LEGRAND 0 026 72 Скачать руководство пользователя страница 18

18/29

Technical data sheet: S000114123EN-1 

Updated: 

Created: 18/01/2021

Cat. No(s): 0 026 72/73/74/76/78/79

KNX controller multi-application DIN

   7 .  COMMUNICATION OBJECTS (continued)

7 .8 "Blind" parameter (continued)
7 .8 .3 "A/B – Drive Slat" parameter

Determine times for slat

*via duration of slat adjustment (step)

  via total duration for slat turning

This parameter defines the slat moving time configuration.

Duration to turn slat from 0% - 100% 

in ms [50…60000]

Duration of slat adjustment (step) 

in ms [50…1000]

50…

*1500

…60000

50…

*200

…1000

These parameters define the travelling time of the slat. The time 

needed for a complete movement or step movement. Sets the 

millisecond of the slat moving time.

Number of slat adjustments

(from 0% = open to 100% = closed)

1…

*7

…60

This parameter defines the number of slat steps. The slat steps are 

required to turn the slats from fully closed to fully opened.

Limit step commands to 

number of slat adjustment

*no

  yes

This parameter defines the limit step adjustment command. If it 

selected “

no

”, the slat adjustment step count is unlimited.

Position of slat after arriving on lower end 

position (100% = disable)

0…

*100

The blind will set the slat according to the parameterized value, after 

the end position is reached. This parameter is valid for move up down 

communication object. 

7 .8 .4 "A/B – Functions" parameter

All outputs can be parameterized independent of one other. These 

parameters are only visible in blind operation. 

• Enable position/presets

• Weather alarm

• Forced position

• Feedbacks
The functions are described independently in detail below.

   7 .  COMMUNICATION OBJECTS (continued)

7 .8 "Blind" parameter (continued)
7 .8 .4 "A/B – Functions" parameter (continued)
7 .8 .4 .1 "A/B – Position/Presets" parameter

This function allows you set a height position or slat position, directly 

using with communication object.

Enable communication objects

“Move to pos . Height/Move slat 0…255”

*no

 

 yes

The communication “

Move to position height 0…255

” and “

Move 

slats 0…255

” allow you to set the absolute position values. The height 

position object is responsible for the height position of blind. The slat 

position object is responsible for the slat-opening angle. The limit 

position %0 means the blind fully up or slat closed up, %100 means 

the blind fully down or slat closed down. 

Enable communication objects

“Move to/set position1-4” 1 bit

*no

 

 yes

If the parameter selected “

yes

”, “

Move to position 1, 2

”, “

Move 

to position 3, 4

”, “

Set position 1, 2

”, and “

Set position 3, 4

” 1-bit 

telegrams are enabled. The saved or downloaded position can be 

easily changed or called with this communication object. The new 

position is accepted into the devices memory via “

Set position

” 

communication objects.

Overwrite position values during 

download

*no

 

 yes

This parameter is selected the reaction of the position set.

• Set the parameter to “

no

”: 

During storage of a scene, the position values are stored in the 

device. You can protect your custom blind position. 

• Set the parameter to “

yes

”: 

The original ETS parameter values can be reload into the device 

during ETS download operation.

Position 1: Height in % [0…100]

(0% = top; 100% = bottom)

0…

*20

…100

Position 1: Slat in % [0…100]

(0% = top; 100% = bottom)

0…

*20

…100

Position 2: Height in % [0…100]

(0% = top; 100% = bottom)

0…

*40

…100

Position 2: Slat in % [0…100]

(0% = top; 100% = bottom)

0…

*40

…100

Position 3: Height in % [0…100]

(0% = top; 100% = bottom)

0…

*60

…100

Position 3: Slat in % [0…100]

(0% = top; 100% = bottom)

0…

*60

…100

Position 4: Height in % [0…100]

(0% = top; 100% = bottom)

0…

*80

…100

Position 4: Slat in % [0…100]

(0% = top; 100% = bottom)

0…

*80

…100

These parameters define the blind preset height/slat position. Slat 

positions are only visible when the blind type is selected “

Venetian 

blind

”.

CONTENTS

Содержание 0 026 72

Страница 1: ...ch Sensor parameter 10 7 5 2 a Switch Dim Sensor parameter 11 7 5 2 a Switch Dim Sensor parameter continued 11 7 5 3 a Blind Sensor parameter 11 7 5 4 a Value Forced Operation parameter 12 7 6 Enable...

Страница 2: ...n parameter 23 7 10 2 A B1 Status Message parameter 24 7 10 3 A B1 Automatic Operation parameter 25 7 10 4 A B1 Direct Mode parameter 25 7 11 Function Chart 26 7 12 Object Description 26 7 12 1 Genera...

Страница 3: ...ut x4 AC Blind x2 DC Blind x1 2 Point valve x2 3 point valve x2 Suitable for switching resistive capacitive and inductive loads as well as fluorescent lamp loads according to EN 60 669 A single switch...

Страница 4: ...4123EN 1 Updated Created 18 01 2021 Cat No s 0 026 72 73 74 76 78 79 KNX controller multi application DIN 4 CONNECTION 0 026 72 73 AC Motor D2 NA Fan1 Fan2 Fan3 4 CONNECTION continued 0 026 74 AC Moto...

Страница 5: ...ted 18 01 2021 Cat No s 0 026 72 73 74 76 78 79 KNX controller multi application DIN 4 CONNECTION continued 0 026 76 AC Motor AC Motor DC Motor F G DC Motor F G 4 CONNECTION continued 0 026 78 79 AC M...

Страница 6: ...S4 or higher Important A detailed information about parameter configuration can be found in Product Manual of device Installation and commissioning of device may only be implemented by trained electri...

Страница 7: ...100 1 bit CW 98 Output A1 Staircase lighting duration 7 007 2 byte CRW Output A Output A B Move to position height 0 255 5 001 1 byte CW Fan A B1 Switch speed 3 1 001 1 bit CW Control input Fault con...

Страница 8: ...e sent freely within a period Note If the value of the object cannot be sent in the time of a period The object is buffered for the next period time The buffered object will be updated if the object v...

Страница 9: ...valuate the transmitted scene address and switches the output to the stored scene value A scene is activated when it receives its scene number at the scene object The storing of the current channel va...

Страница 10: ...is distinction between short and long operation The contact type of the push button attached to the channel is adjusted here Cyclic transmission of object no switch OFF switch ON always This paramete...

Страница 11: ...operation STOP telegram sends at the end of operation Brightness change on every sent telegram 100 6 25 1 56 This parameter is only visible with the Dimming steps options This parameter is cyclically...

Страница 12: ...op command is sent such as STOP Lamella adj UP or STOP Lamella adj DOWN 1 Shutter MOVE UP STOP Lamella UP 2 Shutter MOVE DOWN STOP Lamella DOWN 2 button stepping On operation Stop lamella adjustment T...

Страница 13: ...n shutter blind DC fan coil valve control individually Both output group can be combined into one DC blind In DC blind operation the four relay contacts of the device can be used to control electrical...

Страница 14: ...bus voltage return Behavior bus voltage failure keep position open contact close contact When the bus voltage fails the device set the wanted switching state of the output The relay can be open close...

Страница 15: ...mber of pre warning and time for pre warning interval The warning function is for warning that the staircase lighting time run out and the lights are switched off soon In the warning lights short turn...

Страница 16: ...B General parameter continued Behavior after ETS programming or after ETS reset Behavior bus voltage failure no reaction up down stop position 1 2 3 4 approach position This parameter can be used to c...

Страница 17: ...e Trigger reference movement communication object is visible The reference movement is triggered via this communication object In long time slight inaccuracies can occur so the upper and lower end pos...

Страница 18: ...This function allows you set a height position or slat position directly using with communication object Enable communication objects Move to pos Height Move slat 0 255 no yes The communication Move t...

Страница 19: ...havior in case of rain alarm Behavior in case of frost alarm no reaction up down stop position 1 position 2 position 3 position 4 individual position When the alarm is activated the blind moves this p...

Страница 20: ...tion communication object is updated After the bus voltage return forced position function set to the parametrized position Set the parameter to no forced position active The forced operation is deact...

Страница 21: ...ING is deactivated Set the parameter to 1 When the telegram is received 1 HEATING operation is activated COOLING is deactivated Monitoring control valves yes no This parameter activate the thermostat...

Страница 22: ...vel time This time is maximum one minute Valve limitation yes no The limitation of the control value limits the height of the control value The limitation is activated when a value is chosen which is...

Страница 23: ...ons Thus initially the number of fan levels required for the connected devices can be defined The number of fan levels can be specified separately for each fan coil channel Controlling the fan levels...

Страница 24: ...ime has elapsed 7 COMMUNICATION OBJECTS continued 7 10 Fan Coil parameter continued 7 10 2 A B1 Status Message parameter Enable communication object Status fan speed x 1 bit yes no The data format for...

Страница 25: ...peed In s 0 65535 0 65535 This parameter defines the dwell time for a fan speed of the fan until it switches to the next higher or lower fan speed 0 no delay time for switching 7 COMMUNICATION OBJECTS...

Страница 26: ...x Des 1 0x00 0 0x80 128 2 0x01 1 0x81 129 3 0x02 2 0x82 130 4 0x03 3 0x83 131 5 0x04 4 0x84 132 6 0x05 5 0x85 133 7 0x06 6 0x86 134 8 0x07 7 0x87 135 9 0x08 8 0x88 136 10 0x09 9 0x89 137 11 0x0A 10 0x...

Страница 27: ...d operation 1 byte 0 255 DPT 5 001 brightness value 2 byte 32768 32767 DPT 7 001 signed value 2 byte 0 65535 DPT 8 001 unsigned value 4 byte float value DPT14 068 temperature 4 byte 0 4294967295 DPT12...

Страница 28: ...or 4 104 Trigger reference movement Output A DTP 1 008 1 bit CW This object is triggered the reference movement If the telegram is received the blind is moved up or down end position Then the blind c...

Страница 29: ...OMMUNICATION OBJECTS continued 7 17 Fan Object Description No Object name Name DTP Type Length Flags 95 Fan speed switch Fan DPT 5 010 1 byte CW This object is used to switch on fan speed via 1 byte o...

Отзывы: