33
3.
Connect the coolant hoses to the corresponding connections of the unit to be cooled.
The coolant hoses are now connected to the unit.
Disconnect Hoses
The coolant hoses are connected to the unit at the coolant inlet and coolant outlet connections,
labeled with respective symbols.
Figure 19 Disconnecting Hoses
Requirements
Unit prepared for maintenance. Refer to
Preparing the Unit for Maintenance
Coolant cooled to the ambient temperature.
Required Tools and Materials
Absorbent cloth
Bonding agent
Protection caps
Procedure
If the coolant inlet and outlet fittings have quick disconnects installed by the customer,
disconnect the hoses from coolant inlet and outlet fittings on the back of the unit.
If the coolant inlet and outlet fittings do not have quick disconnects or valves, the system must
be drained before disconnecting the hoses from fittings on the back of the unit.
Secure the coolant inlet and coolant outlet connections with protection caps against soiling.
The coolant hoses are now disconnected from the unit.
Содержание Nextreme NRC1200 Series
Страница 1: ...Nextreme Recirculating Chiller Specification and User Manual Part Number 387004848 ...
Страница 17: ...17 Component Locations Figure 2 Isometric Views of Unit Figure 3 Top View ...
Страница 18: ...18 Figure 4 Front View Figure 5 Rear View Figure 6 Side View ...
Страница 37: ...37 Figure 21 Refrigerant Circuit and Coolant Circuit Figure 22 Coolant Circuit and Control Panel ...
Страница 39: ...39 Figure 25 Sensor Wiring Low Voltage ...
Страница 40: ...40 Plumbing Refrigeration Diagram Figure 26 Plumbing and Refrigeration Diagram ...
Страница 43: ...43 Figure 31 Pump Performance of NRC5000 with Cooling Fluids Water and 40 EG W ...
Страница 60: ...60 PCFLT Returns FLT fault or NO FAULTS FOUND PCFLT C Clears Fault Returns FLT Faults Cleared ...
Страница 69: ...69 Declaration of Conformity ...