Appendix
12.3
Circuit Diagrams
NOTICE
in progress
12.4
Accessories
12.4.1 Power Supplies
Measurement of the combustion process characteristics:
This must be documented by measuring the characteristic values for an operation
of the furnace at the shut off limits of the ratio control, as well as the set limits of
the correction circuits (e.g. an O
2
.
The combustion is safe at maximum correctional intervention.
The tolerance time for a deviation between the setpoint and actual value of an
actuator greater than B-Band has been set to 3 s by default for the electronic ratio
control (see prEN12067:2012).
Each actuator is then checked that it does not cause any dangerous process con-
dition at its max. speed within 3 s.
Safe burner operation is checked taking into account of the system tolerances
(notes in prEN 12067-2-2012 Annex CC).
Combustion values (exhaust gas measurement) have been checked and cor-
rected where necessary
*
If any servo motors not mentioned in the test report are used, an assessment of the input of the alternative servo motors shall
be available.
Test description
Date/Tester
Result
/
Power Supply
Description
Type
PSU2415 Power supply 100 ... 240 VAC/24 VDC, 15 W
668R0105
PSU2430 Power supply 100 ... 240 VAC/24 VDC, 30 W
668R0030
PSU2460 Power supply 100 ... 240 VAC/24 VDC, 60 W
668R0060
PSU24150 Power supply 100...240VAC/24VDC, 150 W
668R0150
Содержание CMS
Страница 1: ...www lamtec de Sensors and Systems for Combustion Engineering Manual Combustion Management System CMS...
Страница 2: ......
Страница 42: ...41 4 CMS Components 4 2 5 Terminal Assignment Fig 4 9 AEC TPS 230 VAC or 120 VAC terminal assignment...
Страница 131: ...130 7 Operating Control and Displays 7 1 5 5 Deleting Curves Delete firing rate curve...
Страница 142: ...141 7 Operating Control and Displays Accessing channel information AL1 Fig 7 12 GUI6xx channel information...
Страница 148: ...147 7 Operating Control and Displays Channel configuration AL1 Fig 7 18 Channel configuration...
Страница 154: ...153 7 Operating Control and Displays Accessing the CO O2 settings AL2 Fig 7 24 CO O2 settings menu...
Страница 157: ...156 7 Operating Control and Displays Fig 7 27 System CRCs menu...
Страница 162: ...161 7 Operating Control and Displays Fig 7 32 IP setting menu...
Страница 163: ...162 7 Operating Control and Displays 7 2 8 User Settings Accessing the display settings Fig 7 33 Display settings menu...
Страница 164: ...163 7 Operating Control and Displays Accessing the language settings AL1 Fig 7 34 Language settings menu...
Страница 166: ...165 7 Operating Control and Displays Fig 7 35 Installation...
Страница 167: ...166 7 Operating Control and Displays Fig 7 36 Installation...
Страница 176: ...175 7 Operating Control and Displays Fig 7 49 Loading a protected dataset into the device...
Страница 198: ...197 7 Operating Control and Displays 1 Digital inputs 2 Digital outputs 3 PLC Signals 4 Analogue measurement values...
Страница 202: ...201 7 Operating Control and Displays Replacing a Module Fig 7 81 Module replacement menu...
Страница 271: ...270 10 Maintenance 6 Close the window Connection between PC and CMS is established Indication of the con nected CMS...
Страница 272: ...271 10 Maintenance How to update the firmware in the CMS AL2 1 Open the menu Firmware update 2 Prepare firmware update...
Страница 274: ...273 10 Maintenance Activating the Debug Data 1 Start CMS Remote Software 2 Set device online 3 Show debug data...
Страница 276: ...275 10 Maintenance 3 Restart CMS to complete the update...
Страница 282: ...281 12 Appendix 12 5 EU Declaration of Conformity...
Страница 283: ...282 12 Appendix...