background image

(See reverse for additional instructions)

From

Pump

Pressure

Tank

LAKOS
SANDMASTER

Valve

Sand Purge

IMPORTANT: Install SandMaster between

the pump and pressure tank.

Flow to house

Close-Up of Optional

LAKOS Mounting Bracket

Check Valve

Pressure Gauges
(recommended)

Pressure Switch

For effective sand removal, SandMaster must be operated within the recommended flow range for each model (see

product label).

Pipe size is not a factor in model selection.

Use pipe reduction fittings as necessary to connect to

existing piping. Minimum inlet pressure should be at least 15 psi (1 bar). If operating a variable-flow pump,

separator’s performance will be affected at flows below the recommended range for any model; LAKOS recommends

that the separator be sized for the highest expected flow rate (or consult factory for additional considerations). Read

all instructions before proceeding.

Installation Placement

1. Separator must be placed between the pump and pressure tank of a residential water well system.
2. Check valve must be between the pump and separator.
3. Pressure switch must be between the separator and the pressure tank.
4. Any tees or diversions of pump discharge flow (such as to sprinklers or other needs) should be installed after 

the separator’s outlet.

Installation Procedures

1. Remove plastic caps from the inlet, outlet and purge connections.
2. Install separator in the near upright position. For best results, allow at least five pipe diameters of straight 

pipe to and from the separator’s inlet and outlet connections.

3. Support the separator’s weight independently from the inlet/outlet piping. A LAKOS Mounting Bracket Kit is 

recommended, but may be substituted with similar hardware.

SANDMASTER SERIES

Installation & Operating Instructions 

FOR RESIDENTIAL WATER WELL SYSTEMS ONLY

For effective sand removal, SandMaster must be operated within the recommended flow range for each model (see 

product label). 

Pipe size is not a factor in model selection.

  Use pipe reduction fittings as necessary to connect to 

existing piping. Minimum inlet pressure should be at least 15 psi (1 bar). If operating a variable-flow pump, 

separator’s performance will be affected at flows below the recommended range for any model; LAKOS recommends 

that the separator be sized for the highest expected flow rate (or consult factory for additional considerations). 

Read all instructions before proceeding. 

Installation Placement

1. Separator must be placed between the pump and pressure tank of a residential water well system.
2. Check valve must be between the pump and separator.
3. Pressure switch must be between the separator and the pressure tank.
4. Any tees or diversions of pump discharge flow (such as to sprinklers or other needs) should be installed after

  the separator’s outlet.

Installation Procedures

1. Remove plastic caps from the inlet, outlet and purge connections.
2. Install separator in the upright position. For best results, allow at least five pipe diameters of straight
  pipe to and from the separator’s inlet and outlet connections.  

3. Support the separator’s weight independently from the inlet/outlet piping. A LAKOS Mounting Bracket Kit is
  recommended, but may be substituted with similar hardware.

SANDMASTER SERIES

Installation & Operating Instructions 

FOR RESIDENTIAL WATER WELL SYSTEMS ONLY

Residential Purge

Valve Controller

From

Pump

Pressure

Tank

LAKOS

SANDMASTER

SEPARATOR

Valve

(normally

open)

IMPORTANT: Install SandMaster between

the check valve and pressure tank.

Flow to house

Close-Up of Optional LAKOS 

Mounting Bracket (recommended)

Check Valve

Pressure Gauges

(required for monitoring

and troubleshooting)

LAKOS RPV Controller

(recommended)

LAKOS

RPV AutoValve

(recommended)

Sand Purge

Pressure Switch