10

2   General Safety Instructions

2.7

Life time

The mission time or life time of the device is 10 years.
In accordance with the DIN EN 61508 the life time is 8 to 12 years under normal operating 

conditions, because electronic components are assumed to have a constant failure rate  

λ

 through this period. After that period the failure rates of the components will increase  

significantly with time (see "bathtub curve" for electronic components).
The life time of 10 years does not mean, that the device will become unsafe after this time 

immediately. The extensive diagnosis of safety related components remains still active. DIN 

EN 61508-2:2011 Note N3 gives the hint, that appropriate measures taken by the  

manufacturer and plant operator can extend the useful lifetime.
The burner control is designed for 250.000 switching cycles with nominal switch loads. For 

normal operation this is equal to 10 years of operation

5

. For industrial use with reduced loads 

and a lower ambient temperature more switching cycles are possible.
Nevertheless, when the device stays in operation after the end of the life time, LAMTEC does 

not guarantees the proper function and all calculated safety values become invalid.

5

 Base on the switching cycles and the corresponding lifetime are EN 13611, DIN EN 298 and an overview from the 

European Control Manufacturers Association (Afecor, www.afecor.org)

Содержание F200K2 IR-1

Страница 1: ...www lamtec de Sensors and Systems for Combustion Engineering Safety Manual F200K...

Страница 2: ......

Страница 3: ...fe State 7 2 4 Scope of Application 7 2 5 Additional Components 7 2 6 Safety Values 8 2 7 Life time 9 3 Installation and Commissioning 10 3 1 Verification 10 4 Operation 12 4 1 Proof Test 12 4 2 Proof...

Страница 4: ...of the device The plant operator is responsible for the correct execution of these operations NOTICE The Safety Manual does not replace the operating and installation manuals of this device It contain...

Страница 5: ...emperature range as defined in Appendix see chapter 7 2 Hints and require ments for installation commissioning operation and verification leads to a loss of the safety integrity and may cause personne...

Страница 6: ...ttention to the possibility of imminent danger If it is not avoided it may result in death or very serious injury The plant including its surroundings could be damaged CAUTION This draws the user s at...

Страница 7: ...robability of failures with no effect not used in SFF calculation HFT Hardware fault tolerance MooN M out of N channel architecture MTBF Mean time between failures MTTR Mean time to repair MTTF Mean t...

Страница 8: ...pses in the event of modifications to the unit The unit s inputs and outputs must be wired according to the specifications in the instruction manual only DANGER The appendix Hints and requirements for...

Страница 9: ...el drift have been used Under special circumstances short circuits have not to be assumed Estimation of common cause factors 2 D 1 The Proof test interval T1 is equivalent to the product mission or li...

Страница 10: ...EN 61511 see 2 4 Scope of Application 3 SFF is relevant for elements subsystems or systems in a complete safety loop This device is always part of a com plete safety loop A SIL calculation of a safety...

Страница 11: ...components remains still active DIN EN 61508 2 2011 Note N3 gives the hint that appropriate measures taken by the manufacturer and plant operator can extend the useful lifetime The burner control is d...

Страница 12: ...he flame detector e g According to EN 61558 2 6 or EN 60950 1 WARNING Use a floating contact which is feeded by the flame detector s 24 V supply for the remote switching of the F200K2 s range Or use a...

Страница 13: ...l for shutting off the safety valve is trig gered off within the period of TS 1 s on safety period Operation at tVOff 1 s after extinc tion of the flame Red LED lights Green LED dark For the IR compac...

Страница 14: ...operation and decrease the average probability of dangerous failure on demand PFDAVG during the defined mission time According to DIN EN 61508 2011 6 the PFDAVG can be calculated by the use of a proof...

Страница 15: ...d completely dangerous voltages can be applied at the cable contacts To execute a basic proof test with a PTC of 70 for the F200K series the following test steps must be executed and approved Disconne...

Страница 16: ...ured while the device is being repaired or a maintenance is ongoing After a repair or a maintenance follow chapter 3 Installation and Commissioning again WARNING Replace the device only by one of the...

Страница 17: ...uctions from the installation manual and ensure the safe operation of the application after that The device should be replaced after the product s mission or life time see chapter 2 7 Life time The de...

Страница 18: ...17 7 Appendix 7 Appendix 7 1 T V Confirmation...

Страница 19: ...18 7 Appendix...

Страница 20: ...19 7 Appendix 7 2 Hints and requirements for installation commissioning operation and verification...

Страница 21: ...20 8 EU Declaration of Conformity 8 EU Declaration of Conformity...

Страница 22: ...21 8 EU Declaration of Conformity...

Страница 23: ...22 8 EU Declaration of Conformity...

Страница 24: ...KG Wiesenstra e 6 D 69190 Walldorf Telefon 49 0 6227 6052 0 Telefax 49 0 6227 6052 57 info lamtec de www lamtec de Publication no DLT7604 19 aEN 006 The information in this publication is subject to t...

Отзывы: