reference instrument. 

Exit from calibration by pressing button 

 

.

CONFIGURATION PARAMETERS

To get access to the parameter configuration menu, press button 

 

 +    for 5 seconds.

With button  

 

 or  

  select the parameter to be modified.

Press button  

 

 to display the value.

By keeping button  

 

 pressed, use button 

 or    to set the desired value. 

When button  

 

 is released, the newly programmed value is stored and the following parameter is displayed.

To exit from the setup, press button 

 

 or wait for 30 seconds.

PAR

RANGE DESCRIPTION

SCL

1°C;

2°C;

°F

Readout scale (see table of input specifications)

Caution: upon changing the SCL value, it is then absolutely

 necessary to reconfigure the param

-

eters relevant to the absolute and relative temperatures (SPL, SPH, 1SP, 1HY  etc..)

SPL

-50°...SPH

Minimum limit for 1SP setting

SPH

SPL...150° Maximum limit for 1SP setting.

1SP

SPL... SPH Setpoint (value to be maintained in the room).

1CM

HY; PID

Control mode.

With 1CM=HY you select control with hysteresis: parameters 1HY, 1T0 and 1T1 are used.

With 1CM=PID you select a Proportional-Integral-Derivative control mode: parameters 1PB, 1IT, 

1DT, 1AR, 1CT will be used.

1CH

REF; HEA

Refrigerating (REF) or Heating (HEA) control mode.

1CM

=HY

1HY

0...19.9°

OFF/ON thermostat differential. 

 With 1HY=0 the output is always off. 

  

1T0

0...30min

Minimum off time.

After  output  1  has  been  turned  off,  it    remains  inactive  for  1T0  minutes  regardless  of  the 

temperature value measured.

1T1

0...30min

Minimum on time. (

the following parameter will be 1PF

).

After output 1 has been turned on,  it remains active for 1T1 minutes regardless of the temperature 

value measured.

1CM

=PID

1PB

0...19.9°

Proportional bandwidth.   

Temperature control takes place by changing the 

ON time of the output: the closer the temperature 

to the setpoint, the less time of activation. A small 

proportional  band  increases  the  promptness  of 

response of the system to temperature variations, 

but  tends  to  make  it  less  stable.  A  purely 

proportional  control  stabilises  the  temperature 

within  the  proportional  band  but  does  not  cancel 

the deviation from setpoint. 

With 1PB=0 the output is always off.

1IT

0...999s

Integral action time.    

The steady-state error is cancelled by inserting an 

integral action. The integral action time, determines 

the speed with which the steady-state temperature 

is achieved, but a high speed (1IT low) may be the 

cause of overshoot and instability in the response. 

With 1IT=0 the integral control is disabled.

1DT

0...999s

Derivative action time.   

Response  overshoot  may  be  reduced  by  inserting 

a  derivative  Action.  A  high  derivative  action  (1DT 

high)  makes  the  system  very  sensitive  to  small 

temperature  variations  and  causes  instability.  With 

1DT=0 the derivative control is disabled.

1AR

0...100%

Reset of integral action time referred to 1PB

Decreasing the parameter 1AR reduces the integral control action zone, and consequently the 

overshoot (see figure on paragraph 1IT).

1CT

1...255s

Cycle time. 

It’s the period in which the output ON time changes. The quicker the system to be controlled 

reacts to temperature variations, the smaller the cycle time must be, in order to obtain higher 

temperature stability and less sensitivity to load variations.

1PF

ON/OFF

Output state in case of probe failure.

OAU

NON;

THR;

AL0;

AL1

AUX output operation.

NON

 : output disabled (always off). (

the next parameter will be ATM

)

THR

 : output programmed for second thermostat control (

the next parameter will be 2SM

).

AL0

 : contacts open when an alarm condition occurs (

the next parameter will be ATM

).

AL1

 : contacts make when an alarm condition occurs (

the next parameter will be ATM

).

OAU

=THR

2SM

ABS;

REL

Setpoint 2 mode.

Channel 2 setpoint may be absolute (2SM=ABS), or a differential relative to setpoint 1 (2SM=REL)

2SM

=ABS

2SP

SPL...SPH Auxiliary output switchover temperature (

the next parameter will be 2CH

)

 

2SM

=REL

2DF

-19.9...19.9° Temperature differential relative to 1SP. The auxiliary output setpoint is equal to 1SP+2DF

     

ON/OFF refrigerating control 

(

1CM

=HY, 

1CH

=REF)

ON/OFF heating control 

(

1CM

=HY, 

1CH

=HEA)

1SP 1SP+1HY

T[°]

ON

OFF

1SP

1SP-1HY

T[°]

ON

OFF

Time

Temperature

Process

temperature

Overshoot

Steady-state error

1PB

1SP

Time

Temperature

Process

temperature

Overshoot

1PB

1PBx1AR%

integral control

action area

1SP

Time

Temperature

Process

temperature

Overshoot

1PB

1SP

2SP 2SP+2HY T[°]

ON

OFF

2SP

2SP-2HY

T[°]

ON

OFF

ON/OFF control in refrigeration

(2SM=ABS, 2CH=REF)

ON/OFF control in heating

(2SM=ABS, 2CH=HEA)

1SP+2DF

1SP

2DF>0

1SP+2DF+2HY

T[°]

ON

OFF

1SP

1SP+2DF

2DF<0

1SP+2DF-2HY

T[°]

ON

OFF

ON/OFF control in refrigeration. Setpoint 2

relative to setpoint 1 (OAU=THR, 2CH=REF)

ON/OFF control in heating. Setpoint 2

relative to setpoint 1 (OAU=THR, 2CH=HEA)

TECHNICAL DATA

Power supply

AC1-2W…D  

12Vac/dc ±10%, 2W

AC1-2W...E  

230Vac±10%, 50/60Hz, 2W

AC1-2W...U   

115Vac±10%, 50/60Hz, 2W

Relay outputs (AC1-2W..R..)

OUT1 

8(3)A

OUT2 

8(3)A

SSR drive (AC1-2W..F..)

OUT1 

15mA   12Vdc

OUT2  

15mA   12Vdc

Inputs

see table of input specifications

Measurement range

see table of input specifications

Measurement accuracy

see table of input specifications

Operating conditions

-10 … +50°C; 15%...80% r.H.

CE (Reference Norms)

EN60730-1; EN60730-2-9;

EN55022 (Class B); EN50082-1

Front protection

IP55

VIA PADOVA, 25

31046 ODERZO /TV /ITALY

TEL. +39 - 0422 815320

FAX +39 - 0422 814073

www.lae-electronic.com

E-mail: [email protected]

OAU

=THR

2CH

REF; HEA

Refrigerating control (REF) or heating control mode (HEA) for the auxiliary output.

2HY

0...19.9°

Differential of thermostat 2. With 2HY=0 the auxiliary output always remains off.

2T0

0...30min

Minimum off time.

After output 2 has been turned off, it remains inactive for 2T0 minutes regardless of the temperature 

value measured.

2T1

0...30min

Minimum on time.

After output 2 has been turned on, it remains active for 2T1 minutes regardless of the temperature 

value measured.

2PF

ON/OFF

Auxiliary output state in case of probe failure.

ATM

NON;

ABS;

REL

Alarm threshold management.

NON 

: all temperature alarms are inhibited (

the following parameter will be SB

).

ABS 

: the values programmed in ALA and AHA represent the real alarm thresholds.

REL 

: the values programmed in ALR and AHR are alarm differentials referred to 1SP and 1SP+1HY.

ATM

=ABS

ALA

-50°...AHA Low temperature alarm threshold.

AHA

ALA...150° High temperature alarm threshold.

ATM

=REL

ALR

-12.0...0°

Low temperature alarm differential. 

With ALR=0 the low temperature alarm is excluded.

AHR

0...12.0°

High temperature alarm differential. 

With AHR=0 the high temperature alarm is excluded.

ATD

0...120min

Delay before alarm temperature warning.

SB

NO/YES

Stand-by button enabling.

INP

ST1/SN4

Sensor input selection (see table of input specifications).

In the models AC1-2WT... only.

RLO

-19.9...RHI

Minimum range value (

in the models AC1-2WA… only

)

RLO takes the minimum value measured by the transmitter (i.e. the value matching 0V).

RHI

RLO...99.9

Maximum range value (

in the models AC1-2WA… only

)

RHI takes the maximum value measured by the transmitter (i.e. the value matching 1V)

OS1

-12.5...12.5° Probe T1 offset.

TLD

1...30min

Delay for minimum temperature (TLO) and maximum temperature (THI) logging.

SIM

0...100

Display slowdown

ADR

1...255

AC1-2W address for PC communication

INPUT SPECIFICATIONS

MODEL

INPUT

RANGE [MEASUREMENT ACCURACY]

SCL=1°C

SCL=2°C

SCL=°F

AC1-2WA..

0÷1V

RLO÷RHI [< ± 3mV]

---

AC1-2WT...

INP=ST1

PTC 1000 Ω

(LAE ST1..)

-50/-19.9 ÷ 99.9/150°C

[<±0.3°C(-30÷130°),±1°C]

-50 ÷ 150°C 

[<±0.3°C(-30÷130°), ±1°C]

-60 ÷ 300°F 

[< ±0.6°F(-20÷260°),±2°F]

INP=SN4

NTC 10K Ω 

(LAE SN4..)

-40/-19.9 ÷ 99.9/125°C

[<±0.3°C(-40÷100°),±1°C]

-40 ÷ 125°C

[<±0.3°C(-40÷100°),±1°C]

-40 ÷ 260°F

[<±0.6°F(-40÷210°), ±2°F]

WIRING DIAGRAMS

 

 

 

 

 

 

1SP

1SP-ALR

T[°]

ON

OFF

1SP+1HY+AHR

1SP

1SP-1HY-ALR

1SP+AHR

T[°]

ON

OFF

Temperature alarm with relative thresholds, 

refrigerating control (ATM=REL, 1CH=REF)

Temperature alarm with relative thresholds, 

heating control (ATM=REL, 1CH=HEA).

AC1-2WTQ2RE-B

data I/O

230V~

OUT2

8(3)A

OUT1

8(3)A

3

4

8

9

10

6

7

RS485

AC1-2WAQ2RE-A

data I/O

230V~

OUT2

8(3)A

OUT1

8(3)A

3

5

4

8

9

10

6

7

TTL

rH

V

V

IN

V+

V-

DISPLAY

During normal operation, the display shows either the temperature measured or one of the following indications:

Controller in stand-by

Controller in autotuning

Probe T1 overrange or failure

In tuning: timeout1 error

Room high temperature alarm

In tuning: timeout2 error

Room low temperature alarm 

In tuning: overrange error

MENU INFO

The information available in this menu is:

Maximum temperature recorded

Keypad state lock

Minimum temperature recorded

Access to menu and information displayed.

Press and immediately release button 

 

With button 

 

 or    select the data to be displayed.

Press button 

 

 to display value.

To exit from the menu, press button 

 

 or wait for 10 seconds.

Reset of THI, TLO recordings

With button 

 

 or   select the data to be reset.

Display the value with button 

 

.

While keeping button 

 

 pressed, use button 

 . 

CHANNEL 1 SETPOINT 

(display and modification of desired temperature value)

 

Press and release button 

 

 : the LED L1 blinks, the display shows 1SP for 1 second and then the setpoint associated value.

Press buttons 

 

 or 

 to set the desired value (adjustment is within the minimum 

SPL

 and maximum 

SPH

 limit).

To store the new value press button 

 

, or wait for 10 seconds.

To go back to normal mode without saving the new value, press 

 

CHANNEL 2 SETPOINT

With the auxiliary output set as thermostat control (

 

OAU

=THR), it’s possible to modify setpoint 2 during the normal operation 

of the controller.

Press and release button 

 

: the LED L2 blinks, the display shows 2SP for 1 second if setpoint 2 is an absolute threshold 

(

2SM

=ABS), alternatively the display shows 2DF, if setpoint 2 is a threshold relative to setpoint 1 (

2SM

=REL), then the value 

associated to the parameter appears.

Press buttons 

 

 or   to set the desired value.

To store the new value press button 

 

 or wait for 10 seconds.

To go back to normal mode without saving the new value, press 

 

.

STAND-BY

Button 

, when pressed for 3 seconds, allows the controller to be put on a standby or output control to be resumed (with 

SB

=YES only).

KEYPAD LOCK

The keypad lock avoids undesired, potentially dangerous operations, which might be attempted when the controllers is operating 

in a public place. In the INFO menu, set parameter 

LOC

=YES to inhibit all functions of the buttons. To resume normal operation 

of keypad, adjust setting so that 

LOC

=NO.

CONTROLLER AUTOTUNING IN PID MODE

Before starting

In  the  setup  mode  (see  configuration  parameters):  set 

1CM

=PID;  make  sure  that 

1CH

  matches  the  desired  operation  mode 

(

1CH

=REF for refrigerating control, 

1CH

=HEA for heating control); then adjust setpoint 

1SP

 at the desired value.

Start autotuning

During normal operation, keep buttons 

 + 

 pressed for 3 seconds. 1CT blinks on the display. With 

 +   or   set the cycle 

time in order to define the dynamic of the process to be controlled. To abort the autotuning function, press 

; to start autotuning 

press   + 

 or wait for 30 seconds.

During autotuning

During the entire autotuning phase, the display alternates TUN with the actual temperature measured. In case of power failure, 

when power is resumed, after the initial autotest phase, the controller resumes the autotuning function. To abort the autotuning, 

without modifying the previous control parameters, keep button   pressed for 3 seconds. After the autotuning has taken place 

successfully, the controller updates the control parameters and start to control.

Errors

If the autotuning function failed, the display shows an error code:

E1 timeout1 error: the controller could not bring the temperature within the proportional band. Increase 

 

1SP

 in case of heating 

control, vice versa, decrease 

1SP

 in case of refrigerating control and re-start the process.

E2 timeout2 error: the autotuning has not ended within the maximum time allowed (1000 cycle times). Re-start the autotuning 

 

process and set a longer cycle time 

1CT

.

E3 temperature overrange: check that the error was not caused by a probe malfunction, then decrease 

 

1SP

 in case of heating 

control, vice versa increase 

1SP

 in case of refrigerating control and then re-start the process.

To eliminate the error indication and return to the normal mode, press button 

 

.

Control improvement

To reduce overshoot, reduce the integral action reset 

 

1AR

To increase the response speed of the system, reduce the proportional band 

 

1PB

. Caution: doing this makes the system less stable.

To reduce swings in steady-state temperature, increase the integral action time 

 

1IT

; system stability is thus increased, although 

its response speed is decreased.

To increase the speed of response to the variations in temperature, increase the derivative action time 

 

1DT

. Caution: a high 

value makes the system sensitive to small variations and it may be a source of instability.

RECALIBRATION

Have a precision reference thermometer or a calibrator to hand. Ensure that 

 

OS1

=0 and 

SIM

=0.

Switch the controller off then on again.

 

During the auto-test phase, press buttons 

 

   

  and keep them pressed till the controller shows 

0AD

.

With buttons 

 

 and    select 

0AD

 or 

SAD

0AD

 allows a calibration of 0, inserting a constant correction over the whole scale 

of measurement. 

SAD

 allows a calibration of the top part of the measurement scale with a proportional correction between the 

calibration point and 0.

Press 

 

 to display the value and then use    +   or 

  to make the read value coincide with the value measured by the 

OPERATION

The AC1-2W sizes 110x75x55 mm (WxHxD). Fix the plate to the panel using 2 cheese-headed screws with 4 or 5 mm diameter 

 

and  then  apply  the  instrument  casing  to  the  plate. This  should  be  done  for  vertical  panels  and  for  correct  positioning  of  the 

instrument with the outlets at the bottom

.

Make sure that electrical connections comply with the paragraph “wiring diagrams”. To reduce the effects of electromagnetic 

 

disturbance, keep the sensor and signal cables well separate from the power wires. 

Place the probe T1 inside the room in a point that truly represents the temperature of the stored product.

 

INSTALLATION

OUT1

OUT2

L1

L2

Channel 1 output
Channel 2 output

Alarm

Channel 1 setpoint modification
Channel 2 setpoint modification

Fig.1 - Front panel

Thank you for having chosen a LAE electronic product. Before installing the instrument, please read these instructions carefully

to ensure maximum performance and safety.

DESCRIPTION

INDICATION

AC1-2W INSTRUCTION FOR USE

Info / Enter button

Modify Setpoint 1 / Decrease button

Increase / Modify Setpoint 2 button

Exit / Stand-by button