Robotiq Hand-E Gripper Instruction Manual
4.7.6. Modbus RTU example
This section depicts the example from the Control Logic Example section, when programmed using the Modbus RTU protocol. The
example is typical of a pick and place application. After activating the Gripper, the robot is moved to a pick-up location to grip an
object. It moves again to a second location to release the gripped object.
Step 1: Activation Request ( clear and set rACT)
Request is (clear rAct): 09 10 03 E8 00 03 06 00 00 00 00 00 00 73 30
Bits
Description
09
SlaveID
10
Function Code 16 (Preset Multiple Registers)
03E8
Address of the first register
0003
Number of registers written to
06
Number of data bytes to follow (3 registers x 2 bytes/ register = 6 bytes)
0000
Value to write to register 0x03E9 (ACTION REQUEST = 0x01 and GRIPPER OPTIONS= 0x00): rACT = 1 for "Activate
Gripper"
0000
Value written to register 0x03EA
0000
Value written to register 0x03EB
7330
Cyclic Redundancy Check (CRC)
Response is: 09 10 03 E8 00 03 01 30
Bits
Description
09
SlaveID
10
Function Code 16 (Preset Multiple Registers)
03E8
Address of the first register
0003
Number of written registers
0130
Cyclic Redundancy Check (CRC)
49
Содержание ROBOTIQ HAND-E
Страница 19: ...Robotiq Hand E Gripper Instruction Manual Fig 3 2 Mounting fingertips on holders and then on the racks 19...
Страница 25: ...Robotiq Hand E Gripper Instruction Manual Fig 3 6 RS 485 to USB converter ACC ADT USB RS485 pinout 25...
Страница 30: ...Robotiq Hand E Gripper Instruction Manual Fig 4 1 Hand E control logic overview 30...
Страница 85: ...9 Troubleshooting Section to be populated soon Robotiq Hand E Gripper Instruction Manual 85...
Страница 90: ...Robotiq Hand E Gripper Instruction Manual 1 2 3 IngressProtection Certificate 90...