1. The regul. restores factory settings to the charasteristic heating curve settings.
2. Eliminates clock functions
3. Restores user and maintenance level settings
4. Selects automatic control for the operating mode
5. Selects the basic regulator for the regulator type.
6. Identifies the connected sensors and assumes which regulating circuits are in use.
7. Restores factory settings to the tuning values and trend sampling intervals.
8. Selects the 3-point control for actuator control which has a running time of 150s in the H1 and H2 regul.
circuits and the 0...10V control for actuator control which has a running time of 15s in the HW regul. circuit.
9. Selects full effect geothermal heating
10. S
11. Measurements are not read from the net.
12. Erases the telephone number and restores the factory settings to the modem settings.
Original factory settings can be restored with the regulator in the following manner:
ets “ElectricHeat” as an assumption into digital input 2 and “Alarm Dig 1(3)” as an assumption into
digital inputs 1 and 3.
Press the
button to move the cursor to "Special mainten.
The cursor is at "Rstore settings". Press
”.
Press
OK.
OK.
Directions for entering the
maintenance mode are on page 19.
Restore original factory settings:
21.5 °C
0 °C
15 °C
45 °C
1.5 °C
0 °C
0 °C
0 °C
1 °C
20 °C
55.0°C
55°C
10°C
45°C
6 °C
6 °C
User level settings:
Geothermal heating settings:
Room temperature
Temperature drop (supply water)
Min. allowed supply water
Max. allowed supply water
Room compensation ratio
Wind compensation ratio
Sun compensation ratio
Pre-increase
Autumn drying
Valve close
Domestic hot water
Hysteresis of accumulator's lower part
Minimum temp of accumulator's upper part
Hysteresis of accumulator's upper part
Additional hysteresis for electrical heating resistor
control
Minimum temp. of accumulator's lower part
Characteristic heating curve:
80
65
50
35
20
20 0 -20 °C
H1 Curve:
0 = 27°C
+
-20 = 32°C
20 = 21°C
Start function:
2 h/ 0 h
0 h
70 °C
Maintenance level settings:
Outdoor temp. delay H1/ H2
Pre-increase
Domestic hot water alarm
Factory setting:
Geothermal heating:
80
65
50
35
20
20 0 -20 °C
H2 Curve:
0 = 27°C
+
-20 = 30°C
20 = 24°C
Operating mode:
Actuator selection:
Tuning values:
0.5h
10°C
10°C
30°C
30°C
75°C
60min
6°C
30s
Special maintenance settings:
Room temperature delay
H1 Supply water min at 0°C
Domestic hot water alarm delay
H2 Supply water min at 0°C
H1 Supply water min at -20°C
H2 Supply water min at -20°C
The amount of deviation from the setting, which
causes the alarm H1/H2/HW
The duration of the deviation that causes the alarm
Drop in supply water temperature when the exhaust
fan is at ½ speed.
RESTORING SETTING
Restore original
Factory settings
No
Yes
H1 Control modes
Automatic ctrl
Nominal oper.
Reduced oper.
Stand-by
Manual mech.
Manual electr.
Special mainten.
Rstore settings
Settings
Meas. 6 setting
Meas..11 setting
Di1 selection
Dig2 selection
Dig3 selection
LON initializ.
Net measurement
TextMessageSett
H1
3-p./time 150s
0-10V
2-10V
Actuator sel
Start function
H1 Basic regul
H1 Self-learn
H1 Not in use
H2 Basic regul
H2 Self-learn
H2 Not in use
HW Regulator
HW not in use
HW Tuning values
P-area:
70°C
I-time:
18s
D-time:
0.0s
Anticipate:100°C
Quick run:
5%
H1 Tuning values
P-area:
140°C
I-time:
50s
D-time:
0.0s
Geotherm.heat.
GeothHeatFull
GeothHeatPart
Press the
button to move the cursor to "Yes
”.
Press
OK.
HW Control modes
Automatic ctrl
Manual mech.
Manual electr.
Restoring settings:
ORIGINAL FACTORY SETTINGS: