![LEGRAND 0 026 72 Скачать руководство пользователя страница 27](http://html1.mh-extra.com/html/legrand/0-026-72/0-026-72_manual_1870844027.webp)
27/29
Technical data sheet: S000114123EN-1
Updated:
Created: 18/01/2021
Cat. No(s): 0 026 72/73/74/76/78/79
KNX controller multi-application DIN
7 . COMMUNICATION OBJECTS (continued)
7 .13 Input Object Description
No
Object name
Name
DTP Type
Length Flags
5
Disable
Input a
DPT 1.003
1 bit
CW
0: enable input
1: disable input
This object is only visible if it is used as an input. Via the group address linked to this object
blocking of the respective input channel is turned on or off.
When a disabled input is enabled, no telegrams are sent on the bus, even if the state of the
input has changed during blocking. If the input is just being operated as it is being enabled,
the input behaves as if the operation has just commenced.
6
Switch
Switch - short
Input a
DPT 1.001
1 bit
CWT
0: OFF
1: ON
Switching telegrams are sent via the group address linked with this object. Object can be
switched by actuation of the ON, OFF or TOGGLE input.
6
Shutter up/down
Input a
DPT 1.008
1 bit
CT
The driving object is for moving the shutters “move UP” and “move DOWN”.
0: Move upwards (UP)
1: Move downwards (DOWN)
6
Value
Input a
…
…
CWT
An adjustment can be made as to whether a value telegram is to be sent as a reaction to a
short and / or long button press action when a push button is pressed or released. Additionally,
it is possible to configure whether the value associated with the long button press action is
sent via a second object.
1 bit [0 / 1]
DPT 1.001
switch command
2 bit [0…3]
DPT 2.001
forced operation
1 byte [0…255]
DPT 5.001
brightness value
2 byte [-32768…32767]
DPT 7.001
signed value
2 byte [0…65535]
DPT 8.001
unsigned value
4 byte [float value]
DPT14.068
temperature
4 byte [0…4294967295]
DPT12.001
value unsigned
7
Switch - long
Input a
DPT 1.008
1 bit
CT
0: OFF
1: ON
Switching telegrams for long push button press are sent via the group address linked with this
object if the parameter “Number of objects for short/long operation” is set to “2 object”.
7
Dimming brighter / darker
Input a
DPT 3.007
4 bit
CT
4 bit: B
1
U
3
1
c StepCode
B U U U
c = {0,1}
StepCode = [000b . . .111b]
c
Increase or decrease the brightness
0 – recall scene
1 – store scene
StepCode The amount of intervals into
which the range of 0 % … 100 % is
subdivided or the break indication.
- 001b … 111b: Step
Number of interval = (2)
(StepCode-1)
- 000b : Break
The dimming telegrams are sent to the dimming actuator via the group address linked with
this object. In the process, a long push button action produces a “100 % dimming” telegram. A
stop command is sent when the push button is released.
7
Shutter stop / lamella
Input a
DPT 1.007
1 bit
CT
The stop‐/lamella adjustment object is for the adjustment of the lamellas and additional it
stops a running movement of the shutter.
0: Stop / lamella UP
1: Stop / lamella DOWN
7
Value
Input a
…
…
CWT
An adjustment can be made as to whether a value telegram is to be sent as a reaction to a short
and / or long button press action when a push button is pressed or released. Additionally, it is
possible to configure whether the value associated with the long button press action is sent via
a second object.
1 bit [0 / 1]
DPT 1.001
switch command
2 bit [0…3]
DPT 2.001
forced operation
1 byte [0…255]
DPT 5.001
brightness value
2 byte [-32768…32767]
DPT 7.001
signed value
2 byte [0…65535]
DPT 8.001
unsigned value
4 byte [float value]
DPT14.068
temperature
4 byte [0…4294967295]
DPT12.001
value unsigned
8
Shutter upper limit position
Input a
DPT 1.002
1 bit
CW
This object the shutter actuator indicates is it is in the upper limit position. This object is used
for 1 button options.
0: No Upper end limit
1: Upper end limit
8
Value (temperature)
Input a
DPT 14.068
32 bit
CT
The value type is selected “floating point” this object is created. For more information look
Value communication object.
7 . COMMUNICATION OBJECTS (continued)
7 .13 Input Object Description (continued)
No
Object name
Name
DTP Type
Length Flags
9
Shutter lower limit position
Input a
DPT 1.002
1 bit
CW
This object the shutter actuator indicates is it is in the lower limit position. This object is used
for 1 button options.
0: No Lower end limit
1: Lower end limit
9
Value (temperature) - long
Input a
DPT 14.068
32 bit
CT
The value type is selected “floating point” this object is created. For more information look Value
communication object.
7 .14 Switch Object Description
No
Object name
Name
DTP Type
Length Flags
95
Switch
Output A1
DTP 1.001
1 bit
CW
This object is used to switching of relay. If a logic operation is enabled, the output is calculated
via logic combination.
The object is;
0 = switched ON
1 = switched OFF
96
Status switch
Output A1
DPT 1.001
1 bit
CRT
The current switching state of the channel is saved in the status object. It can be transmitted
automatically its state changed.
This object is ;
0 = relay OFF position
1 = relay ON position
97
Enable staircase function
Output A1
DPT 1.003
1 bit
CRW
This object is used to activation of the staircase function. This object is enabled, the staircase
function is activated.
The object is;
0 = disable
1 = enable
98
Staircase lighting duration
Output A1
DPT 7.007
2 byte
CRW
The staircase lighting duration is set via this object. The object resolution is second. In addition,
the bus return state can be parameterized by the parameter at the staircase function tag.
The object is;
0 = must be greater than zero
….
65535
99
Permanent ON
Output A1
DTP 1.001
1 bit
CW
This object is used to mask the other function. This meanings function is working back ground
of the Permanent ON. If the Permanent ON object is set to off, the other function switch result
can be visible on the output. After bus voltage return, the object is deactivated.
This object feature is useful for cleaning person.
The object is;
0 = permanent ON active
1 = deactivate
100
External logic input
Output A1
DPT 1.001
1 bit
CW
This object is used to receive the switching data for the second input. The switch operation and
external logic are respect with logic OR, AND.
The object is;
0 = logic state
1 = logic state
101
Forced positioning
Output A1
DPT 2.001
2 bit
CW
This object is used to the switching state of the output is directly determined by this object.
The first bit is switching state and the second bit is activated or deactivated the forced control.
Bit Field Description
Bit 0
Switching state “0”: switching off “1”:
switching on
Bit 1
Forced control “0”: inactive “1”: active
102
Sweep
Output A1
DPT 1.017
1 bit
CW
This object is used to trigger the sweep function.
The object is;
0 = do nothing
1 = trigger
CONTENTS