background image

RVE01440DME

220/240V 50Hz

14W

1050lm

4000K

85

110°

0.7

-20°C ~ 35°C

65

Class II

360 detection angle,  

1-8m motion

2.8m mounting height

Adjustable time delay 8 

second ~ 12 minutes

Daylight to night adjustable

6V x 1Ah Ni-Cd 

Greater than 4 years 

normal use

300mm

91mm

1.35kg

3 Years

Model No: 

                                 

Supply Voltage: 

                               

Power Consumption:  

               

Lumen Output:  

                            

CCT: 

               

CRI:  

                                                

Beam Angle:                                          

Power Factor: 

                               

Ta Range: 

           

IP Rating:  

                              

Safety Class:  

            

Detection range:                                  

                                                                    

                                                                  

Time Delay:                                               

                                                                    

Light Level Adjustment:                        

Battery                                      

Battery Life 

                        

                                                  

Diameter:  

                                  

Depth:                                                    

Weight:                                                      

Warranty:                                   

Suitable for mounting on a normally flammable surface

This fitting is not suitable for installation where ambient air temperature 

is above 35°C

Complies with EN60598-1:2008+A11:2009, EN62493:2010, 

EN61547:2009, EN61000-3-3:2008, EN60669-1:1999+A2:2008 

EN61000-3-2:2006+A1:2009+A2:2009, AS/NZS 2293.3

EN5515:2006+A1:2007+A2:2009, 

Optimal mounting height of 2.5m. Turn the dial fully

anticlockwise to select minimum range ( approx. 1m)

and fully clockwise to select maximum range (approx. 8m).
The light can be set to stay ON for any period of time 

between approx. 8sec ( turn fully anticlockwise ) and a 

maximum of 12min ( turn fully clockwise ). Any movement 

detected before this time elapse will re-start the timer. It is 

recommended to select the shortest time for adjusting the 

detection range and for performing the walk test.

Lux levels can be selected anywhere from 2-2000lux. 

Turn the dial fully anticlockwise to select dusk- to-dawn 

operation at about 10lux.Turn it fully clockwise to select 

daylight operation at about 2000lux. The dial must be 

turned fully clockwise when adjusting the detection zone 

and performing the walk test in daylight.

The green led should come on indicating correct battery charge status, 

all LEDs will come on.When supply to the switched live PL is lost, 

battery will operate fitting in emergency mode. Interrupt supply by 

pressing the test switch, the fitting will then operate in emergency mode 

for a short period of time.

Issue 1  250515

VEGA 14W IP65 BULKHEAD, 4000K, PLAIN DIFFUSER, 

MICROWAVE SENSOR, EMERGENCY, GREY & BLACK

RVE01440DME-01, RVE01440DME-04, RVE01440DME-24

Information for the Product user:

1. Please note the requirement to dispose of Waste Electrical & Electronic Equipment separately from household waste (WEEE marked with 

    crossed out wheelie bin symbol). 

2. Please consider your role in contributing to re-use and recycling by returning this product at end of life to a collection centre for waste electrical 

    equipment or a Civic Amenity site, or to a retail outlet from which you are purchasing a replacement.

3. This equipment may contain substances that are hazardous to health and the environment if disposed of carelessly.  It is important that it is   

    separated from normal household waste and recycled in the WEEE chain

4. The “crossed out wheelie bin symbol” on a product indicates this equipment must not be disposed of in normal household waste, but should be    

    disposed of according to local WEEE regulations

The Installation must be carried out by an electrician

LED Group

  

 

Western Retail Park 

         Tel: +353 1 7099000 

Nangor Road 

 

         Fax: +353 1 7099060

Dublin 12  

 

         Email: [email protected] 

Ireland   

 

         Website: www.led.ie

ISO 9001:2008

Q UAL IT Y ASSU RED CO MPANY

1

INSTRUCTION MANUAL

PLEASE READ INSTRUCTION BEFORE COMMENCING INSTALLATION AND RETAIN FOR FUTURE REFERENCES.
! Electrical products can cause death or injury, or damage to property. If in any doubt about the installation or
use of this prodcut, consult a competent electrician
                                                                                                          Note:
Product technical information and specification may change over time without prior notification. For the latest 
technical information please visit our web site www.ledgrouprobus.com or www.ledgrouprobus.com.au or ideal.co.nz

Specifications

Installation

Sensor symbol 

Switch testing

1.  Ensure mains supply is switched off before commencing work

2.  Ensure there is at least 100mm of free space around the 

     luminaire location

3.  Remove diffuser and LED plate from base of the fitting

4.  Drill cable entry and mounting holes in the base

5. Mark appropriate fixing hole positions on wall, check location 

    of buried cables, pipes and other building services before drilling.

6. Feed supply cables to cable entry hole and attach base to surface

7. Write installation date on battery and connect battery

8. Connect wires from unswitched supply to terminals on 

    plate, brown to PL and Blue to N; For fitting always on , link terminal

    “SL” to terminal “PL”, fitting controlled by switch connect switched live

    wire to terminal SL and permanent live to PL.

    Note: if “SL” terminal not connected, fitting works as non-maintained

9. Attached LED plate to the base: align the centre point of the 

    unlock & lock indicator on the tray with the location mark on 

    the base, rotate clockwise so that it is secure

10. Refit trim/ diffuser to base. ( note: ensure that trim and base 

    are aligned )