3.4 Troubleshooting
Diagnostics
The boiler is equipped with an advanced self-diagnosis system. In case of a boiler anomaly, the display will flash to-
gether with the fault symbol (detail 22 - fig. 1) indicating the fault code.
There are faults that cause permanent shutdowns (marked with the letter “
A
”): to restore operation just turn the selector
(detail 3 - fig. 1) to RESET (detail 8 - fig. 1) for 1 second or use the RESET on the Remote Timer Control (optional) if
installed; if the boiler fails to start, it is necessary to eliminate the fault indicated by the operation LEDs.
Other faults cause temporary shutdowns (marked with the letter “
F
” with operation automatically restored as soon as
the value returns within the boiler's normal operating range.
Table. 5 - Fault list
Fault
code
Fault
Possible cause
Cure
A01
No burner ignition
No gas
Check the regular gas flow to the boiler and that the
air has been removed from the pipes
Ignition/detection electrode fault
Check the wiring of the electrode and that it is cor-
rectly positioned and free of any deposits
Faulty gas valve
Check and replace the gas valve
Lighting power too low
Adjust the lighting power
A02
Flame present signal with
burner off
Electrode fault
Check the ionisation electrode wiring
Card fault
Check the card
A03
Overtemperature protection
intervention
Heating sensor damaged
Check correct positioning and operation of the heat-
ing sensor
No water circulation in system
Check the circulating pump
Air in system
Vent the system
F05
Air pressure switch (fails to
close contacts within 20 sec.
of fan activation)
Air pressure switch contact open
Check the thermostat
Air pressure switch wiring dis-
connected
Check the wiring
Flue not correctly sized or
obstructed
Replace the flue
A06
No flame after ignition phase
Low pressure in gas system
Check the gas pressure
Burner minimum pressure set-
ting
Check the pressures
F10
Delivery sensor 1 fault
Sensor damaged
Check the wiring or replace the sensor
Wiring shorted
Wiring disconnected
F11
DHW circuit sensor fault
Sensor damaged
Check the wiring or replace the sensor
Wiring shorted
Wiring disconnected
F14
Delivery sensor 2 fault
Sensor damaged
Check the wiring or replace the sensor
Wiring shorted
Wiring disconnected
F34
Power supply voltage under
170V.
Electric mains trouble
Check the electrical system
F35
Mains frequency fault
Electric mains trouble
Check the electrical system
F37
Incorrect system water pres-
sure
System empty
Fill the system
Water pressure switch not con-
nected or damaged
Check the sensor
F39
External probe fault
Probe damaged or wiring
shorted
Check the wiring or replace the sensor
Probe disconnected after acti-
vating sliding temperature
Reconnect the external probe or disable the sliding
temperature
Содержание NINFA 24 MCS
Страница 152: ...NINFA 24 MCS 152 EL B O 90 396 O 92 42 O T 73 23 93 68 O H 89 336 93 68 B A cod 3540F611 05 2007 Rev 00...
Страница 155: ...NINFA 24 MCS 155 EL cod 3540F611 05 2007 Rev 00 5 1 9 1 2 6 1 9 1 3 Comfort Comfort 6 1 9 1 4...
Страница 156: ...NINFA 24 MCS 156 EL cod 3540F611 05 2007 Rev 00 1 3 5 B sez 2 3 6 120 FH AIR PURGE 5 FH 3 1 0 7...
Страница 157: ...NINFA 24 MCS 157 EL cod 3540F611 05 2007 Rev 00 3 1 8 1 4 3 1 9 3 1 1 1 30 C 85 C 45 C 10...
Страница 161: ...NINFA 24 MCS 161 EL cod 3540F611 05 2007 Rev 00 1 0 bar F37 16 16 1 17 1 0 bar 145 29 17 A 120 AIR PURGE FH 1 17...
Страница 169: ...NINFA 24 MCS 169 EL cod 3540F611 05 2007 Rev 00 B H D TEST TEST G faston C faston H D TEST 15 A 25 B E H C G D...
Страница 172: ...NINFA 24 MCS 172 EL cod 3540F611 05 2007 Rev 00 3 2 B sez 4 4 sez 1 3 sez 4 4 3 3 1 bar A...
Страница 173: ...NINFA 24 MCS 173 EL cod 3540F611 05 2007 Rev 00 1 A 2 3 B B 26 27 A B 1 2 3 4 10 15 5 A A A B A B...
Страница 175: ...NINFA 24 MCS 175 EL cod 3540F611 05 2007 Rev 00 F37 F39 A41 F42 F43 H2O F50...
Страница 181: ...NINFA 24 MCS 181 EL cod 3540F611 05 2007 Rev 00 4 6 31 16 32 42 43 44 47 72 81 95 114 136 138 139 Opentherm 278 B...
Страница 182: ......
Страница 183: ......