8
3
For Your Safety
3.2
Security Advice - Mounting
•
Compliance with national safety regulations and standards is obligatory at all times.
•
During the assembly and installation process, you must meet the standard requirements
of DIN
VDE
0100, 0550 and DIN
VDE
0722
•
To mount the BT300 basic unit, use screw fittings with an M4 thread (UNC32) and a max-
imum tightening torque of 1.8
Nm for fastening all four fixing points. Keep in mind that
housings have improved mechanical stability when connected on surrounding contact sur-
faces.
Generally connect to an even mounting surface.
NOTICE
Deterioration of the 0.8 Nm servomotor through opening.
Opening the servomotor in a different position other than the cap of the electrical connection,
destroys the servomotor.
The warranty expires.
Open the servomotor at the cap of the electrical connection only.
NOTICE
Damaging the servomotors with 1.2 Nm and 9.0 Nm through opening.
Opening the servomotor destroys the servomotor.
The warranty expires.
Содержание BT300 BurnerTronic
Страница 2: ......
Страница 39: ...38 6 Leakage Test for Main Gas Valves Fig 6 2 Leakage test process diagram...
Страница 46: ...45 7 Technical Data...
Страница 47: ...46 7 Technical Data...