WARNING!
Risk of refrigerant escaping from refrigerant circuit
Explosion, fire
Before decommissioning the device or if there is a risk of
freezing, drain the refrigerant circuit on the refrigerating
machine using compressed air or an industrial vacuum
cleaner (watertight). Blow compressed air through the cir-
cuit.
7.2 Maintenance intervals
The maintenance intervals described in the following table must be observed.
The following compulsory maintenance tasks must be performed before
operating the device for prolonged periods.
Interval
Maintenance work
Weekly
Perform an external visual inspection of the drainage system for leaks
Monthly
Inspect the external condition of the device
Inspect the external hoses for material fatigue
Clean the air-cooled condenser
Clean the dirt trap
Check the overtemperature protection
Check the low-level protection
Quarterly
Descale the refrigerating machine and the cooling coil
(a shorter interval must be selected, depending on the water hardness and operating period)
Six monthly
Check the heat transfer liquid
7.3 Cleaning the device
WARNING!
Risk of cleaning agent entering the device
Electric shock
Only use a slightly damp cloth to clean the device.
Please also note the following:
Only use water and detergent to clean the operating unit. Do not use
acetone or solvent as these substances will permanently damage the
plastic surfaces.
Ensure that the device is decontaminated after coming into contact with
hazardous materials.
V6
PRO bath thermostats and circulation thermostats
114 / 156
Содержание P 10
Страница 146: ...V6 PRO bath thermostats and circulation thermostats 146 156 ...
Страница 147: ...V6 PRO bath thermostats and circulation thermostats 147 156 ...
Страница 148: ...V6 PRO bath thermostats and circulation thermostats 148 156 ...
Страница 157: ......
Страница 158: ......
Страница 159: ......