40
8.2
ENERGY EFFICIENCY INFORMATION
The Energy Efficiency data included in the following pages is required by the Ecodesign directive
2009/125/EC and is reported as specified in said directive.
Model: UC 2
Type of condensing: Air-cooled
Refrigerant fluid: R410A
Item
Symbol
Value
Unit
Operating temperature
t
7
ºC
Seasonal energy performance ratio
SEPR
6,24
[-]
Annual electricity consumption
Q
2278
kWh/a
Parameters at full load and reference ambient temperature at rating point A
Rated refrigeration capacity
P
A
1,92
kW
Rated power input
D
A
0,63
kW
Rated energy efficiency ratio
EER
DC,A
3,02
[-]
Parameters at rating point B
Rated refrigeration capacity
P
B
1,79
kW
Rated power input
D
B
0,41
kW
Rated energy efficiency ratio
EER
DC,B
4,37
[-]
Parameters at rating point C
Rated refrigeration capacity
P
C
1,66
kW
Rated power input
D
C
0,28
kW
Rated energy efficiency ratio
EER
DC,C
6,00
[-]
Parameters at rating point D
Rated refrigeration capacity
P
D
1,54
kW
Rated power input
D
D
0,20
kW
Rated energy efficiency ratio
EER
DC,D
7,64
[-]
Other items
Capacity control
Variable
Degradation co-efficient chillers
C
dc
0,90
[-]
GWP of the refrigerant
2088
kg CO
2 eq
(100 years)
Contact details
LAUDA Ultracool S.L.
–
Ctra. Rubí 316,
08228 Terrassa (Barcelona), Spain