INSTALLATION &

MAINTENANCE MANUAL

Design and specifications subject to change without notice.

Please refer to 

temperedwater.com

 to ensure most

current data sheet and other design solutions. 

CAUTION: When maintaining and adjusting the 

mixing valve, all fixtures should be isolated from 

use. Lawler Manufacturing Co., Inc. recommends 

that you work safely at all times and in a manner 

consistent with the OSHA Lock/Tagout standard,  

29 CFR 1910.147 and other applicable standards.

temperedwater.com/patents

ASSE 1017 Approved
NST 372 Certified Lead Free

Certified to CSA B125.3

NOTICE!

 

No mixing valve will work satisfactorily if improperly installed. We suggest, therefore, that you read 

these instructions carefully before installing and follow directions as outlined. Handle the mixing valve with care.

Neptune EMX Electronic 

Mixing Valve

WARNING: This product contains chemicals known 

to the State of California to cause cancer and birth 

defects or other reproductive harm.
(Installer: California law requires that this warning 

be given to the consumer.)
For more information: www.oehha.org/prop65

Each system consists of

PI Controller with LED Readout
Fast Immersion Sensor 1/2” NPT
Stainless Steel 3-Way Valve
NEMA 4 Enclosure

Description

EMX is an ASSE 1017 Listed Electronic Tempering Valve 

System used to control domestic hot water temperature. The 

EMX is designed to work in domestic hot water systems a 

return line and a continuously running recirculation pump.
The EMX valve should not be used in a gang shower 

application. Use an ASSE 1069 approved valve for those 

applications.

Features

•   Easy setup, simple 3 button interface

•   Low demand dead zone with adjustable activation point

•   High temperature alarm function

•   Fast sampling rate of sensor input

•   Two valves can be installed in parallel with one controller

•   ModBus communication standard

•   Lead Free valve conforms to NSF/

ANSI 372-2011 requirements

Selection

Valves should be selected based on 

a 5 to 10 PSI pressure drop. The 

valve is typically smaller than the 

system piping for most applications.

Pressure Drop PSI 

 

10 

20 

30

Valve 

Inlet Size 

  CAPACITY GPM

NEPTUNE EMX 075 

 3/4 

 17 

24.3 

34 

43

NEPTUNE EMX 100 

1     

25.5 

37 

52 

64

NEPTUNE EMX 125 

1-1/4 

41.4 

58.6 

83 

101

NEPTUNE EMX 150 

1-1/2 

64.4 

91 

128 

157

NEPTUNE EMX 200 

102 

145 

205 

252

Minimum flowrate 1/4 gpm in properly recirculated system. 
5 gpm minimum recirculation flow rate.

Technical Data

Water Temperature Ranges

Cold Inlet 

39° F to 80° F

Hot Inlet 

120° F to 200° F

Outlet 

95° F to 140° F

Maximum Pressure 

150 PSI

Model 

Size

EMX-075 3/4”
EMX-100 1”
EMX-125 1-1/4”
EMX-150 1-1/2”
EMX-200 2”

WARNING: The EMX is not a safety device.  

It should not be installed as an anti-scald device.  

It is only a temperature control system.
Only professional installers with working 

knowledge of plumbing and electrical systems 

should install the EMX system. Incorrectly installed 

or sized systems will result in improper function of 

the control system