5.1.3. Connection with a three-sensor cable connector
Figure 14. Connection with a three-sensor cable connector
5.2.
Explanations of connection diagrams
1
Supply voltage 100–240 V AC
(N.B. The device does not include a mains switch, see Section General safety
instructions)
1
= L, phase connector
2
= N, neutral connector
3
= PE, protective earth connector
The supply cable must feature copper wires, 3 x 1.5-2.5 mm2 (L, N,
PE), AWG 16-13. The supply voltage and local supply voltage
tolerances must be taken into account with regard to the cable’s
maximum voltage.
Installation and Operating Instructions | idOil-D30
16/51