background image

Anerkennungs-Nr.
approval-no.

G 506001

0786 - CPR - 50382

EN 12101-10 : 2005/AC:2007

conform

Zertifikat-Nr.
certificate-no.

B 06 05 22802 024

CNBOP-PIB

2265/2014

AT-0401-0382/2013

CNBOP-PIB

2921/2014

RZN

 

4408-K

Original instructions

AdComNet ready

®

RZN 4408-K

(ZP RZN 4408-K + GEH-KST)

RZN 4404-M

(ZP RZN 4404-M + GEH-KST)

RZN 4408-M

(ZP RZN 4408-M + GEH-KST)

RZN 4408-KS

(ZP RZN 4408-K + GEH-S-RWA)

RZN 4404-MS

(ZP RZN 4404-M + GEH-S-RWA)

RZN 4408-MS

(ZP RZN 4408-M + GEH-S-RWA)

Содержание AdComNet RZN4408-K

Страница 1: ...22802 024 CNBOP PIB 2265 2014 AT 0401 0382 2013 CNBOP PIB 2921 2014 RZN4408 K Original instructions AdComNet ready RZN 4408 K ZP RZN 4408 K GEH KST RZN 4404 M ZP RZN 4404 M GEH KST RZN 4408 M ZP RZN 4...

Страница 2: ...y supply 21 Pictogram explanation 21 Mounting of SHEV control panel with housing GEH KST 22 View motherboard 23 DIP switch settings 24 25 Cables for D H smoke an heat vent systems Wiring plan Paragon...

Страница 3: ...ales partners is at your disposal to professionally install your system and commission it Our partner system guarantees that D H products are installed exclusively by trained and experienced fitters i...

Страница 4: ...ventilation function OPEN can be interrupted depending on the presetting of the service timer Attention Reset of the service timer can be carried out by a specialist company only who has been authoriz...

Страница 5: ...K ZPRZN 4408 M Power supply 230 VAC 50 Hz 230 VAC 50 Hz 230 VAC 50 Hz Rated power 120 VA 240 VA 240 VA Stand by operating 6 8 W 4 5 W 5 W Output voltage 24 V DC Ripple 2 Vss Output rated current 4A 8A...

Страница 6: ...DESENFUMAGEM EVACUARE FUM ROOKAFVOER R G L E M ODDYMIANIE EVACUACI N DE HUMOS DESENFUMAGE ODVOD KOU E ODVOD DYMU BRANDVENTILATION 2 x 1 2 A h 2 x 3 4 A h max 5 mm not included 4x Install batteries Po...

Страница 7: ...i t c h S 5 g r o u p 3 L E D m a l f u n c t i o n l i n e 3 F u s e g r o u p 3 Mains supply Fuse mains LED mains F u s e b a t t e r y B a t t e r y c o n n e c t i o n L E D b a t t e r y f a u l...

Страница 8: ...F OPEN as long as is pressed Drives will only the vent button 6 ON roup CLOSE in case of alarm G The group will be closing in case of alarm 7 ON group fault In case of a e g in case of an interrupted...

Страница 9: ...one line connected and with several groups the fault for example at the last group will not be shown at the first line In this case fault and control must be set at the E slot No indication of the ser...

Страница 10: ...bles are monitored for short circuit and for interruption If line DIP switch 3 is ON the group will in case of a fault automatically triggered and opens Line lenghts and cross sections Cross section m...

Страница 11: ...s been connected L N X 1 5 X 1 5 L N PE 2 8 3 1 6 4 7 5 RT 45 3 2 5 SD O 371 2 8 3 1 6 4 7 5 RT 45 2 8 3 1 6 4 7 5 OK Line T R A K E A a Z b S RZN 440x M RZN 4408 K Line N Control Alarm CLOSE Mot b Mo...

Страница 12: ...4 5 6 7 8 RZN 440x M RZN 4408 K Line Control Alarm CLOSE RM 10kW Alarm Control Line Line CLOSE Failure Shunt connection by customer Alarm Control Line CLOSE Failure n c RT 2 8 3 1 6 4 7 5 RT 45 2 8 3...

Страница 13: ...VdS 2581 For this the drives must be blockage safe All D H drives meet this precondition Otherwise the DIP switches has to be switched on OFF Mounting of the drives Please take mounting informations f...

Страница 14: ...omplete connection of components can cause malfunction Check following connections mains 230 V drives smoke vent buttons when necessary fire detectors and vent buttons See wiring an connection plans p...

Страница 15: ...ternal control Manual opening by smoke vent button Automatic opening by fire detector Automatic opening by external control e g fire alarm system OK SMOKE VENT OK OK RT Reset OFF ON Line RZN OK RT OK...

Страница 16: ...ng in case of non resettable alarm Reset OFF ON Reset 0 I Line click OFF Reset 0 I Line With manual release In case of automatic release by fire detector or external control External control or Operat...

Страница 17: ...line 1 local alarm LED lights continuous 2 BUS alarm LED flashes 3 No alarm LED OFF Only if wind detector or rain detector available Upon triggering of the corresponding sensor the group of the contr...

Страница 18: ...units Functional testing of connected system components Record of competent carrying out of maintenance and designation according to directions Inspection Regular visual inspection between maintenance...