LAE electronic AR2-5 Скачать руководство пользователя страница 1

CONFIGURATION PARAMETERS

To get access to the parameter configuration menu, press button 

 

 +   for 5 seconds.

With button 

 

 or   select the parameter to be modified.

Press button 

 

 to display the value.

By keeping button 

 

 pressed, use button   or   to set the desired value. 

When button 

 

 is released, the newly programmed value is stored and the following parameter is displayed.

To exit from the setup, press button 

 

 or wait for 30 seconds. 

PAR RANGE DESCRIPTION

SCL

1°C;

2°C;

°F

Readout scale.

1°C

 (with 

INP

=SN4 only): measuring range  -50/-9.9 … 19.9/80°C

2°C

 : measuring range   -50 … 120°C

°F

 : measuring range   -55 … 240°F

Caution:  upon  changing  the  SCL  value,  it  is  then  absolutely

  necessary  to  re-configure  the 

parameters  relevant  to  the  absolute  and  relative  temperatures  (SPL

SPH

SP

ALA

AHA

,

  etc..).

SPL

-50..SPH

Minimum limit for SP

 

setting.

SPH

SPL.120°

Maximum limit for SP

 

setting.

SP

SPL... SPH Setpoint (value to be maintained in the room). 

C-H

REF; HEA

Refrigerating (REF) or Heating (HEA) control mode.

HYS

1...10°

OFF/ON thermostat differential.

    

SP

SP+HYS

T[°]

ON

OFF

         

SP

SP-HYS

T[°]

ON

OFF

                                                 

CRT

0...30min

Compressor rest time. The output is switched on again after CRT minutes have elapsed since the 

previous switchover. We recommend to set CRT=03 with HYS<2.0°.

CT1

0...30min

Thermostat output run when probe T1 is faulty. With CT1=0 the output will always remain OFF.

CT2

0...30min

Thermostat output stop when probe T1 is faulty. With CT2=0 and CT1>0

  

the output will always be ON.

Example: 

CT1=4, CT2= 6: In case of probe T1 failure, the compressor will cycle 4 minutes ON and 6 minutes OFF.

CSD

0..30min

Compressor stop delay after the door has been opened (active only if DS=YES).

DFM

NON;

TIM;

RTC

Defrost start mode

NON

 : defrost function is disabled 

(the following parameter will be 

FID

).

TIM

 : regular time defrost.

RTC

 : the defrost time is scheduled by parameters DH1, DH2...DH6.

DFT

0...99 hours Time interval among defrosts. When this time has elapsed since the last defrost, a new defrost cycle is started.

DH1

...

DH6

HH.M

Scheduled time for defrost 1 to 6. HH hours from midnight, M tens of minutes. Accepted values go from 

00.0 to 23.5. After “23.5” the value is “---” that means “skipped defrost”. 

Example

: DH1=8.3 means 8.30 

AM.

DLI

-50...120°

Defrost end temperature.

DTO

1...120min

Maximum defrost duration.

DTY

OFF;

ELE;

GAS

Defrost type

OFF

: off cycle defrost (Compressor and Heater OFF).

ELE

: electric defrost (Compressor OFF and Heater ON).

GAS

: hot gas defrost (Compressor and Heater ON).

DPD

0...240sec

Evaporator pump down. At the beginning of defrost, defrost outputs (determined by DTY) are OFF for 

DPD seconds.

DRN

0...30min

Pause after defrost (evaporator drain down time).

DDM

RT;

LT;

 SP;

 DEF

Defrost display mode. During defrost the display will show:

RT

: the real temperature;

LT

 : the last temperature before defrost;

SP

 : the current setpoint value;

DEF

 : “dEF”.

DDY

0...60min

Display delay. The display shows the information selected with parameter DDM

 

during defrost and for 

DDY minutes after defrost termination. 

FID

NO/YES

Fans active during defrost.

FDD

-50...120°

Evaporator fan re-start temperature after defrost.

FTO

0...120min

Maximum evaporator fan stop after defrost.

FCM

NON; 

TMP; 

TIM

Fan mode during thermostatic control.

NON

 : The fans remain ON all the time; 

TMP

 : Temperature-based control. The fans are ON when the compressor is ON. When the compressor 

is turned OFF, the fans remain ON as long as the temperature difference Te-Ta is greater than FDT. The 

fans are turned ON again with FDH differential. (Te = Evaporator temperature, Ta = Air temperature);

TIM

  :  Timed-based  control.  The  fans  are 

ON when the compressor is ON. When the 

compressor is OFF, the fans switch ON and 

OFF according to parameteres FT1, FT2, 

FT3

 

(See Fig.2).

FDT

-120...0°

Evaporator-Air temperature difference for the fans to turn OFF after the compressor has stopped.

FDH

1...120°

Temperature differential for fan re-start.

Example

: FDT

 

= -1, FDH=3. In this case, after the compressor has stopped, the fans are OFF when Te 

> Ta - 1 (FDT), whereas the fans are ON when Te < Ta - 4 (FDT-FDH).

FT1

0...180sec

Fan stop delay after compressor stop. See Fig. 2

FT2

0...30min

Timed fan stop. With FT2=0 the fans remain on all the time.

FT3

0...30min

Timed fan run. With FT3=0, and FT2 > 0, the fans remain off all the time.

ATM

NON;

ABS;

REL

Alarm threshold management.

NON 

: all temperature alarms are inhibited (

the following parameter will be 

ADO

).

ABS 

: the values programmed in ALA

 

and

 

AHA represent the real alarm thresholds.

REL 

: the values programmed in

 

ALR and AHR are alarm differentials referred to SP and SP+HYS.

SP

T[°]

SP+HYS+AHR

SP-ALR

ON

OFF

                

SP

T[°]

SP+AHR

SP-HYS-ALR

ON

OFF

           

ALA

-50... 120°

Low temperature alarm threshold.

AHA

-50... 120°

High temperature alarm threshold. 

ALR

-12... 0°

Low temperature alarm differential. With ALR=0 the low temperature alarm is excluded.

AHR

0... 12°

High temperature alarm differential. With AHR=0 the high temperature alarm is excluded.

ATI

T1; T2; T3

Probe used for temperature alarm detection.

ATD

0... 120min Delay before alarm temperature warning.

Refrigerating control (C-H=REF)

Heating control (C-H=HEA)

OFF

ON

COMPR.

ON

COMPR.

ON

COMPR. OFF

FT1

FT2

FT3

FT3

FT2

Fig.2 Time-optimised fan control (FCM=TIM)

Temperature alarm with relative thresholds,

refrigerating control (ATM=REL, C-H=REF).

Temperature alarm with relative thresholds,

heating control (ATM=REL, C-H=HEA).

TECHNICAL DATA

Power supply

AR2-5.…D   

12Vac/dc ±10%, 3W

AR2-5....W   

110 - 230Vac±10%, 50/60Hz, 3W

Relay output

Compressor  

12(5)A 240Vac

Defrost 

 

7(2)A 240Vac

Evap. Fan   

8(3)A 240Vac

Auxiliary loads  

7(2)A 240Vac

Input

NTC 10KΩ@25°C 

 LAE Part No. SN4...

PTC 1000Ω@25°C 

 LAE Part No. ST1…

Measurement Range

-50…120°C, -55…240°F

-50 / -9.9 … 19.9 / 80°C (NTC10K only)

Measurement accuracy

<0.5°C within the measurement range

Real Time Clock battery

>150 hours; self-rechargeable

Operating conditions

-10 … +50°C; 15%...80% r.H.

CE (Reference norms)

EN60730-1; EN60730-2-9;

EN55022 (Class B);

EN50082-1

VIA PADOVA, 25

31046 ODERZO /TV /ITALY

TEL. +39 - 0422 815320

FAX +39 - 0422 814073

www.lae-electronic.com

E-mail: [email protected]

ADO

0... 30min

Delay before door open alarm warning.

AHM

NON;

ALR;

STP;

Operation in case of high condenser alarm

NON

 : high condenser alarm inhibited.

ALR

 : in case of alarm, “HC” flashes in the display and the buzzer is switched on.

STP 

: in addition to the alarm symbols displayed, the compressor is stopped  and defrosts are suspended.

AHT

-50...120°

Condensation temperature alarm (referred to T3 probe).

ACC

0...52

weeks

Condenser periodic cleaning. When the compressor operation time, expressed in weeks, matches the 

ACC

 value programmed, “CL” flashes in the display. With ACC=0 the condenser cleaning warning is 

disabled and CND disappears from Info Menu.

IISM

NON;

MAN;

HDD;

DI2

Switchover mode to second parameter set

NON

 : inhibition to use the second parameter group (

the following parameter will be 

SB

).

MAN

 : button   switches the two parameter groups over.

HDD

 : automatic switchover to the second parameter group, when heavy duty conditions are detected.

DI2

 : switchover to the second parameter group when the auxiliary DI2 input makes.

IISL

-50... IISH

Minimum limit for IISP

 

setting.

IISH

IISL... 120° Maximum limit for IISP

 

setting.

IISP

IISL... IISH Setpoint in mode 2.

IIHY

1... 10°

OFF/ON differential in mode 2.

IIFC

NON;TMP; 

TIM

Fan control in mode 2. See FCM.

HDS

1...5

Controller sensitivity for the automatic switchover from Group 

I

 to Group 

II

 (1=minimum, 5=maximum).

IIDF

0...99 hours Time interval among defrosts in mode 2.

SB

NO/YES

Stand-by button   enabling. 

DS

NO/YES

Door switch input enabling (closed when door is closed).

DI2

NON;

HPS;

IISM;

RDS;

DSY

DI2 digital input operation

NON

 : digital input 2 not active.

HPS

 : when contact opens a condensing unit high pressure alarm occurs.

IISM

 : when contact makes the controller will use group 2 parameters.

RDS

 : when contact makes a defrost is started (remote control).

DSY 

: defrost synchronisation. The controllers, linked as per Fig. 3, will all start and end defrost together. 

The first controller in defrost will get defrost of all the others started. The last controller ending defrost will 

get defrost of all the others stopped.

LSM

NON;

MAN;

DOR

Light control mode

NON

 : light output not controlled.

MAN

 : light ouput controlled through button   (if OA1=LGT).

DOR

 : light ouput switched on when door is opened (if OA1=LGT).

OA1

NON;

0-1;

LGT; 

2CU;

2EU; 

AL0;

AL1

AUX output operation

NON

 : output disabled (always off).

0-1

 : the relay contacts follow the on/standby state of controller.

LGT

 : output enabled for light control.

2CU

 : output programmed for the control of an auxiliary compressor.

2EU

 : output enabled for the control of the electrical defrost of a second evaporator.

AL0

 : contacts open when an alarm condition occurs.

AL1

 : contacts make when an alarm condition occurs.

2CD

0...120 sec Auxiliary compressor start delay. If OA1=2CU the auxiliary output is switched on  with a delay of 2CD 

seconds after the main compressor has cut-in. Both compressors are turned off at the same time.

INP

SN4; ST1

Temperature sensor selection. With INP=SN4, the probes must be the LAE models SN4..; with INP = 

ST1, the probes must be the LAE models ST1... 

OS1

-12.5..12.5°C Probe T1 offset.

T2

NO/YES

Probe T2 enabling (evaporator).

OS2

-12.5..12.5°C Probe T2 offset.

T3

NON;

DSP;

CND;

2EU

Auxiliary probe T3 operation

NON 

: probe T3 not fitted.

DSP 

: temperature T3 to be displayed.

CND 

: condenser temperature measurement.

2EU 

: second evaporator temperature measurement.

OS3

-12.5..12.5°C Probe 3 offset.

TLD

1...30 min

Delay for minimum temperature (TLO) and maximum temperature (THI) logging.

SIM

0...100

Display slowdown.

ADR

1...255

AR2-5 address for PC communication.

WIRING DIAGRAMS

DISPLAY

During normal operation, the display shows either the temperature measured or one of the following indications:

Defrost in progress

Condenser high pressure alarm

Controller in stand-by

Room high temperature alarm

Condenser clean warning

Room low temperature alarm

 Door open alarm

Probe T1 failure

Condenser high temperature alarm

Probe T2 failure

Probe T3 failure

INFO MENU

The information available in this menu is:

Instant probe 1 temperature

Maximum probe 1 temperature recorded

  

 *

Instant probe 2 temperature

Minimum probe 1 temperature recorded

   

 *

Instant probe 3 temperature

     

 **

Compressor working weeks

Minutes of the Real Time Clock

Keypad state lock

Hours of the Real Time Clock

*: displayed only if enabled (see §Configuration Parameters) **: displayed only if 

ACC

 

> 0

Access to menu and information displayed.

Press and immediately release button 

 

 . 

With button 

 

 or   select the data to be displayed.

Press button 

 

 to display value.

To exit from the menu, press button 

 

 or wait for 10 seconds.

Reset of THI, TLO, CND recordings

With button 

 

 or   select the data to be reset.

Display the value with button 

 

.

While keeping button 

 

 pressed, use button  .

STAND-BY

Button  , when pressed for 3 seconds, allows the controller to be put on a standby or output control to be resumed (with  

SB

=YES only).

KEYPAD LOCK

The keypad lock avoids undesired, potentially dangerous operations, which might be attempted when the controller is operating in 

a public place. In the INFO menu, set parameter 

LOC

=YES to inhibit all functions of the buttons. To resume normal operation of 

keypad, adjust setting so that 

LOC

=NO.

SELECTION OF SECOND PARAMETER GROUP

It’s  possible  to  select  control  parameters  between  two  different  pre-programmed  groups,  in  order  for  the  fundamental  control 

parameters to be adapted quickly to changing needs. Changeover from Group 

I

 to Group 

II

 (and vice versa) may take place 

MANUALLY by pressing button   for 2 seconds (with 

IISM

=MAN), or AUTOMATICALLY when heavy duty conditions are detected 

(with 

IISM

=HDD),  or  when 

IISM

=DI2  and  the AUXILIARY  INPUT  DI2  is  activated  (the  activation  of  DI2  selects  Group 

II

).  If 

IISM

=NON, switchover to Group 

II

 is inhibited. The activation of Group 

II

 is signalled by the lighting up of the relevant LED on the 

controller display.

REAL TIME CLOCK SETTING

The Real Time Clock (RTC) can be adjusted directly from the Info Menu (see Setpoint modification procedure). Tens of minutes 

MIN range from 0 to 59 and Hours HRS range from 0 to 23. If RTC is adjusted just before an upcoming change of hour, verify the 

correctness of the setting again. The RTC does not automatically change upon Daylight Saving Time.

DEFROST

Automatic defrost

. Defrost starts automatically at fixed time-intervals or at programmed scheduled (up to six per 24 hours).

Timed defrost

 

. With 

DFM

=TIM defrosts take place at regular intervals when the timer reaches the value of 

DFT

. For example, 

with 

DFM

=TIM and 

DFT

=06, a defrost will take place every 6 hours.

Scheduled defrost

 

. With 

DFM

=RTC defrost takes place at time specified by 

DH1

...

DH6

. The format of time is “HH.M”, where 

HH are hours and M are tens of minutes. To disable one or more of the 6 scheduled defrosts, assign the value “---” (it is the value 

after “23.5”). Parameters 

DH1

...

DH6

 are accessible both in the setup (see §Configuration Parameters) and by keeping button   

pressed for 4 seconds during normal operation.

Synchronised defrost

 

. With 

DI2

=DSY and when more units (models AR2-5x3xxx only) are linked to each other as per Fig. 

3, synchronised defrosts of all linked controllers will take place. The first controller which will start defrost, will also get all other 

controllers synchronised.

Manual or remote defrost start

 

. If 

DFM

=TIM it’s possible to manually start a defrost, by pressing button   for 4 seconds. If 

DFM

=RTC hold button   down for 4 seconds to display 

DH1

, then press button   again for 4 seconds to manually start a defrost. 

Defrost may be also started remotely, if 

DI2

=RDS, through the making of the auxiliary contact DI2.

Defrost type

. Once defrost has started, Compressor and Defrost outputs are controlled according to parameter 

DTY

. If 

FID

=YES, 

the evaporator fans are active during defrost.

Defrost termination

. The actual defrost duration is influenced by a series of parameters.

Time termination

 

T2

=NO and 

T3

 different from 2EU: the evaporator temperature is not monitored and defrost will last as long 

as time 

DTO

Temperature monitoring of one evaporator

 

T2

=YES and 

T3

 different from 2EU. In this case, if the sensor T2 measures the 

temperature 

DLI

 before the time 

DTO

 elapses, defrost will be terminated in advance.

Temperature monitoring of two evaporators

 

T2

=YES, 

T3

=2EU, 

OAU

=2EU. This function is for the control of two independent 

evaporators and it switches off the individual heating of the evaporator which gets to temperature 

DLI

 first, waiting for the second 

evaporator to get to that temperature before the time 

DTO

 elapses.

Resuming thermostatic cycle

. When defrost is over, if 

DRN

 is greater than 0, all outputs will remain off for 

DRN

 minutes, in 

order for the ice to melt completely and the resulting water to drain. Moreover, if probe T2 is active (

T2

=YES), the fans will re-start 

when the evaporator gets to a temperature lower than 

FDD

; Vice versa, if probe T2 is not active (

T2

=NO) or after defrost has 

come to an end, such condition does not occur by end of the time 

FTO

, after 

FTO

 minutes have elapsed the fans will be switched 

on anyway.

Caution: if  

DFM

=NON or 

C-H

=HEA all defrost functions are inhibited; if 

DFT

=0, automatic defrost functions are excluded. During 

a high pressure alarm, defrost is suspended. During defrost, high temperature alarm is bypassed.

OPERATION

Insert the controller through a hole measuring 71x29 mm.

 

Make sure that electrical connections comply with the paragraph “wiring diagrams”. To reduce the effects of electromagnetic 

 

disturbance, keep the sensor and signal cables well separate from the power wires.

Fix the controller to the panel by means of the suitable clips, by pressingly gently; if fitted, check that the rubber gasket adheres 

 

to the panel perfectly, in order to prevent debris and moisture infiltration to the back of the instrument.

Place the probe T1 inside the room in a point that truly represents the temperature of the stored product.

 

Place the probe T2 on the evaporator where there is the maximum formation of frost.

 

The function of probe T3 is determined by the parameter T3. With 

 

T3

=DSP the probe measures the temperature to be displayed. 

With 

T3

=CND the probe measures the condenser temperature, it must therefore be placed between the fins of the condensing 

unit. With 

T3

=2EU the probe measures the temperature of the second evaporator and it must therefore be placed where there is 

the maximum formation of frost. With 

T3

=NON, the third probe is disabled.

INSTALLATION

Thermostat output
Fan output

Alarm

Defrost output
Activation of 2nd parameter set

Info / Setpoint button.

Fig.1 - Front panel

Manual defrost / Decrease button.

Manual activation / Increase button.
Exit / Stand-by button.

Thank you for having chosen an LAE electronic product. Before installing the instrument, please read this instruction booklet 

carefully in order to ensure safe installation and optimum performance.

DESCRIPTION

INDICATIONS

AR2-5 INSTRUCTIONS FOR USE

SETPOINT : display and modification

Press button 

 

 for at least half second, to display the 

setpoint value.

By keeping button 

 

 pressed, use button   or   to set 

the desired value (adjustment is within the minimum 

SPL

 and 

the maximum 

SPH

 limit).

When button 

 

 is released, the new value is stored.

AR2-5C34W-BG

AUX

7(2)A

7(2)A

12(5)A

12A

8(3)A

5

6

115...230Vac

RS485

data I/O

7

8

AUX

17 18

DI2

-

+

Def sync

24

T3

Aux

T2

T1

Door

3

19 21 20

22

23

2

1

4

19

19

19

21

21

21

20

20

20

22

22

22

23

23

23

5

5

5

6

6

6

17

17

17

18

18

18

DI2

DI2

DI2

24

24

24

T3

T3

T3

3

3

3

7

7

7

8

8

8

2

2

2

1

1

1

AR2-5C34W-BG

AR2-5C34W-BG

AR2-5C34W-BG

4

4

4

AUX

AUX

AUX

T2

T2

T2

T1

T1

T1

Door

Door

Door

data

data

data

remote

remote

remote

-

-

-

+

+

+

Fig.3 Connection for synchronising defrost start and termination

Отзывы: