Installation & Operation
NOTE: The
EXP-EMG-EXT-LE6-1L
is designed to be surface mounted to flat surfaces such
as
walls.
I.
Installation
Mounting for this fixture is achieved via
mounting tabs located on the back side
of the light.
The EXP-EMG-2L-LE6 explosion proof
emergency self-testing LED fixture is NOT
a factory sealed fixture. Operators will bring
their own rigid conduit to a junction box and
complete their connects. Cap off any hubs
that are not in use.
Both battery legs
must be
connected
together. This prevents the battery from
draining during storage and transit.
DO
NOT CONNECT HIGH VOLTAGE TO
BATTERY LEGS.
II. Operation
1. Apply AC power to the light. The LED
indicator will turn RED.
2. See wires labeled for connections.
3. Use appropriate methods for wiring
within hazardous areas following all
appropriate NEC codes. Consult an
electrician if unsure.
4.
In the event of power loss, the fixture
will illuminate all lights automatically.
Once power is restored, the lights
will turn off and the batteries will
charge.