Depending on how many sensors are
connected to the control unit, the display
may show the following message, for
example: "Detecting sensors, 3 sensor(s)
found".
Figure 19. Three sensors found.
Once all sensors have been identified, the
display shows the message: SYSTEM OK.
The idOil separator alarm system is now
operational at factory settings.
Figure 20. All sensors found.
If the control unit does not identify all connected sensors.
Check the sensor connections.
After the check, press the sensor identification button again.
The control unit will look for the sensors for approx. 2 minutes, unless it
has already found three sensors.
The sensor identification can be stopped by pressing the sensor identification button for 5
seconds.
6.2.
Factory settings of the idOil control unit
System settings
Language
English
Date and time
not set
Alarm settings
Alarm buzzer
on
Alarm repeat (24h)
on
Alarm delay for all sensors
10 s
Alarm reset button
on
Inspection settings
Inspection interval counter and
inspection warning
not set
Installation and Operating Instructions | idOil-D30
19/51
DOC001602-EN-4