16
| HPI Combi Flow User Guide |
Version 3.11
www.lafert.com
4. Electrical Installation
4.1. Connection Diagram
All power terminal locations are marked directly on the product.
4.1.1. Electrical Power Connections
L1/L L2/N L3
L1/L L2/N L3
Mains (1 or 3 phase)
U V W
HP Combi Flow Non-Switched
PE
PE
WI
VI
UI
M
Incoming Power Connection
Additional information in section
4.3.
Protective Earth PE Connection
Additional information in section
4.2.
Isolator/Disconnect
Ensure there is at least 30 seconds between each power-on!
Fuses/Circuit Breaker
Additional information in section
4.5.3.
External Line Reactor
Device must not be used with Low Harmonic Drives!
External EMC Filter (optional)
Additional information in section
4.5.
External Output Filter (optional)
Output Choke (load reactor)
dV/dT filter
Sinewave filter
Shielded Motor Cable with PE Connection
Additional information in section
4.6.
NOTE
Enclosed drives are not suitable for rigid conduit system connection.
This manual is intended as a guide for proper installation. Lafert Group cannot assume responsibility for the compliance
or the non-compliance to any code, national, local or otherwise, for the proper installation of this drive or associated
equipment. A hazard of personal injury and/or equipment damage exists if codes are ignored during installation.
This HP Combi Flow contains high voltage capacitors that take time to discharge after removal of the main supply. Before
working on the drive, ensure isolation of the main supply from line inputs. Wait ten (10) minutes for the capacitors to
discharge to safe voltage levels. Failure to observe this precaution could result in severe bodily injury or loss of life.
Only qualified electrical personnel familiar with the construction and operation of this equipment and the hazards involved
should install, adjust, operate, or service this equipment. Read and understand this manual and other applicable manuals
in their entirety before proceeding. Failure to observe this precaution could result in severe bodily injury or loss of life.
4
Elec
trical Installation