1.5 Clearances to Combustible Surfaces
It is of the utmost importance that the installation conforms to the minimum
clearances to combustible surfaces (Material made of or surfaced with wood, compressed
paper, plant fibers, plastics, or other material that can ignite and burn, whether flame proofed
or not, or whether plastered or unplastered). Consult applicable codes and regulations for
precedence. Non-compliance to minimum clearances may result in fire, explosion, personal
injury or death. Minimum Clearances per U.L. Listing:
Front - 24", Sides - 18", Rear - 6", Flue Pipe (Single Wall) - 18"
18” (46 cm) from outer
surface of single-wall flue
tee/pipe in all directions.
6” (45.7 cm) from rear of cabinet.
24” (61 cm) from
front of cabinet.
18” (46 cm) from sides.
Mount to non-combustible flooring.
Minimum Clearances to Combustible Surfaces
NOTE: These are the minimum allowed clearances for fire safety. Leaving additional access space
around the unit will make periodic maintenance easier.