cod. 3541V620 - Rev. 00 - 05/2021
ALHENA TECH H
To use the desired function refer to table 3.
Table 3- Settings LC32
ON/OFF switch configuration (A fig. 28)
Table 4- Switch A setting
2.6 Fume ducts
B
THE BOILERS MUST BE INSTALLED IN ROOMS THAT
MEET THE FUNDAMENTAL VENTILATION REQUIRE-
MENTS. OTHERWISE THERE IS A DANGER OF AS-
PHYXIA OR POISONING.
READ THE INSTALLATION AND MAINTENANCE IN-
STRUCTIONS BEFORE INSTALLING THE UNIT.
ALSO RESPECT THE DESIGN INSTRUCTIONS
.
IN CASE OF PRESSURES EXCEEDING 200 Pa INSIDE
THE FUME EXHAUST PIPES, THE USE OF CLASS
"H1” FLUES IS MANDATORY.
Important
The unit is a “C-type” with sealed chamber and forced draft; the air inlet and fume outlet must be
connected to one of the extraction/suction systems indicated below. Before proceeding with in-
stallation, check and carefully observe the above instructions. Also, comply with the provisions on
the positioning of wall and/or roof terminals and the minimum distances from windows, walls, ven-
tilation openings, etc.
Parameter b07
Function LC32
Action LC32
0
Manages a secondary gas valve (default)
The contacts are closed when the gas valve (in the boiler) is
powered
1
Use as an alarm output (warning light comes on)
The contacts are closed when there is an error condition
(generic)
2
Manages a water filling valve
The contacts are closed until the water pressure in the hea-
ting circuit is restored to the normal level (after manual or
automatic topping up)
3
Manages a legionella pump
The contacts are closed as long as the anti-legionella protec-
tion is active.
4
Manages a second heating pump
The contacts are closed when the heating mode is active
5
Use as an alarm output (warning light goes off)
The contacts are opened when there is an error condition
(generic)
6
Indicates ignition of the burner
The contacts are closed when the flame is present
7
Manages the trap heater
The contacts are closed when the frost protection mode is
active
DHW configuration
Parameter b06
b01 = 2
b06=0
Contact open disables DHW and re-enables it if closed.
b06=1
Contact open disables heating and displays
F50
. Contact closed enables heating.
b06=2
The contact acts as a room thermostat.
b06=3
Contact open displays
F51
and the boiler continues to operate.
It is used as an alarm.
b06=4
The contact acts as a limit thermostat, if open it displays
F53
and turns off the request.
Содержание ALHENA TECH H
Страница 45: ...45 IT cod 3541V620 Rev 00 05 2021 ALHENA TECH H fig 48 fig 49 fig 50 5 6 6...
Страница 103: ...103 ES cod 3541V620 Rev 00 05 2021 ALHENA TECH H fig 48 fig 49 fig 50 5 6 6...
Страница 160: ...160 RO cod 3541V620 Rev 00 05 2021 ALHENA TECH H fig 48 fig 49 fig 50 5 6 6...
Страница 217: ...217 PL cod 3541V620 Rev 00 05 2021 ALHENA TECH H wygl d 48 wygl d 49 wygl d 50 5 6 6...
Страница 231: ...B 231 EL cod 3541V620 Rev 00 05 2021 ALHENA TECH H...
Страница 232: ...232 EL B CE IT ES RO PL GR cod 3541V620 Rev 00 05 2021 A ALHENA TECH H 8 8...
Страница 235: ...235 EL cod 3541V620 Rev 00 05 2021 ALHENA TECH H 3 2 3 3 Comfort Comfort 27 C 29 C 1 2bar 27 C 29 C 1 2bar...
Страница 236: ...236 EL cod 3541V620 Rev 00 05 2021 ALHENA TECH H 5 C A 5 2 F 4 6 4 5 6 F13 A01 21 C C F12 Alarm...
Страница 237: ...237 EL cod 3541V620 Rev 00 05 2021 ALHENA TECH H 1 3 B 5 7 20 FH 8 280 9 Fh 7 8 9 MAINFW 1 00 DSPFW 1 00 FH 2 Fh 6...
Страница 238: ...238 EL cod 3541V620 Rev 00 05 2021 ALHENA TECH H FH Fh 2 10 0 FH 2 Stop...
Страница 249: ...249 EL cod 3541V620 Rev 00 05 2021 ALHENA TECH H 3 27 27 b09 1 1 2bar 0 7bar F37 3...
Страница 250: ...250 EL cod 3541V620 Rev 00 05 2021 ALHENA TECH H 2 2 1 2 2 B 2009 142 5 C 15 C A 2 3 B...
Страница 253: ...253 EL cod 3541V620 Rev 00 05 2021 ALHENA TECH H 2 5 B B 3 mm 3A...
Страница 254: ...254 EL cod 3541V620 Rev 00 05 2021 ALHENA TECH H B HAR H05 VV F 3x0 75 mm2 8 mm B 230 V...
Страница 262: ...262 EL cod 3541V620 Rev 00 05 2021 ALHENA TECH H B 2 7 B 0 5 lt B 37...
Страница 271: ...271 EL cod 3541V620 Rev 00 05 2021 ALHENA TECH H 1 1 41 2 41 B 1 42 42 OK NO 1 1...
Страница 272: ...272 EL cod 3541V620 Rev 00 05 2021 ALHENA TECH H 1 bar venturi AUTO SETUP AUTO SETUP on page 264 on page 263...
Страница 273: ...273 EL cod 3541V620 Rev 00 05 2021 ALHENA TECH H 1 43 2 43 3 44 4 5 45 43 44 45 1 2 3 4 5...
Страница 274: ...274 EL cod 3541V620 Rev 00 05 2021 ALHENA TECH H A B 1 2 5 49 2 6 50 5 46 47 1...
Страница 275: ...275 EL cod 3541V620 Rev 00 05 2021 ALHENA TECH H 48 49 50 5 6 6...
Страница 276: ...276 EL cod 3541V620 Rev 00 05 2021 ALHENA TECH H 1 2 3 4 51 52 1 1 2 2 3 3 4...
Страница 277: ...277 EL cod 3541V620 Rev 00 05 2021 ALHENA TECH H 1 2 venturi 3 53 54 A 1 2 55 2 1 1 1 2...
Страница 284: ...284 EL cod 3541V620 Rev 00 05 2021 ALHENA TECH H E d d t W D KZ E KZ D W W W W W W Y t EK t t t t t t t t t V...
Страница 285: ...285 EL cod 3541V620 Rev 00 05 2021 ALHENA TECH H E d d t W D KZ E KZ D W W W W W W Y t EK t t t t t t t t t V...
Страница 330: ...330 EN cod 3541V620 Rev 00 05 2021 ALHENA TECH H fig 48 fig 49 fig 50 5 6 6...
Страница 343: ......