Design and Functions
4.9
Actuator
4.9.1
Operation after Power ON/Long RESET
The actuators have internal position feedback using an incremental encoder. For the automat-
ic adjustment of the position detection, the actuators move to the reference mark set in param-
eters P 455 - P 457. The actuators carry out a transposition test, if activated by P 461. After
passing this test the actuators move to position for the closed damper.
4.9.2
Direction of Rotation/Position Damper Closed
For actuator 662R550... (0.8 Nm) direction of rotation of factory setting is clockwise in quad-
rant from 12 o'clock to 3 o'clock position (P 458 - P 460/channel 1 - channel 3). Adjust ’closed
damper’ position between 12 o’clock and 3 o’clock position as follows:
•
12 o’clock position
P 458 - P 460 = 0
•
3 o’clock position
P 458 - P 460 = 1
For actuator 662R5001...(1,2 Nm), 662R5003...(3 Nm) and 662R5009... (9 Nm) direction of
rotation of factory setting is counter-clockwise in quadrant from the 12 o'clock to 9 o'clock po-
sition (P 458 - P 460/channel 1 - channel 3). Adjust ’closed damper’ position between 12
o’clock and 9 o’clock position as follows:
•
12 o’clock position
P 458 - P 460 = 0
•
9 o’clock position
P 458 - P 460 = 1
4.9.3
Detection of Actuators with Mixed-up Connections
While replacing BT300 make sure actuators are re-connected to the correct channel. Label
the plugs/cables to prevent faults or use the ’transposition test’ in BT300 (parameter 461 = 1).
Automatic transposition detection according to this principle is not possible if channel 1 or
channel 2 are moved to 9 o'clock position (662 R 550...) or 3 o'clock position (662R550...) for
referencing.
To detect transposition of actuators you must implement certain features into burner design.
•
The actuator on channel 1 requires a mechanical stop at an angle of 94° (+- 2°).
•
The actuator on channel 2 requires a mechanical stop at an angle of 104° (+- 2°).
•
The actuator on channel 3 does not need a mechanical stop.
After a long RESET (e.g. after BT300 is switched on), all actuators automatically align position
detection.
Next, channel 1 will not be moved, channel 2 moves on 99° further from 12 o'clock position
and channel 3 moves 108.5° in a clockwise direction.
If actuators are connected to correct channel, none of the actuators will be blocked.
If two actuators are transposed, one of the actuators is blocked and therefore does not reach
its target position. This leads to an error message, and a burner start-up is prevented.
In versions 3.7.0.0. and 3.8.0.0., the detection of inverse connected actuators and referencing
at the 3 o'clock / 9 o'clock position cannot be selected.
From version 3.9.0.0. on, the detection of inverse connected actuators and referencing of
channel 3 at the 3 o'clock / 9 o'clock position can be selected.
Содержание BT300 BurnerTronic
Страница 2: ......
Страница 21: ...20 3 Product Description Fig 3 3 UI300 and Fig 3 4 UI300 and dimensional drawings Fig 3 5 UI300 panel cut out...
Страница 25: ...24 3 Product Description Fig 3 9 Temperature derating BT300 for operation 2000 m NHN...
Страница 49: ...48 4 Design and Functions Fig 4 20 Oil with pilot burner BT300...
Страница 50: ...49 4 Design and Functions Fig 4 21 Oil without pilot burner BT300...
Страница 51: ...50 4 Design and Functions Fig 4 22 Gas with pilot burner and leakage test BT300...
Страница 52: ...51 4 Design and Functions Fig 4 23 Gas without pilot burner and leakage test BT300...
Страница 53: ...52 4 Design and Functions Fig 4 24 Oil without pilot burner BT335...
Страница 54: ...53 4 Design and Functions Fig 4 25 Gas without pilot burner and leakage test BT335...
Страница 59: ...58 4 Design and Functions Fig 4 28 Leakage test process diagram...
Страница 98: ...97 6 Operating Control and Displays...
Страница 99: ...98 6 Operating Control and Displays...
Страница 102: ...101 6 Operating Control and Displays NOTICE If the license agreements are not accepted the installation is aborted...
Страница 103: ...102 6 Operating Control and Displays...
Страница 105: ...104 6 Operating Control and Displays...
Страница 106: ...105 6 Operating Control and Displays...
Страница 107: ...106 6 Operating Control and Displays...
Страница 109: ...108 6 Operating Control and Displays...
Страница 126: ...125 6 Operating Control and Displays 6 3 4 2 Curve Table Fig 6 37 Curve table window...
Страница 246: ...242 10 EU Declaration of Conformity 10 EU Declaration of Conformity...
Страница 247: ...243 10 EU Declaration of Conformity...
Страница 248: ...244 10 EU Declaration of Conformity...