamella DOWN

7

Value

Input a

CWT

An adjustment can be made as to whether a value telegram is to be sent as a reaction to a short 

and / or long button press action when a push button is pressed or released. Additionally, it is 

possible to configure whether the value associated with the long button press action is sent via 

a second object.
1 bit [0 / 1]

DPT 1.001

switch command

2 bit [0…3]

DPT 2.001

forced operation

1 byte [0…255]

DPT 5.001

brightness value

2 byte [-32768…32767]

DPT 7.001

signed value

2 byte [0…65535]

DPT 8.001

unsigned value

4 byte [float value]

DPT14.068

temperature

4 byte [0…4294967295]

DPT12.001

value unsigned

8

Shutter upper limit position

Input a

DPT 1.002

1 bit

CW

This object the shutter actuator indicates is it is in the upper limit position. This object is used 

for 1 button options.

0: No Upper end limit 

1: Upper end limit

8

Value (temperature)

Input a

DPT 14.068

32 bit

CT

The value type is selected “floating point” this object is created. For more information look 

Value communication  object.

   7 .  COMMUNICATION OBJECTS (continued)

7 .13 Input Object Description (continued)

No

Object name

Name

DTP Type

Length Flags

9

Shutter lower limit position

Input a

DPT 1.002

1 bit

CW

This object the shutter actuator indicates is it is in the lower limit position. This object is used 

for 1 button options.

0: No Lower end limit

1: Lower end limit

9

Value (temperature) - long

Input a

DPT 14.068

32 bit

CT

The value type is selected “floating point” this object is created. For more information look Value 

communication object.

7 .14 Switch Object Description

No

Object name

Name

DTP Type

Length Flags

95

Switch

Output A1

DTP 1.001

1 bit

CW

This object is used to switching of relay. If a logic operation is enabled, the output is calculated 

via logic combination.

The object is;

0 = switched ON 

1 = switched OFF

96

Status switch

Output A1

DPT 1.001

1 bit

CRT

The current switching state of the channel is saved in the status object. It can be transmitted 

automatically its state changed.

This object is ;

0 = relay OFF position

1 = relay ON position

97

Enable staircase function

Output A1

DPT 1.003

1 bit

CRW

This object is used to activation of the staircase function. This object is enabled, the staircase 

function is activated.

The object is;

0 = disable 

1 = enable

98

Staircase lighting duration

Output A1

DPT 7.007

2 byte

CRW

The staircase lighting duration is set via this object. The object resolution is second. In addition, 

the bus return state can be parameterized by the parameter at the staircase function tag. 

The object is;

0 = must be greater than zero

….

65535

99

Permanent ON

Output A1

DTP 1.001

1 bit

CW

This object is used to mask the other function. This meanings function is working back ground 

of the Permanent ON. If the Permanent ON object is set to off, the other function switch result 

can be visible on the output.  After bus voltage return, the object is deactivated. 

This object feature is useful for cleaning person.  

The object is;

0 = permanent ON active

1 = deactivate

100

External logic input

Output A1

DPT 1.001

1 bit

CW

This object is used to receive the switching data for the second input. The switch operation and 

external logic are respect with logic OR, AND.

The object is;

0 = logic state 

1 = logic state

101

Forced positioning 

Output A1

DPT 2.001

2 bit

CW

This object is used to the switching state of the output is directly determined by this object. 

The first bit is switching state and the second bit is activated or deactivated the forced control. 

Bit Field Description

Bit 0

Switching state “0”: switching off “1”: 

switching on

Bit 1

Forced control “0”: inactive “1”: active

102

Sweep

Output A1

DPT 1.017

1 bit

CW

This object is used to trigger the sweep function. 

The object is;

0 = do nothing

1 = trigger

CONTENTS

Содержание 0 026 72

Страница 1: ...ch Sensor parameter 10 7 5 2 a Switch Dim Sensor parameter 11 7 5 2 a Switch Dim Sensor parameter continued 11 7 5 3 a Blind Sensor parameter 11 7 5 4 a Value Forced Operation parameter 12 7 6 Enable...

Страница 2: ...n parameter 23 7 10 2 A B1 Status Message parameter 24 7 10 3 A B1 Automatic Operation parameter 25 7 10 4 A B1 Direct Mode parameter 25 7 11 Function Chart 26 7 12 Object Description 26 7 12 1 Genera...

Страница 3: ...ut x4 AC Blind x2 DC Blind x1 2 Point valve x2 3 point valve x2 Suitable for switching resistive capacitive and inductive loads as well as fluorescent lamp loads according to EN 60 669 A single switch...

Страница 4: ...4123EN 1 Updated Created 18 01 2021 Cat No s 0 026 72 73 74 76 78 79 KNX controller multi application DIN 4 CONNECTION 0 026 72 73 AC Motor D2 NA Fan1 Fan2 Fan3 4 CONNECTION continued 0 026 74 AC Moto...

Страница 5: ...ted 18 01 2021 Cat No s 0 026 72 73 74 76 78 79 KNX controller multi application DIN 4 CONNECTION continued 0 026 76 AC Motor AC Motor DC Motor F G DC Motor F G 4 CONNECTION continued 0 026 78 79 AC M...

Страница 6: ...S4 or higher Important A detailed information about parameter configuration can be found in Product Manual of device Installation and commissioning of device may only be implemented by trained electri...

Страница 7: ...100 1 bit CW 98 Output A1 Staircase lighting duration 7 007 2 byte CRW Output A Output A B Move to position height 0 255 5 001 1 byte CW Fan A B1 Switch speed 3 1 001 1 bit CW Control input Fault con...

Страница 8: ...e sent freely within a period Note If the value of the object cannot be sent in the time of a period The object is buffered for the next period time The buffered object will be updated if the object v...

Страница 9: ...valuate the transmitted scene address and switches the output to the stored scene value A scene is activated when it receives its scene number at the scene object The storing of the current channel va...

Страница 10: ...is distinction between short and long operation The contact type of the push button attached to the channel is adjusted here Cyclic transmission of object no switch OFF switch ON always This paramete...

Страница 11: ...operation STOP telegram sends at the end of operation Brightness change on every sent telegram 100 6 25 1 56 This parameter is only visible with the Dimming steps options This parameter is cyclically...

Страница 12: ...op command is sent such as STOP Lamella adj UP or STOP Lamella adj DOWN 1 Shutter MOVE UP STOP Lamella UP 2 Shutter MOVE DOWN STOP Lamella DOWN 2 button stepping On operation Stop lamella adjustment T...

Страница 13: ...n shutter blind DC fan coil valve control individually Both output group can be combined into one DC blind In DC blind operation the four relay contacts of the device can be used to control electrical...

Страница 14: ...bus voltage return Behavior bus voltage failure keep position open contact close contact When the bus voltage fails the device set the wanted switching state of the output The relay can be open close...

Страница 15: ...mber of pre warning and time for pre warning interval The warning function is for warning that the staircase lighting time run out and the lights are switched off soon In the warning lights short turn...

Страница 16: ...B General parameter continued Behavior after ETS programming or after ETS reset Behavior bus voltage failure no reaction up down stop position 1 2 3 4 approach position This parameter can be used to c...

Страница 17: ...e Trigger reference movement communication object is visible The reference movement is triggered via this communication object In long time slight inaccuracies can occur so the upper and lower end pos...

Страница 18: ...This function allows you set a height position or slat position directly using with communication object Enable communication objects Move to pos Height Move slat 0 255 no yes The communication Move t...

Страница 19: ...havior in case of rain alarm Behavior in case of frost alarm no reaction up down stop position 1 position 2 position 3 position 4 individual position When the alarm is activated the blind moves this p...

Страница 20: ...tion communication object is updated After the bus voltage return forced position function set to the parametrized position Set the parameter to no forced position active The forced operation is deact...

Страница 21: ...ING is deactivated Set the parameter to 1 When the telegram is received 1 HEATING operation is activated COOLING is deactivated Monitoring control valves yes no This parameter activate the thermostat...

Страница 22: ...vel time This time is maximum one minute Valve limitation yes no The limitation of the control value limits the height of the control value The limitation is activated when a value is chosen which is...

Страница 23: ...ons Thus initially the number of fan levels required for the connected devices can be defined The number of fan levels can be specified separately for each fan coil channel Controlling the fan levels...

Страница 24: ...ime has elapsed 7 COMMUNICATION OBJECTS continued 7 10 Fan Coil parameter continued 7 10 2 A B1 Status Message parameter Enable communication object Status fan speed x 1 bit yes no The data format for...

Страница 25: ...peed In s 0 65535 0 65535 This parameter defines the dwell time for a fan speed of the fan until it switches to the next higher or lower fan speed 0 no delay time for switching 7 COMMUNICATION OBJECTS...

Страница 26: ...x Des 1 0x00 0 0x80 128 2 0x01 1 0x81 129 3 0x02 2 0x82 130 4 0x03 3 0x83 131 5 0x04 4 0x84 132 6 0x05 5 0x85 133 7 0x06 6 0x86 134 8 0x07 7 0x87 135 9 0x08 8 0x88 136 10 0x09 9 0x89 137 11 0x0A 10 0x...

Страница 27: ...d operation 1 byte 0 255 DPT 5 001 brightness value 2 byte 32768 32767 DPT 7 001 signed value 2 byte 0 65535 DPT 8 001 unsigned value 4 byte float value DPT14 068 temperature 4 byte 0 4294967295 DPT12...

Страница 28: ...or 4 104 Trigger reference movement Output A DTP 1 008 1 bit CW This object is triggered the reference movement If the telegram is received the blind is moved up or down end position Then the blind c...

Страница 29: ...OMMUNICATION OBJECTS continued 7 17 Fan Object Description No Object name Name DTP Type Length Flags 95 Fan speed switch Fan DPT 5 010 1 byte CW This object is used to switch on fan speed via 1 byte o...

Отзывы: