Service Manual - NeoTherm 500
Exhaust vent
blocked?
Yes
No
Clear the vents.
Check the bird screens
or terminals.
Check for blocked air intake
and exhaust vents.
Clean with a shop-vac.
Dirty fan?
Yes
No
Switch is OK?
No
Replace switch.
Yes
Problem with
blower?
Yes
No
Heat exchanger
is plugged?
Yes
B19
Checking the Air Pressure Switch - Blower Proving Switch