Operating and  
Installation Instruction 

 

Ultrasonic heat and cooling meter 
ULTRAHEAT®T230

 

 

 

13.07.2020 

Translation 

 

T230 

 

 

Gyr GmbH 

Subject to change without prior notice 

13.07.2020 

 

Note:

  In  the  text  below,  the  term  meter  refers  both  to 

the  heat  meter  and  to  the  cooling  meter  and  the  com-
bined  heat  and  cooling  meter,  unless  otherwise  speci-
fied. 

1. 

General 

1.1 

Use 

The  T230 is used  as a meter  for  heating or  cooling consump-
tion measurement in systems with water. 
The meter consists of a high-tech plastic volume measurement 
unit, two temperature sensors connected in a fixed position and 
an electronic unit that calculates the energy consumption from 
the volume and temperature difference.  
The  meter  combines  modern  microcomputer  technology  with 
innovative  ultrasonic  measuring  technology  for  which  no  me-
chanically moving parts are necessary. 
This  technology  is  thus  wear  free,  robust  and  largely  mainte-
nance  free.  High  precision  and  long-term  stability  guarantee 
precise and equitable cost accounts. 

 

Note:

  The  meter  cannot  be  opened  without  damaging 

the security seal. 

1.2 

General notes 

The meter left the factory in a faultless condition where safety 
is  concerned.  The  manufacturer  will  provide  additional  tech-
nical support on request. Calibration relevant security seals on 
the  meter  must  not  be  damaged  or  removed.  Otherwise,  the 
warranty  and  calibration  validity  of  the  meter  will  no  longer 
apply. 

 

Keep the packaging so that you can transport the meter in 
its original packaging following expiry of the calibration va-
lidity. 

 

Lay all cables at a minimum distance of 500 mm to high 
voltage and high frequency cables.  

 

A relative humidity of < 93% at 25 °C is permissible (without 
condensation). 

 

Avoid  cavitation  in  the  whole  system  due  to  overpressure 
i.e. at least 1 bar at qp and approx. 2 bar at qs (applies for 
approx. 80 °C). 

2. 

Safety 

information’s 

 

The  meters  may  only  be  used  in  building  service 
engineering  plants  and  only  for  the  applications 
described. 

 

The  local  regulations  (installation  etc.)  must  be  ad-
hered to. 

 

The  operating  conditions  according  to  the  type  plate 
must  be  complied  with  during  use.  Non-compliance 
can result in hazardous situations and the expiry of all 
claims  arising  from  liability  for  defects  as  well  as 
liability based on any expressly granted guarantees. 

 

Do not under any circumstances carrying out welding, 
drilling or soldering work close to the meter. 

 

The  meter  is  only  suitable  for  circulating  water  in 
heating systems.

 

 

The meter is not suitable for drinking water.

 

 

Requirements  for  circulating  water  (CEN/TR  16911: 
2016). 

 

Only personnel,  trained in  the installation and opera-
tion  of  meters  in  heating  and  cooling  systems,  may 
install and remove the meter.

 

 

Only install or remove the meter when the pipes are 
pressure-less.

 

 

After installing  the  meter,  check  the  leak-tightness of 
the system.

 

 

Guarantee  and  calibration  validity  will  lapse  if  the 
calibration relevant security seal is broken.

 

 

Only  clean  the  meter  from  outside  with  a  soft,  lightly 
wetted  cloth.  Do  not  use  any  spirit  or  cleaning  sol-
vent.

 

 

As far as disposal is concerned, the meter is a waste 
electronic  appliance  in  the  sense  of  European  Di-
rective  2012/19/EU  (WEEE)  and  it  must  not  be  dis-
posed  of  as  domestic  waste.  The  relevant  national, 
legal  regulations  must  be  observed  as  the  appliance 
must  be  disposed  of  via  the  channels  provided  for 
this purpose.  The  local and currently valid legislation 
must be observed.

 

 

The  meter  contains  lithium  batteries.  Do  not  dispose 
of  the  meter  and  the  batteries  with  domestic  waste. 
Observe the local stipulations and laws on disposal.

 

 

You  can  return  the  lithium  batteries  to  the  manufac-
turer  for  appropriate  disposal  following  use.  When 
shipping please observe legal regulations,  in particu-
lar,  those  governing  the  labelling  and  packaging  of 
hazardous goods.

 

 

Do not open the batteries. Do not bring batteries into 
contact  with  water  or  expose  to  temperatures  above 
80 °C.

 

 

The  meter  does  not  have  any  lightning  protection. 
Ensure  lightning  protection  via  the  in-house  installa-
tion.

 

3. 

Installation 

To install the meter, proceed as follows: 

 

Determine  the  place  of  installation  in  line  with  the  inscrip-
tion on the meter. 

 

Note:

 At a 

heat meter

 

 or combined heat/cooling 

meter  the  mounting  place  of  the  flow  sensor  cold 

side  is  equivalent  to  return 

.  The  mounting 

place of the flow sensor hot side is equivalent to flow 

 

Note: 

At a 

cooling meter

 the mounting place of the 

flow sensor hot side is equivalent to the return 

The  mounting  place  of  the  flow  sensor  cold  side  is 

equivalent to flow 

 

Note:

  At  a  meter  with  an 

adjustable  mounting 

place

 

, the mounting place hot side is displayed 

as 

.  The  mounting  place  cold  side  is  dis-

32 

18 

1

01

 0

03

 k

 

Содержание ULTRAHEAT T230

Страница 1: ...well as liability based on any expressly granted guarantees Do not under any circumstances carrying out welding drilling or soldering work close to the meter The meter is only suitable for circulating water in heating systems The meter is not suitable for drinking water Requirements for circulating water CEN TR 16911 2016 Only personnel trained in the installation and opera tion of meters in heati...

Страница 2: ...th a minimum distance of 10 DN from the T piece This distance ensures a good thorough mixing of the different water temperatures You can install the temperature sensors in T pieces ball valves directly immersed or in pock ets depending on the version The temperature sensor ends must reach to at least the middle of the pipe cross section Note Protect the meter against damage through impacts or vibr...

Страница 3: ... or expose to tempera tures above 80 C Dispose of used batteries at suitable collection points 3 4 Interfaces and Communication The meter is equipped with an optical interface in accordance with EN 62056 21 as standard If the meter is equipped with the option M Bus it is supplied with a 2 wire cable which you can extend by fitting a junction box 3 5 Temperature sensor Note Wires must not be separa...

Страница 4: ...ocks to the fittings and the temperature sen sors The scope of supply includes two self lock seals for sealing a sensor and the connecting fitting Read the meter status for energy volume operation and missing time and note the values Error messages for incorrect installation Error incorrect flow direction negative Check that the flow direction arrows on the volume measurement unit match the flow d...

Страница 5: ...erature 20 60 C Electronic unit Ambient temperature 5 55 C Housing protection rating IP 54 according to EN 60529 Power supply Battery for 6 or 11 years Operation threshold f T 0 2 K Temperature difference T 3 K 80 K Temperature measurement range 0 180 C LCD 7 digits Optical interface Standard EN 62056 21 Communication Optional Separability Always cable length 1 5 m Sensor Type Pt 500 according to ...

Страница 6: ...Landis Gyr GmbH Subject to change without prior notice 13 07 2020 6 10 Declaration of conformity Landis Gyr GmbH Humboldtstraße 64 90459 Nuremberg Germany ...

Отзывы: