Lantronix
LSS2200-8P Install Guide
29
Protection class : IP20
Protection class, with PE connection : I
Overvoltage category acc. to EN 50178, IEC 62103 : III
Pollution degree : 2
Insulation voltage, input–output / input–earth / output–earth : 4 kV AC / 3.5 kV AC / 0.5 kV AC, 1 min
Earth discharge current : < 3.5 mA
MTBF acc. to IEC 61709 / MIL-HDBK-217 :
Protection against inverse voltages from the load : > 500000 h / > 100000 h
Parallel capability (without diode module) : 58...65 V DC
Corrosion-resistant metal housing : yes, max. 3
Separation between units : 0 mm
Height x Width x Depth : 130 x 140 x 150 mm
Weight : 3.4 kg (7.49 Lbs.)
Approvals : CE, cULus, cULus listed C1D2, cURus, RCM, EAC, SEMI F47, CB-scheme, CCC, DNV-GL, TÜV
25172 Connection data (Screw connection), input / output
Number of terminals : 3 (L, N, PE) / 8 (11, 12, 14, +, +, -, -, -)
Rigid wire cross-section : 0.18...6 mm² / 0.5...16 mm2
Flexible wire cross-section : 0.22...4 mm² / 0.5...16 mm2
Wire cross-section AWG : 26...10 / 22...8
Screw terminal torque : 0.5...0.6 Nm / 1.2...1.5 Nm
Insulation stripping length : 6 mm / 6 mm
25172 EMC / shock / vibration
Interference radiation acc. to EN 55022 (Class) : B
Interference immunity tests acc. to : EN 61000-4-2 (ESD), EN 61000-4-3, EN 61000-4-4 (Burst), EN 61000-4-5
(Surge),EN 610004-6 (conducted), EN 61000-4-8 (Fields), EN 61000-4-11 (Dips)
Limiting of mains harmonic currents acc. to : EN 61000-3-2
Shock resistance (in all directions) / Vibration resistance acc. to EN 50178 : 30 g / 2.3 g
25172 Electrical safety
Electrical machinery equipment acc. to : EN 60204
Safety transformers for switched-mode power supplies acc. to : EN 61558-2-16
Installation with electronic equipment acc. to : EN 50178, VDE 0160
Protective isolation / protection against electrical shock : VDE 0100-410 / DIN 57100-410
Bodily protection against dangerous electrical shock : VDE 0106-101
25172 Usage
PROmax power supplies are built-in installation units featuring IP20 protection. They should be installed in an
appropriate enclosure (such as an electrical cabinet or distributor box) which provides a sufficient level of
protection so that live current-carry components cannot be touched and so that dust and water cannot penetrate
the unit.