11.1
Technical Data
11.1.1
F130l evaluation device
Housing material: Plastic
The right to make technical changes is reserved.
Fig. 11-1 F130I
Fig. 11-2 dimensions F130I
Input parameters
Auxiliary power/device supply
Supply voltage
1
Factory setting
230
VAC
+10
%
-15
%
or
120
VAC
+10
%
-20
%
Mains frequency
1
47
Hz
...
63
Hz
Power consumption
≤
10
VA
Internal device fusing
50
mAT for 230
V
device
100
mAT for 120
V
device
External device fusing
(mandatory)
min. 500
mAT
max. 4
AT
Ionisation input
Supply voltage
1, 2
(Auxiliary power)
Device supply voltage
Ionisation current
from 1
μ
ADC Flame ON
Mode
Continuous operation capable
1
The product may not be transported, stored or operated outside the specified range. If it is, any guarantees with regard to safety-related functions lose their valid-
ity.
2
The attainable ionisation current at the plant is dependent on the supply voltage. The higher the supply voltage, the higher the sensitivity of the Ionisation lance.
The min. sensitivity of the device of 1
uA is independent on the supply voltage. See also Chapter F130I connection diagram 120
V device.